828 lines
93 KiB
CSV
828 lines
93 KiB
CSV
|
|
Component;Company;Bus type;Value name;Value - factor;Value - unit;Logging rate;sending rate;Info;value - type;size (Byte);Endianness;first Register;BUS address;offset;read/write;function;range
|
|||
|
|
Monitoring;Siemens;Modbus TCP;voltage L1-N;1;V;1s;1s;mean;float;4;;;;1;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;voltage L2-N;1;V;1s;1s;mean;float;4;;;;3;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;voltage L3-N;1;V;1s;1s;mean;float;4;;;;5;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;voltage L1-L2;1;V;1s;1s;mean;float;4;;;;7;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;voltage L2-L3;1;V;1s;1s;mean;float;4;;;;9;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;voltage L3-L1;1;V;1s;1s;mean;float;4;;;;11;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;current L1;1;A;1s;1s;mean;float;4;;;;13;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;current L2;1;A;1s;1s;mean;float;4;;;;15;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;current L3;1;A;1s;1s;mean;float;4;;;;17;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;apparent power L1;1;VA;1s;1s;mean;float;4;;;;19;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;apparent power L2;1;VA;1s;1s;mean;float;4;;;;21;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;apparent power L3;1;VA;1s;1s;mean;float;4;;;;23;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;active power L1;1;W;1s;1s;mean;float;4;;;;25;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;active power L2;1;W;1s;1s;mean;float;4;;;;27;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;active power L3;1;W;1s;1s;mean;float;4;;;;29;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;reactive power L1 (Qn);1;var;1s;1s;mean;float;4;;;;31;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;reactive power L2 (Qn);1;var;1s;1s;mean;float;4;;;;33;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;reactive power L3 (Qn);1;var;1s;1s;mean;float;4;;;;35;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;power factor L1;1;;1s;1s;mean;float;4;;;;37;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;power factor L2;1;;1s;1s;mean;float;4;;;;39;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;power factor L3;1;;1s;1s;mean;float;4;;;;41;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;THD voltage L1-L2;1;%;1s;1s;mean;float;4;;;;43;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;THD voltage L2-L3;1;%;1s;1s;mean;float;4;;;;45;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;THD voltage L3-L1;1;%;1s;1s;mean;float;4;;;;47;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;reserved;;;;;;;;;;;49;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;reserved;;;;;;;;;;;51;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;reserved;;;;;;;;;;;53;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;line frequency;1;Hz;1s;1s;mean;float;4;;;;55;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;3-phase average voltage L-N ;1;V;1s;1s;mean;float;4;;;;57;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;3-phase average voltage L-L ;1;V;1s;1s;mean;float;4;;;;59;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;3-phase average current L-L ;1;A;1s;1s;mean;float;4;;;;61;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;total apparent power;1;VA;1s;1s;mean;float;4;;;;63;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;total active power;1;W;1s;1s;mean;float;4;;;;65;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;total reactive power;1;var;1s;1s;mean;float;4;;;;67;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;total power factor;1;;1s;1s;mean;float;4;;;;69;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;amplitude unbalance of voltage;1;%;1s;1s;mean;float;4;;;;71;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;amplitude unbalance of current;1;%;1s;1s;mean;float;4;;;;73;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum voltage L1-N;1;V;1s;1s;mean;float;4;;;;75;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum voltage L2-N;1;V;1s;1s;mean;float;4;;;;77;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum voltage L3-N;1;V;1s;1s;mean;float;4;;;;79;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum voltage L1-L2;1;V;1s;1s;mean;float;4;;;;81;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum voltage L2-L3;1;V;1s;1s;mean;float;4;;;;83;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum voltage L3-L1;1;V;1s;1s;mean;float;4;;;;85;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum current L1;1;A;1s;1s;mean;float;4;;;;87;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum current L2;1;A;1s;1s;mean;float;4;;;;89;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum current L3;1;A;1s;1s;mean;float;4;;;;91;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum apparent power L1;1;VA;1s;1s;mean;float;4;;;;93;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum apparent power L2;1;VA;1s;1s;mean;float;4;;;;95;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum apparent power L3;1;VA;1s;1s;mean;float;4;;;;97;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum active power L1;1;W;1s;1s;mean;float;4;;;;99;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum active power L2;1;W;1s;1s;mean;float;4;;;;101;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum active power L3;1;W;1s;1s;mean;float;4;;;;103;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum reactive power L1 (Qn);1;var;1s;1s;mean;float;4;;;;105;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum reactive power L2 (Qn);1;var;1s;1s;mean;float;4;;;;107;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum reactive power L3 (Qn);1;var;1s;1s;mean;float;4;;;;109;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum power factor L1;1;;1s;1s;mean;float;4;;;;111;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum power factor L2;1;;1s;1s;mean;float;4;;;;113;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum power factor L3;1;;1s;1s;mean;float;4;;;;115;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum THD voltage L1-L2;1;%;1s;1s;mean;float;4;;;;117;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum THD voltage L2-L3;1;%;1s;1s;mean;float;4;;;;119;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum THD voltage L3-L1;1;%;1s;1s;mean;float;4;;;;121;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;reserved;;;;;;;;;;;123;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;reserved;;;;;;;;;;;125;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;reserved;;;;;;;;;;;127;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum line frequency;1;Hz;1s;1s;mean;float;4;;;;129;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 3-phase average voltage L-N ;1;V;1s;1s;mean;float;4;;;;131;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 3-phase average voltage L-L ;1;V;1s;1s;mean;float;4;;;;133;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 3-phase average current L-L ;1;A;1s;1s;mean;float;4;;;;135;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum total apparent power;1;VA;1s;1s;mean;float;4;;;;137;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum total active power;1;W;1s;1s;mean;float;4;;;;139;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum total reactive power (Qn);1;var;1s;1s;mean;float;4;;;;141;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum total power factor;1;;1s;1s;mean;float;4;;;;143;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal voltage L1-N;1;V;1s;1s;mean;float;4;;;;145;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal voltage L2-N;1;V;1s;1s;mean;float;4;;;;147;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal voltage L3-N;1;V;1s;1s;mean;float;4;;;;149;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal voltage L1-L2;1;V;1s;1s;mean;float;4;;;;151;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal voltage L2-L3;1;V;1s;1s;mean;float;4;;;;153;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal voltage L3-L1;1;V;1s;1s;mean;float;4;;;;155;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal current L1;1;A;1s;1s;mean;float;4;;;;157;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal current L2;1;A;1s;1s;mean;float;4;;;;159;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal current L3;1;A;1s;1s;mean;float;4;;;;161;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal apparent power L1;1;VA;1s;1s;mean;float;4;;;;163;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal apparent power L2;1;VA;1s;1s;mean;float;4;;;;165;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal apparent power L3;1;VA;1s;1s;mean;float;4;;;;167;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal active power L1;1;W;1s;1s;mean;float;4;;;;169;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal active power L2;1;W;1s;1s;mean;float;4;;;;171;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal active power L3;1;W;1s;1s;mean;float;4;;;;173;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal reactive power L1 (Qn);1;var;1s;1s;mean;float;4;;;;175;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal reactive power L2 (Qn);1;var;1s;1s;mean;float;4;;;;177;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal reactive power L3 (Qn);1;var;1s;1s;mean;float;4;;;;179;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal power factor L1;1;;1s;1s;mean;float;4;;;;181;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal power factor L2;1;;1s;1s;mean;float;4;;;;183;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal power factor L3;1;;1s;1s;mean;float;4;;;;185;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal line frequency;1;Hz;1s;1s;mean;float;4;;;;187;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal 3-phase average voltage L-N ;1;V;1s;1s;mean;float;4;;;;189;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal 3-phase average voltage L-L ;1;V;1s;1s;mean;float;4;;;;191;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal 3-phase average current L-L ;1;A;1s;1s;mean;float;4;;;;193;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal total apparent power;1;VA;1s;1s;mean;float;4;;;;195;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal total active power;1;W;1s;1s;mean;float;4;;;;197;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal total reactive power;1;var;1s;1s;mean;float;4;;;;199;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimal total power factor;1;;1s;1s;mean;float;4;;;;201;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit value violations;1;;1s;1s;mean;Unsigned long;4;;;;203;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;PMD diagnostic and status;1;;1s;1s;mean;Unsigned long;4;;;;205;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;digital outputs status;1;;1s;1s;mean;Unsigned long;4;;;;207;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;digital input status;1;;1s;1s;mean;Unsigned long;4;;;;209;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;active rate;1;;1s;1s;mean;Unsigned long;4;;;;211;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;hourmeter;1;s;1s;1s;mean;Unsigned long;4;;;;213;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;universal counter;1;;1s;1s;mean;Unsigned long;4;;;;215;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;change counter of basic parameters;1;;1s;1s;mean;Unsigned long;4;;;;217;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;change counter of all parameters;1;;1s;1s;mean;Unsigned long;4;;;;219;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;change counter limits;1;;1s;1s;mean;Unsigned long;4;;;;221;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;counter all events;1;;1s;1s;mean;Unsigned long;4;;;;223;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;counter of all alarms;1;;1s;1s;mean;Unsigned long;4;;;;225;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;counter on all load output records;1;;1s;1s;mean;Unsigned long;4;;;;227;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;counter for other;1;;1s;1s;mean;Unsigned long;4;;;;229;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;status digital outputs module 1;1;;1s;1s;mean;Unsigned long;4;;;;231;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;status digital input module 1;1;;1s;1s;mean;Unsigned long;4;;;;233;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;status digital outputs module 2;1;;1s;1s;mean;Unsigned long;4;;;;235;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;status digital input module 2;1;;1s;1s;mean;Unsigned long;4;;;;237;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;cos ? L1;1;;1s;1s;mean;float;4;;;;243;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;cos ? L2;1;;1s;1s;mean;float;4;;;;245;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;cos ? L3;1;;1s;1s;mean;float;4;;;;247;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;phase shift angle L1;1;<3B>;1s;1s;mean;float;4;;;;249;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;phase shift angle L2;1;<3B>;1s;1s;mean;float;4;;;;251;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;phase shift angle L3;1;<3B>;1s;1s;mean;float;4;;;;253;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;phase angle L1-L2;1;<3B>;1s;1s;mean;float;4;;;;255;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;phase angle L2-L3;1;<3B>;1s;1s;mean;float;4;;;;257;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;phase angle L1-L3;1;<3B>;1s;1s;mean;float;4;;;;259;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;THD voltage L1;1;%;1s;1s;mean;float;4;;;;261;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;THD voltage L2;1;%;1s;1s;mean;float;4;;;;263;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;THD voltage L3;1;%;1s;1s;mean;float;4;;;;265;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;THD current L1;1;%;1s;1s;mean;float;4;;;;267;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;THD current L2;1;%;1s;1s;mean;float;4;;;;269;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;THD current L3;1;%;1s;1s;mean;float;4;;;;271;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;distortion power L1;1;A;1s;1s;mean;float;4;;;;273;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;distortion power L2;1;A;1s;1s;mean;float;4;;;;275;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;distortion power L3;1;A;1s;1s;mean;float;4;;;;277;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;total reactive power L1 (Qtot);1;var;1s;1s;mean;float;4;;;;279;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;total reactive power L2 (Qtot);1;var;1s;1s;mean;float;4;;;;281;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;total reactive power L3 (Qtot);1;var;1s;1s;mean;float;4;;;;283;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP; reactive power L1 (Q1);1;var;1s;1s;mean;float;4;;;;285;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP; reactive power L1 (Q1);1;var;1s;1s;mean;float;4;;;;287;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP; reactive power L1 (Q1);1;var;1s;1s;mean;float;4;;;;289;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;voltage unbalance;1;%;1s;1s;mean;float;4;;;;291;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;current unbalance;1;%;1s;1s;mean;float;4;;;;293;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;neutral conductor current;1;A;1s;1s;mean;float;4;;;;295;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;total reactive power (Qtot);1;var;1s;1s;mean;float;4;;;;297;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;total reactive power (Q1);1;var;1s;1s;mean;float;4;;;;299;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean voltage L1-N;1;V;1s;1s;mean;float;4;;;;301;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean voltage L2-N;1;V;1s;1s;mean;float;4;;;;303;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean voltage L3-N;1;V;1s;1s;mean;float;4;;;;305;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean voltage L1-L2;1;V;1s;1s;mean;float;4;;;;307;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean voltage L2-L3;1;V;1s;1s;mean;float;4;;;;309;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean voltage L3-L1;1;V;1s;1s;mean;float;4;;;;311;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean current L1;1;A;1s;1s;mean;float;4;;;;313;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean current L2;1;A;1s;1s;mean;float;4;;;;315;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean current L3;1;A;1s;1s;mean;float;4;;;;317;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean apparent power L1;1;VA;1s;1s;mean;float;4;;;;319;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean apparent power L2;1;VA;1s;1s;mean;float;4;;;;321;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean apparent power L3;1;VA;1s;1s;mean;float;4;;;;323;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean active power L1;1;W;1s;1s;mean;float;4;;;;325;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean active power L2;1;W;1s;1s;mean;float;4;;;;327;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean active power L3;1;W;1s;1s;mean;float;4;;;;329;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean reactive power L1 (Qn);1;var;1s;1s;mean;float;4;;;;331;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean reactive power L2 (Qn);1;var;1s;1s;mean;float;4;;;;333;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean reactive power L3 (Qn);1;var;1s;1s;mean;float;4;;;;335;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean total reactive power L1 (Qtot);1;var;1s;1s;mean;float;4;;;;337;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean total reactive power L2 (Qtot);1;var;1s;1s;mean;float;4;;;;339;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean total reactive power L3 (Qtot);1;var;1s;1s;mean;float;4;;;;341;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean reactive power L1 (Q1);1;var;1s;1s;mean;float;4;;;;343;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean reactive power L2 (Q1);1;var;1s;1s;mean;float;4;;;;345;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean reactive power L3 (Q1);1;var;1s;1s;mean;float;4;;;;347;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean power factor L1;1;;1s;1s;mean;float;4;;;;349;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean power factor L2;1;;1s;1s;mean;float;4;;;;351;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean power factor L3;1;;1s;1s;mean;float;4;;;;353;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean total apparent power;1;VA;1s;1s;mean;float;4;;;;355;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean total active power;1;W;1s;1s;mean;float;4;;;;357;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean total reactive power (Qn);1;var;1s;1s;mean;float;4;;;;359;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean total reactive power (Qtot);1;var;1s;1s;mean;float;4;;;;361;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean total reactive power (Q1);1;var;1s;1s;mean;float;4;;;;363;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean total power factor;1;;1s;1s;mean;float;4;;;;365;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;shared on mean neutral conductor current;1;A;1s;1s;mean;float;4;;;;367;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;process hourmeter;1;s;1s;1s;mean;Unsigned long;4;;;;369;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;universal counter 2;1;;1s;1s;mean;Unsigned long;4;;;;371;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;pulse counter 0;1;;1s;1s;mean;Unsigned long;4;;;;373;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;pulse counter 02;1;;1s;1s;mean;Unsigned long;4;;;;375;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;pulse counter 03;1;;1s;1s;mean;Unsigned long;4;;;;377;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;pulse counter 04;1;;1s;1s;mean;Unsigned long;4;;;;379;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;pulse counter 05;1;;1s;1s;mean;Unsigned long;4;;;;381;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;pulse counter 06;1;;1s;1s;mean;Unsigned long;4;;;;383;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;pulse counter 07;1;;1s;1s;mean;Unsigned long;4;;;;385;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;pulse counter 08;1;;1s;1s;mean;Unsigned long;4;;;;387;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;pulse counter 09;1;;1s;1s;mean;Unsigned long;4;;;;389;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;pulse counter 10;1;;1s;1s;mean;Unsigned long;4;;;;391;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;total power factor reference in the current period;1;;1s;1s;mean;float;4;;;;479;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;total power factor output in the current period;1;;1s;1s;mean;float;4;;;;481;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;timestamp of the current period;1;;1s;1s;mean;timestamp;8;;;;483;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;average apparent power in the current period;1;VA;1s;1s;mean;float;4;;;;489;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;average active power reference in the current period;1;W;1s;1s;mean;float;4;;;;491;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;average reactive power reference in the current period;1;var;1s;1s;mean;float;4;;;;493;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;average active power output in the current period;1;W;1s;1s;mean;float;4;;;;495;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;average reactive power output in the current period;1;var;1s;1s;mean;float;4;;;;497;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;cumulated apparent power in the current period;1;VA;1s;1s;mean;float;4;;;;499;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;cumulated active power reference in the current period;1;W;1s;1s;mean;float;4;;;;501;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;cumulated reactive power reference in the current period;1;var;1s;1s;mean;float;4;;;;503;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;cumulated active power output in the current period;1;W;1s;1s;mean;float;4;;;;505;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;cumulated reactive power output in the current period;1;var;1s;1s;mean;float;4;;;;507;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maxumum active power of the current peroid;1;W;1s;1s;mean;float;4;;;;509;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum active power of the current peroid;1;W;1s;1s;mean;float;4;;;;511;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maxumum reactive power of the current peroid;1;var;1s;1s;mean;float;4;;;;513;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum reactive power of the current peroid;1;var;1s;1s;mean;float;4;;;;515;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;length of the current peroid;1;s;1s;1s;mean;Unsigned long;4;;;;517;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;time since the beginning of the current period;1;s;1s;1s;mean;Unsigned long;4;;;;519;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;actual subinterval duration;1;s;1s;1s;mean;Unsigned long;4;;;;521;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;imformation of the last period;1;;1s;1s;mean;Unsigned long;4;;;;523;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maxumum apparent power of the current peroid;1;VA;1s;1s;mean;float;4;;;;525;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum apparent power of the current peroid;1;VA;1s;1s;mean;float;4;;;;527;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;cumulated active power in respect of the current period;1;W;1s;1s;mean;float;4;;;;529;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;cumulated reactive power in respect of the current period;1;var;1s;1s;mean;float;4;;;;531;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;cumulated active power output in the current period;1;W;1s;1s;mean;float;4;;;;533;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;cumulated reactive power output in the current period;1;var;1s;1s;mean;float;4;;;;535;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum active power of the current period;1;W;1s;1s;mean;float;4;;;;537;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum active power of the current period;1;W;1s;1s;mean;float;4;;;;539;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum reactive power of the current period;1;var;1s;1s;mean;float;4;;;;541;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum reactive power of the current period;1;var;1s;1s;mean;float;4;;;;543;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;date / time;1;;1s;1s;mean;timestamp;8;;;;797;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;related active energy tariff 1;1;Wh;1s;1s;mean;double;8;;;;801;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;related active energy tariff 2;1;Wh;1s;1s;mean;double;8;;;;805;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;delivered active energy tariff 1;1;Wh;1s;1s;mean;double;8;;;;809;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;delivered active energy tariff 2;1;Wh;1s;1s;mean;double;8;;;;813;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;related reactive energy tariff 1;1;varh;1s;1s;mean;double;8;;;;817;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;related reactive energy tariff 2;1;varh;1s;1s;mean;double;8;;;;821;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;delivered reactive energy tariff 1;1;varh;1s;1s;mean;double;8;;;;825;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;delivered reactive energy tariff 2;1;varh;1s;1s;mean;double;8;;;;829;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;translucent energy tariff 1;1;VAh;1s;1s;mean;double;8;;;;833;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;translucent energy tariff 2;1;VAh;1s;1s;mean;double;8;;;;837;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;process active energy;1;Wh;1s;1s;mean;double;8;;;;841;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;process reactive energy;1;varh;1s;1s;mean;double;8;;;;845;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;process translucent energy;1;VAh;1s;1s;mean;double;8;;;;849;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;process active energy - prior measurement;1;Wh;1s;1s;mean;double;8;;;;853;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;process reactive energy - prior measurement;1;varh;1s;1s;mean;double;8;;;;857;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;process translucent energy - prior measurement;1;VAh;1s;1s;mean;double;8;;;;861;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;date / time;1;;1s;1s;mean;Unsigned long;4;;;;2799;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;related active energy tariff 1;1;Wh;1s;1s;mean;float;4;;;;2801;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;related active energy tariff 2;1;Wh;1s;1s;mean;float;4;;;;2803;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;delivered active energy tariff 1;1;Wh;1s;1s;mean;float;4;;;;2805;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;delivered active energy tariff 2;1;Wh;1s;1s;mean;float;4;;;;2807;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;related reactive energy tariff 1;1;varh;1s;1s;mean;float;4;;;;2809;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;related reactive energy tariff 2;1;varh;1s;1s;mean;float;4;;;;2811;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;delivered reactive energy tariff 1;1;varh;1s;1s;mean;float;4;;;;2813;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;delivered reactive energy tariff 2;1;varh;1s;1s;mean;float;4;;;;2815;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;translucent energy tariff 1;1;VAh;1s;1s;mean;float;4;;;;2817;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;translucent energy tariff 2;1;VAh;1s;1s;mean;float;4;;;;2819;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;process active energy;1;Wh;1s;1s;mean;float;4;;;;2821;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;process reactive energy;1;varh;1s;1s;mean;float;4;;;;2823;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;process translucent energy;1;VAh;1s;1s;mean;float;4;;;;2825;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;process active energy - prior measurement;1;Wh;1s;1s;mean;float;4;;;;2827;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;process reactive energy - prior measurement;1;varh;1s;1s;mean;float;4;;;;2829;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;process translucent energy - prior measurement;1;VAh;1s;1s;mean;float;4;;;;2831;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum voltage L1-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;3001;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum voltage L2-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;3007;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum voltage L3-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;3013;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum voltage L1-L2 with time;1;V;1s;1s;mean;float + timestamp;12;;;;3019;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum voltage L2-L3 with time;1;V;1s;1s;mean;float + timestamp;12;;;;3025;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum voltage L3-L1 with time;1;V;1s;1s;mean;float + timestamp;12;;;;3031;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum current L1 with time;1;A;1s;1s;mean;float + timestamp;12;;;;3037;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum current L2 with time;1;A;1s;1s;mean;float + timestamp;12;;;;3043;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum current L3 with time;1;A;1s;1s;mean;float + timestamp;12;;;;3049;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum apparent power L1 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;3055;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum apparent power L2 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;3061;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum apparent power L3 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;3067;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum active power L1 with time;1;W;1s;1s;mean;float + timestamp;12;;;;3073;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum active power L2 with time;1;W;1s;1s;mean;float + timestamp;12;;;;3079;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum active power L3 with time;1;W;1s;1s;mean;float + timestamp;12;;;;3085;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum reactive power L1 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3091;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum reactive power L2 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3097;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum reactive power L3 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3103;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum total reactive power L1 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3109;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum total reactive power L2 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3115;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum total reactive power L3 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3121;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum reactive power L1 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3127;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum reactive power L2 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3133;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum reactive power L3 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3139;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum power factor L1 with time;1;;1s;1s;mean;float + timestamp;12;;;;3145;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum power factor L2 with time;1;;1s;1s;mean;float + timestamp;12;;;;3151;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum power factor L3 with time;1;;1s;1s;mean;float + timestamp;12;;;;3157;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum THD voltage L1-L2 based on the fundamental frequency with time;1;%;1s;1s;mean;float + timestamp;12;;;;3163;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum THD voltage L2-L3 based on the fundamental frequency with time;1;%;1s;1s;mean;float + timestamp;12;;;;3169;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum THD voltage L3-L1 based on the fundamental frequency with time;1;%;1s;1s;mean;float + timestamp;12;;;;3175;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum cos ? L1 with time;1;cos ?_L1;1s;1s;mean;float + timestamp;12;;;;3199;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum cos ? L2 with time;1;cos ?_L2;1s;1s;mean;float + timestamp;12;;;;3205;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum cos ? L3 with time;1;cos ?_L3;1s;1s;mean;float + timestamp;12;;;;3211;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum phase shift angle L1 with time;1;<3B>;1s;1s;mean;float + timestamp;12;;;;3217;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum phase shift angle L2 with time;1;<3B>;1s;1s;mean;float + timestamp;12;;;;3223;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum phase shift angle L3 with time;1;<3B>;1s;1s;mean;float + timestamp;12;;;;3229;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum phase angle L1-L2 with time;1;<3B>;1s;1s;mean;float + timestamp;12;;;;3235;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum phase angle L2-L3 with time;1;<3B>;1s;1s;mean;float + timestamp;12;;;;3241;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum phase angle L1-L3 with time;1;<3B>;1s;1s;mean;float + timestamp;12;;;;3247;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum THD voltage L1 with time;1;%;1s;1s;mean;float + timestamp;12;;;;3253;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum THD voltage L2 with time;1;%;1s;1s;mean;float + timestamp;12;;;;3259;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum THD voltage L3 with time;1;%;1s;1s;mean;float + timestamp;12;;;;3265;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum THD current L1 with time;1;%;1s;1s;mean;float + timestamp;12;;;;3271;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum THD current L2 with time;1;%;1s;1s;mean;float + timestamp;12;;;;3277;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum THD current L3 with time;1;%;1s;1s;mean;float + timestamp;12;;;;3283;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum distortion power L1 with time;1;A;1s;1s;mean;float + timestamp;12;;;;3289;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum distortion power L2 with time;1;A;1s;1s;mean;float + timestamp;12;;;;3295;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum distortion power L3 with time;1;A;1s;1s;mean;float + timestamp;12;;;;3301;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum line frequency with time;1;;1s;1s;mean;float + timestamp;12;;;;3307;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 3-phase average voltage L-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;3313;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 3-phase average voltage L-L with time;1;V;1s;1s;mean;float + timestamp;12;;;;3319;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 3-phase average current with time;1;A;1s;1s;mean;float + timestamp;12;;;;3325;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum total apparent power with time;1;VA;1s;1s;mean;float + timestamp;12;;;;3331;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum total active power with time;1;W;1s;1s;mean;float + timestamp;12;;;;3337;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum total reactive power (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3343;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum total power factor with time;1;;1s;1s;mean;float + timestamp;12;;;;3349;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum neutral conductor current with time;1;A;1s;1s;mean;float + timestamp;12;;;;3355;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum total reactive power (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3361;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum total reactive power (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3367;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean voltage L1-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;3373;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean voltage L2-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;3379;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean voltage L3-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;3385;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean voltage L1-L2 with time;1;V;1s;1s;mean;float + timestamp;12;;;;3391;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean voltage L2-L3 with time;1;V;1s;1s;mean;float + timestamp;12;;;;3397;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean voltage L3-L1 with time;1;V;1s;1s;mean;float + timestamp;12;;;;3403;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean current L1 with time;1;A;1s;1s;mean;float + timestamp;12;;;;3409;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean current L2 with time;1;A;1s;1s;mean;float + timestamp;12;;;;3415;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean current L3 with time;1;A;1s;1s;mean;float + timestamp;12;;;;3421;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean apparent power L1 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;3427;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean apparent power L2 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;3433;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean apparent power L3 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;3439;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean active power L1 with time;1;W;1s;1s;mean;float + timestamp;12;;;;3445;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean active power L2 with time;1;W;1s;1s;mean;float + timestamp;12;;;;3451;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean active power L3 with time;1;W;1s;1s;mean;float + timestamp;12;;;;3457;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean reactive power L1 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3463;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean reactive power L2 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3469;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean reactive power L3 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3475;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean total reactive power L1 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3481;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean total reactive power L2 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3487;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean total reactive power L3 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3493;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean reactive power L1 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3499;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean reactive power L2 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3505;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean reactive power L3 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3511;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean power factor L1 with time;1;;1s;1s;mean;float + timestamp;12;;;;3517;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean power factor L2 with time;1;;1s;1s;mean;float + timestamp;12;;;;3523;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean power factor L3 with time;1;;1s;1s;mean;float + timestamp;12;;;;3529;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean total apparent power with time;1;VA;1s;1s;mean;float + timestamp;12;;;;3535;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean total active power with time;1;W;1s;1s;mean;float + timestamp;12;;;;3541;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean total reactive power (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3547;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean total reactive power (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3553;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean total reactive power (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3559;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean total power factor with time;1;;1s;1s;mean;float + timestamp;12;;;;3565;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum shared on mean neutral conductor current with time;1;A;1s;1s;mean;float + timestamp;12;;;;3571;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum voltage L1-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;6001;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum voltage L2-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;6007;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum voltage L3-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;6013;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum voltage L1-L2 with time;1;V;1s;1s;mean;float + timestamp;12;;;;6019;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum voltage L2-L3 with time;1;V;1s;1s;mean;float + timestamp;12;;;;6025;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum voltage L3-L1 with time;1;V;1s;1s;mean;float + timestamp;12;;;;6031;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum current L1 with time;1;A;1s;1s;mean;float + timestamp;12;;;;6037;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum current L2 with time;1;A;1s;1s;mean;float + timestamp;12;;;;6043;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum current L3 with time;1;A;1s;1s;mean;float + timestamp;12;;;;6049;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum apparent power L1 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;6055;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum apparent power L2 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;6061;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum apparent power L3 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;6067;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum active power L1 with time;1;W;1s;1s;mean;float + timestamp;12;;;;6073;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum active power L2 with time;1;W;1s;1s;mean;float + timestamp;12;;;;6079;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum active power L3 with time;1;W;1s;1s;mean;float + timestamp;12;;;;6085;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum reactive power L1 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6091;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum reactive power L2 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6097;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum reactive power L3 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6103;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum total reactive power L1 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6109;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum total reactive power L2 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6115;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum total reactive power L3 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6121;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum reactive power L1 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6127;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum reactive power L2 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6133;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum reactive power L3 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6139;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum power factor L1 with time;1;;1s;1s;mean;float + timestamp;12;;;;6145;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum power factor L2 with time;1;;1s;1s;mean;float + timestamp;12;;;;6151;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum power factor L3 with time;1;;1s;1s;mean;float + timestamp;12;;;;6157;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum cos ? L1 with time;1;cos ?_L1;1s;1s;mean;float + timestamp;12;;;;6163;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum cos ? L2 with time;1;cos ?_L2;1s;1s;mean;float + timestamp;12;;;;6169;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum cos ? L3 with time;1;cos ?_L3;1s;1s;mean;float + timestamp;12;;;;6175;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum phase shift angle L1 with time;1;<3B>;1s;1s;mean;float + timestamp;12;;;;6181;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum phase shift angle L2 with time;1;<3B>;1s;1s;mean;float + timestamp;12;;;;6187;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum phase shift angle L3 with time;1;<3B>;1s;1s;mean;float + timestamp;12;;;;6193;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum phase angle L1-L2 with time;1;<3B>;1s;1s;mean;float + timestamp;12;;;;6199;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum phase angle L2-L3 with time;1;<3B>;1s;1s;mean;float + timestamp;12;;;;6205;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum phase angle L1-L3 with time;1;<3B>;1s;1s;mean;float + timestamp;12;;;;6211;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum line frequency with time;1;;1s;1s;mean;float + timestamp;12;;;;6217;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum 3-phase average voltage L-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;6223;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum 3-phase average voltage L-L with time;1;V;1s;1s;mean;float + timestamp;12;;;;6229;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum 3-phase average current with time;1;A;1s;1s;mean;float + timestamp;12;;;;6235;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum total apparent power with time;1;VA;1s;1s;mean;float + timestamp;12;;;;6241;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum total active power with time;1;W;1s;1s;mean;float + timestamp;12;;;;6247;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum total reactive power (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6253;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum total power factor (Qn) with time;1;;1s;1s;mean;float + timestamp;12;;;;6259;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum neutral conductor current with time;1;A;1s;1s;mean;float + timestamp;12;;;;6265;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum total reactive power (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6271;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum total reactive power (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6277;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean voltage L1-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;6283;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean voltage L2-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;6289;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean voltage L3-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;6295;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean voltage L1-L2 with time;1;V;1s;1s;mean;float + timestamp;12;;;;6301;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean voltage L2-L3 with time;1;V;1s;1s;mean;float + timestamp;12;;;;6307;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean voltage L3-L1 with time;1;V;1s;1s;mean;float + timestamp;12;;;;6313;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean current L1 with time;1;A;1s;1s;mean;float + timestamp;12;;;;6319;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean current L2 with time;1;A;1s;1s;mean;float + timestamp;12;;;;6325;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean current L3 with time;1;A;1s;1s;mean;float + timestamp;12;;;;6331;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean apparent power L1 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;6337;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean apparent power L2 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;6343;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean apparent power L3 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;6349;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean active power L1 with time;1;W;1s;1s;mean;float + timestamp;12;;;;6355;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean active power L2 with time;1;W;1s;1s;mean;float + timestamp;12;;;;6361;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean active power L3 with time;1;W;1s;1s;mean;float + timestamp;12;;;;6367;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean reactive power L1 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6373;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean reactive power L2 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6379;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean reactive power L3 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6385;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean total reactive power L1 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6391;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean total reactive power L2 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6397;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean total reactive power L3 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6403;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean reactive power L1 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6409;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean reactive power L2 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6415;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean reactive power L3 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6421;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean power factor L1 with time;1;;1s;1s;mean;float + timestamp;12;;;;6427;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean power factor L2 with time;1;;1s;1s;mean;float + timestamp;12;;;;6433;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean power factor L3 with time;1;;1s;1s;mean;float + timestamp;12;;;;6439;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean total apparent power with time;1;VA;1s;1s;mean;float + timestamp;12;;;;6445;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean total active power with time;1;W;1s;1s;mean;float + timestamp;12;;;;6451;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean total reactive power (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6457;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean total reactive power (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6463;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean total reactive power (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6469;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean total power factor with time;1;;1s;1s;mean;float + timestamp;12;;;;6475;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;minimum shared on mean neutral conductor current with time;1;A;1s;1s;mean;float + timestamp;12;;;;6481;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;fundamental oscillation voltage L1-N;1;V;1s;1s;mean;float;4;;;;9001;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;fundamental oscillation voltage L2-N;1;V;1s;1s;mean;float;4;;;;9003;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;fundamental oscillation voltage L3-N;1;V;1s;1s;mean;float;4;;;;9005;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;3. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9007;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;3. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9009;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;3. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9011;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;5. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9013;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;5. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9015;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;5. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9017;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;7. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9019;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;7. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9021;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;7. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9023;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;9. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9025;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;9. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9027;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;9. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9029;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;11. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9031;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;11. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9033;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;11. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9035;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;13. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9037;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;13. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9039;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;13. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9041;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;15. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9043;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;15. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9045;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;15. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9047;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;17. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9049;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;17. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9051;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;17. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9053;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;19. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9055;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;19. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9057;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;19. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9059;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;21. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9061;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;21. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9063;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;21. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9065;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;23. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9067;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;23. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9069;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;23. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9071;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;25. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9073;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;25. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9075;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;25. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9077;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;27. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9079;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;27. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9081;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;27. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9083;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;29. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9085;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;29. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9087;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;29. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9089;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;31. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9091;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;31. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9093;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;31. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9095;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;fundamental oscillation current L1;1;A;1s;1s;mean;float;4;;;;11001;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;fundamental oscillation current L2;1;A;1s;1s;mean;float;4;;;;11003;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;fundamental oscillation current L3;1;A;1s;1s;mean;float;4;;;;11005;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;3. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11007;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;3. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11009;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;3. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11011;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;5. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11013;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;5. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11015;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;5. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11017;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;7. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11019;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;7. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11021;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;7. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11023;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;9. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11025;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;9. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11027;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;9. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11029;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;11. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11031;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;11. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11033;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;11. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11035;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;13. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11037;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;13. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11039;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;13. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11041;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;15. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11043;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;15. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11045;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;15. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11047;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;17. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11049;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;17. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11051;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;17. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11053;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;19. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11055;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;19. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11057;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;19. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11059;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;21. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11061;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;21. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11063;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;21. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11065;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;23. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11067;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;23. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11069;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;23. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11071;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;25. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11073;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;25. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11075;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;25. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11077;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;27. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11079;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;27. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11081;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;27. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11083;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;29. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11085;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;29. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11087;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;29. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11089;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;31. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11091;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;31. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11093;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;31. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11095;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;fundamental oscillation voltage L1-L2;1;V;1s;1s;mean;float;4;;;;22001;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;fundamental oscillation voltage L2-L3;1;V;1s;1s;mean;float;4;;;;22003;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;fundamental oscillation voltage L3-L1;1;V;1s;1s;mean;float;4;;;;22005;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;3. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22007;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;3. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22009;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;3. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22011;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;5. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22013;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;5. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22015;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;5. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22017;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;7. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22019;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;7. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22021;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;7. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22023;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;9. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22025;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;9. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22027;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;9. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22029;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;11. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22031;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;11. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22033;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;11. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22035;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;13. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22037;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;13. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22039;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;13. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22041;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;15. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22043;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;15. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22045;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;15. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22047;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;17. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22049;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;17. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22051;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;17. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22053;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;19. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22055;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;19. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22057;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;19. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22059;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;21. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22061;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;21. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22063;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;21. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22065;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;23. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22067;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;23. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22069;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;23. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22071;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;25. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22073;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;25. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22075;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;25. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22077;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;27. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22079;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;27. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22081;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;27. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22083;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;29. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22085;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;29. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22087;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;29. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22089;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;31. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22091;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;31. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22093;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;31. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22095;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 3. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;12999;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 3. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13005;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 3. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13011;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 5. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13017;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 5. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13023;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 5. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13029;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 7. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13035;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 7. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13041;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 7. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13047;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 9. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13053;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 9. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13059;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 9. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13065;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 11. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13071;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 11. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13077;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 11. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13083;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 13. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13089;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 13. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13095;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 13. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13101;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 15. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13107;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 15. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13113;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 15. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13119;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 17. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13125;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 17. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13131;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 17. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13137;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 19. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13143;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 19. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13149;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 19. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13155;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 21. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13161;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 21. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13167;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 21. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13173;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 23. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13179;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 23. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13185;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 23. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13191;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 25. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13197;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 25. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13203;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 25. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13209;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 27. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13215;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 27. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13221;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 27. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13227;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 29. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13233;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 29. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13239;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 29. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13245;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 31. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13251;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 31. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13257;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 31. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13263;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum fundamental oscillation current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19001;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum fundamental oscillation current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19007;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum fundamental oscillation current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19013;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 3. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19019;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 3. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19025;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 3. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19031;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 5. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19037;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 5. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19043;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 5. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19049;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 7. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19055;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 7. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19061;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 7. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19067;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 9. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19073;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 9. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19079;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 9. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19085;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 11. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19091;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 11. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19097;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 11. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19103;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 13. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19109;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 13. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19115;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 13. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19121;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 15. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19127;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 15. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19133;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 15. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19139;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 17. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19145;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 17. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19151;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 17. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19157;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 19. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19163;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 19. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19169;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 19. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19175;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 21. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19181;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 21. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19187;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 21. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19193;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 23. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19199;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 23. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19205;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 23. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19211;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 25. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19217;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 25. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19223;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 25. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19229;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 27. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19235;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 27. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19241;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 27. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19247;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 29. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19253;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 29. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19259;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 29. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19265;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 31. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19271;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 31. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19277;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;maximum 31. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19283;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;connection type;1;;1s;1s;mean;Unsigned long;4;;;;50001;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;voltage transformer yes/no;1;;1s;1s;mean;Unsigned long;4;;;;50003;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;primary voltage;1;;1s;1s;mean;Unsigned long;4;;;;50005;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;secondary voltage;1;;1s;1s;mean;Unsigned long;4;;;;50007;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;current transformer yes/no;1;;1s;1s;mean;Unsigned long;4;;;;50009;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;primary current;1;;1s;1s;mean;Unsigned long;4;;;;50011;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;secondary current;1;;1s;1s;mean;Unsigned long;4;;;;50013;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;line frequency settings;1;;1s;1s;mean;Unsigned long;4;;;;50017;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;zero point suppression;1;%;1s;1s;mean;float;4;;;;50019;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;under an accrual duration;1;;1s;1s;mean;Unsigned long;4;;;;50021;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;synchronization;1;;1s;1s;mean;Unsigned long;4;;;;50023;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;DI 0.0 usage;1;;1s;1s;mean;Unsigned long;4;;;;50025;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;DI 0.0 pulse edge evaluation;1;;1s;1s;mean;Unsigned long;4;;;;50027;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;DI 0.0 usage of the count information;1;;1s;1s;mean;Unsigned long;4;;;;50029;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;DI 0.0 valency of the counter information;1;;1s;1s;mean;Unsigned long;4;;;;50031;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;DO 0.0 switching groups assignment;1;;1s;1s;mean;Unsigned long;4;;;;50033;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;DO 0.0 usage;1;;1s;1s;mean;Unsigned long;4;;;;50035;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;DO 0.0 limit allocation;1;;1s;1s;mean;Unsigned long;4;;;;50037;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;DO 0.0 pulse edge evaluation;1;;1s;1s;mean;Unsigned long;4;;;;50039;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;DO 0.0 source count signal;1;;1s;1s;mean;Unsigned long;4;;;;50041;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;DO 0.0 valency of the counter information;1;;1s;1s;mean;Unsigned long;4;;;;50043;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;DO 0.0 pulse length;1;;1s;1s;mean;Unsigned long;4;;;;50045;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;conversational language;1;;1s;1s;mean;Unsigned long;4;;;;50047;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;phase labels IEC/UL;1;;1s;1s;mean;Unsigned long;4;;;;50049;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;universal counter 1 source;1;;1s;1s;mean;Unsigned long;4;;;;50051;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;display update cycle;1;;1s;1s;mean;Unsigned long;4;;;;50053;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;display contrast;1;;1s;1s;mean;Unsigned long;4;;;;50055;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;display brightness;1;;1s;1s;mean;Unsigned long;4;;;;50057;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;display brightness is reduced;1;;1s;1s;mean;Unsigned long;4;;;;50059;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;brightness duration;1;;1s;1s;mean;Unsigned long;4;;;;50061;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 0 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50063;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 0 hysteresis;1;%;1s;1s;mean;float;4;;;;50065;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 0 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50067;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 0 source;1;;1s;1s;mean;Unsigned long;4;;;;50071;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 0 value;1;;1s;1s;mean;float;4;;;;50073;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 0 mode ?|< ;1;;1s;1s;mean;Unsigned long;4;;;;50075;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 1 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50077;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 1 hysteresis;1;%;1s;1s;mean;float;4;;;;50079;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 1 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50081;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 1 source;1;;1s;1s;mean;Unsigned long;4;;;;50085;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 1 value;1;;1s;1s;mean;float;4;;;;50087;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 1 mode ?|<;1;;1s;1s;mean;Unsigned long;4;;;;50089;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 2 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50091;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 2 hysteresis;1;%;1s;1s;mean;float;4;;;;50093;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 2 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50095;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 2 source;1;;1s;1s;mean;Unsigned long;4;;;;50099;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 2 value;1;;1s;1s;mean;float;4;;;;50101;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 2 mode ?|< ;1;;1s;1s;mean;Unsigned long;4;;;;50103;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 3 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50105;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 3 hysteresis;1;%;1s;1s;mean;float;4;;;;50107;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 3 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50109;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 3 source;1;;1s;1s;mean;Unsigned long;4;;;;50113;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 3 value;1;;1s;1s;mean;float;4;;;;50115;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 3 mode ?|<;1;;1s;1s;mean;Unsigned long;4;;;;50117;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 4 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50119;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 4 hysteresis;1;%;1s;1s;mean;float;4;;;;50121;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 4 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50123;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 4 source;1;;1s;1s;mean;Unsigned long;4;;;;50127;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 4 value;1;;1s;1s;mean;float;4;;;;50129;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 4 mode ?|< ;1;;1s;1s;mean;Unsigned long;4;;;;50131;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 5 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50133;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 5 hysteresis;1;%;1s;1s;mean;float;4;;;;50135;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 5 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50137;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 5 source;1;;1s;1s;mean;Unsigned long;4;;;;50141;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 5 value;1;;1s;1s;mean;float;4;;;;50143;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 5 mode ?|<;1;;1s;1s;mean;Unsigned long;4;;;;50145;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 6 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50147;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 6 hysteresis;1;%;1s;1s;mean;float;4;;;;50149;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 6 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50151;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 6 source;1;;1s;1s;mean;Unsigned long;4;;;;50155;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 6 value;1;;1s;1s;mean;float;4;;;;50157;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 6 mode ?|< ;1;;1s;1s;mean;Unsigned long;4;;;;50159;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 7 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50161;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 7 hysteresis;1;%;1s;1s;mean;float;4;;;;50163;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 7 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50165;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 7 source;1;;1s;1s;mean;Unsigned long;4;;;;50169;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 7 value;1;;1s;1s;mean;float;4;;;;50171;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 7 mode ?|<;1;;1s;1s;mean;Unsigned long;4;;;;50173;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 8 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50175;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 8 hysteresis;1;%;1s;1s;mean;float;4;;;;50177;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 8 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50179;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 8 source;1;;1s;1s;mean;Unsigned long;4;;;;50183;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 8 value;1;;1s;1s;mean;float;4;;;;50185;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 8 mode ?|< ;1;;1s;1s;mean;Unsigned long;4;;;;50187;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 9 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50189;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 9 hysteresis;1;%;1s;1s;mean;float;4;;;;50191;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 9 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50193;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 9 source;1;;1s;1s;mean;Unsigned long;4;;;;50197;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 9 value;1;;1s;1s;mean;float;4;;;;50199;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 9 mode ?|<;1;;1s;1s;mean;Unsigned long;4;;;;50201;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 10 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50203;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 10 hysteresis;1;%;1s;1s;mean;float;4;;;;50205;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 10 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50207;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 10 source;1;;1s;1s;mean;Unsigned long;4;;;;50211;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 10 value;1;;1s;1s;mean;float;4;;;;50213;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 10 mode ?|< ;1;;1s;1s;mean;Unsigned long;4;;;;50215;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 11 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50217;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 11 hysteresis;1;%;1s;1s;mean;float;4;;;;50219;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 11 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50221;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 11 source;1;;1s;1s;mean;Unsigned long;4;;;;50225;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 11 value;1;;1s;1s;mean;float;4;;;;50227;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;limit 11 mode ?|<;1;;1s;1s;mean;Unsigned long;4;;;;50229;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;date format;1;;1s;1s;mean;Unsigned long;4;;;;50231;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;daylight saving time;1;;1s;1s;mean;Unsigned long;4;;;;50233;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;time zone;1;min;1s;1s;mean;long;4;;;;50235;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;mediation time moving averages;1;s;1s;1s;mean;Unsigned long;4;;;;50237;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;reactive power numbers used;1;;1s;1s;mean;Unsigned long;4;;;;50239;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;universal counter 1 DI-count signal;1;;1s;1s;mean;Unsigned long;4;;;;50241;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;invert current L1;1;;1s;1s;mean;Unsigned long;4;;;;50243;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;invert current L2;1;;1s;1s;mean;Unsigned long;4;;;;50245;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;invert current L3;1;;1s;1s;mean;Unsigned long;4;;;;50247;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;current lower limit for hourmeter;1;%;1s;1s;mean;Unsigned long;4;;;;50249;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;universal counter 1 source;1;;1s;1s;mean;Unsigned long;4;;;;50251;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;universal counter 2 DI-count signal;1;;1s;1s;mean;Unsigned long;4;;;;50253;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;digital input parameter;1;;1s;1s;mean;Unsigned long;14;;;;61167;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;digital output parameter;1;;1s;1s;mean;stOutputPara;14;;;;61175;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;event recording parameters;1;;1s;1s;mean;stEventPara;16;;;;62101;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;logically linked limit parameters;1;;1s;1s;mean;stCombLimitPara;54;;;;62301;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;IP-address;1;;1s;1s;mean;Unsigned long;4;;;;63001;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;subnet mask;1;;1s;1s;mean;Unsigned long;4;;;;63003;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;gateway;1;;1s;1s;mean;Unsigned long;4;;;;63005;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;bootloader version;1;;1s;1s;mean;Unsigned long;4;;;;63007;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;password protection ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;63009;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;date of manufacture;1;;1s;1s;mean;Unsigned long;4;;;;63011;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;ethernet protocol;1;;1s;1s;mean;Unsigned long;4;;;;63015;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;protocol module interface 1;1;;1s;1s;mean;Unsigned long;4;;;;63017;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;address module interface 1;1;;1s;1s;mean;Unsigned long;4;;;;63019;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;baudrate module interface 1;1;;1s;1s;mean;Unsigned long;4;;;;63021;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;format module interface 1;1;;1s;1s;mean;Unsigned long;4;;;;63023;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;response time module interface 1;1;ms;1s;1s;mean;Unsigned long;4;;;;63025;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;protocol module interface 2;1;;1s;1s;mean;Unsigned long;4;;;;63033;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;address module interface 2;1;;1s;1s;mean;Unsigned long;4;;;;63035;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;baudrate module interface 2;1;;1s;1s;mean;Unsigned long;4;;;;63037;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;format module interface 2;1;;1s;1s;mean;Unsigned long;4;;;;63039;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;response time module interface 2;1;ms;1s;1s;mean;Unsigned long;4;;;;63041;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;TCP/IP-Port gateway module interface 1;1;ms;1s;1s;mean;Unsigned long;4;;;;63043;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;TCP/IP-Port gateway module interface 2;1;ms;1s;1s;mean;Unsigned long;4;;;;63045;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;profibus ID PAC4200;1;;1s;1s;mean;Unsigned long;4;;;;63065;r;0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;I&M-data PAC4200;1;;1s;1s;mean;stIM0;54;;;;64001;r(w);0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;I&M 0 to I&M 4-data PAC4200;1;;1s;1s;mean;stIM14;178;;;;64028;rw;0x03 & 0x04 & 0x10;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;I&M-data module interface 1;1;;1s;1s;mean;stIM0-;54;;;;64117;r(w);0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;I&M-data module interface 2;1;;1s;1s;mean;stIM0;54;;;;64144;r(w);0x03 & 0x04;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;reset the maximum values;1;;1s;1s;mean;Unsigned short;2;;;;60002;w;0x06;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;reset the minimum values;1;;1s;1s;mean;Unsigned short;2;;;;60003;w;0x06;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;reset the energy meter;1;;1s;1s;mean;Unsigned short;2;;;;60004;w;0x06;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;synchronization of the measurement period;1;;1s;1s;mean;Unsigned short;2;;;;60005;w;0x06;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;tariff switch;1;;1s;1s;mean;Unsigned short;2;;;;60006;w;0x06;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;Acknowledge the diagnostic bit;1;;1s;1s;mean;Unsigned short;2;;;;60007;w;0x06;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;outputs switch (if configured);1;;1s;1s;mean;Unsigned short;2;;;;60008;w;0x06;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;power on command vector group;1;;1s;1s;mean;Unsigned short;2;;;;60009;w;0x06;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;reset the daily energy meters;1;;1s;1s;mean;Unsigned short;2;;;;60010;w;0x06;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;reset the load input record;1;;1s;1s;mean;Unsigned short;2;;;;60011;w;0x06;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;reset the energy record;1;;1s;1s;mean;Unsigned short;2;;;;60012;w;0x06;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;set the standard event-recording conditions;1;;1s;1s;mean;Unsigned short;2;;;;60013;w;0x06;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;set the standard I/O parameters;1;;1s;1s;mean;Unsigned short;2;;;;60014;w;0x06;
|
|||
|
|
Monitoring;Siemens;Modbus TCP;increment date / time;1;;1s;1s;mean;Unsigned long;4;;;;65292;w;0x10;
|