modbus modul lauffähig, pacs.csv angefügt, pCahrger angefangen

This commit is contained in:
Philipp Rauch 2014-02-04 18:36:27 +01:00
parent 2412589ef8
commit 9a95c211eb
6 changed files with 905 additions and 30 deletions

View file

@ -5,52 +5,88 @@ Created on 05.12.2013
'''
from pymodbus.client.sync import ModbusTcpClient
from datetime import datetime
from profile.datasheet import Datasheet
import struct
def setup(conf):
PACS = []
csv = '%s/%s' % (conf['config_dictionary'], conf['pac_csvfile'])
pac_csv = Datasheet()
pac_csv.loadDatasheet(strFile = csv)
messages = pac_csv.readDatasheet()
### INITIALIZE ###
PACS.append(messages)
PACS.append(ModbusTcpClient('10.2.6.5'))
PACS.append(ModbusTcpClient('10.2.6.6'))
PACS.append(ModbusTcpClient('10.2.6.7'))
PACS.append(ModbusTcpClient('10.2.6.8'))
### CONNECT ###
for PAC in PACS:
for PAC in PACS[1::]:
PAC.connect()
return PACS
def loop(PACS, item):
# PAC[0].write_coil(213, 100,2)
# result = PAC[0].read_coils(213,1,unit=2)
#
# ans = PAC[0].write_registers(213,(1,0),unit=2)
# print "Antwort: %s" % ans
res = PACS[1].read_holding_registers(797,2,unit=2)
print "Werte: %s" % _to_time(res.registers)
row = PACS[0][PACS[0]['offset'] == item]
inx = row.index.values[0]
#print row.get('value - type')[inx]
valType = row.get('value - type')[inx]
reg = row.get('size (Byte)')[inx]/2
type_picker = {'double' : _to_double,
'float' : _to_float,
'float + timestamp' : _to_float_time,
'long' : _to_long,
'timestamp' : _to_time_abs,
'Unsigned long' : _to_ulong,
'Unsigned short' : _to_ushort }
func = type_picker.get(valType, None)
if func is None:
raise NotImplementedError
res = PACS[2].read_holding_registers(item,reg,unit=2)
return { row.get('Value name')[inx] : func(res.registers) }
def _to_float_time(reg):
res = []
res.append(_to_float(reg[0:2]))
res.append(_to_time_abs(reg[2:6]))
return res
def _to_long(reg):
tmp = int(reg[0]) << 16 | int(reg[1])
s = struct.pack('=i', tmp)
return struct.unpack('=l', s)[0]
def _to_double(reg):
tmp = int(reg[0]) << 3*16 | int(reg[1]) << 2*16 | int(reg[2]) << 16 | int(reg[3])
s = struct.pack('=q', tmp)
return struct.unpack('=d', s)[0]
def _to_time_abs(reg):
correction = (6*60*60 - 6*60 - 9) #21231 / 5h 53m 51s
timestamp = _to_ulong(reg) + correction
timestamp = _to_ulong(reg)
date = datetime.fromtimestamp(timestamp)
return date
def _to_time_rel(reg):
return _to_ulong(reg)/3600.0
return str(date)
def _to_ulong(reg):
return (reg[0]*int(0xFFFF) + reg[1])
return (reg[0]*(int(0xFFFF)+1) + reg[1])
def _to_ushort(reg):
return reg[0]
def _to_float(reg):
tmp = int(reg[0]) << 16 | int(reg[1])
s = struct.pack('=i', tmp)
return struct.unpack('=f', s)
return struct.unpack('=f', s)[0]
def close(PACS):
### CLOSE ###
for PAC in PACS:
for PAC in PACS[1::]:
PAC.close()

View file

@ -65,17 +65,17 @@ class Switch(Thread):
# item = query.get() #block = True
# query should be included in the result
item = None #self.query.get(block = True)
item = self.query.get(block = True)
if self.source == MYSQL:
result = database.loop(self.cursor, item)
elif self.source == MODBUS:
result = modbus.loop(self.cursor, item)
#print 'PUT:\t%s' % result
print 'PUT:\t%s' % result
#self.queue.put(result)
#self.query.task_done()
self.queue.put(result)
self.query.task_done()
if self.source == MYSQL:
sleep(float(conf['mySQL_speed']))
elif self.source == MODBUS:

View file

@ -18,3 +18,6 @@ config_debug = True # default False
## possible Baud Rates: 100k, 125k, 250k, 500k, 1000k ##
can_baudrate = 250k # default 500k
can_symfile = ems-test.sym
#### PAC ####
pac_csvfile = pacs.csv

827
src/config/pacs.csv Normal file
View file

@ -0,0 +1,827 @@
Component;Company;Bus type;Value name;Value - factor;Value - unit;Logging rate;sending rate;Info;value - type;size (Byte);Endianness;first Register;BUS address;offset;read/write;function;range
Monitoring;Siemens;Modbus TCP;voltage L1-N;1;V;1s;1s;mean;float;4;;;;1;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;voltage L2-N;1;V;1s;1s;mean;float;4;;;;3;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;voltage L3-N;1;V;1s;1s;mean;float;4;;;;5;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;voltage L1-L2;1;V;1s;1s;mean;float;4;;;;7;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;voltage L2-L3;1;V;1s;1s;mean;float;4;;;;9;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;voltage L3-L1;1;V;1s;1s;mean;float;4;;;;11;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;current L1;1;A;1s;1s;mean;float;4;;;;13;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;current L2;1;A;1s;1s;mean;float;4;;;;15;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;current L3;1;A;1s;1s;mean;float;4;;;;17;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;apparent power L1;1;VA;1s;1s;mean;float;4;;;;19;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;apparent power L2;1;VA;1s;1s;mean;float;4;;;;21;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;apparent power L3;1;VA;1s;1s;mean;float;4;;;;23;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;active power L1;1;W;1s;1s;mean;float;4;;;;25;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;active power L2;1;W;1s;1s;mean;float;4;;;;27;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;active power L3;1;W;1s;1s;mean;float;4;;;;29;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;reactive power L1 (Qn);1;var;1s;1s;mean;float;4;;;;31;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;reactive power L2 (Qn);1;var;1s;1s;mean;float;4;;;;33;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;reactive power L3 (Qn);1;var;1s;1s;mean;float;4;;;;35;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;power factor L1;1;;1s;1s;mean;float;4;;;;37;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;power factor L2;1;;1s;1s;mean;float;4;;;;39;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;power factor L3;1;;1s;1s;mean;float;4;;;;41;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;THD voltage L1-L2;1;%;1s;1s;mean;float;4;;;;43;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;THD voltage L2-L3;1;%;1s;1s;mean;float;4;;;;45;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;THD voltage L3-L1;1;%;1s;1s;mean;float;4;;;;47;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;reserved;;;;;;;;;;;49;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;reserved;;;;;;;;;;;51;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;reserved;;;;;;;;;;;53;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;line frequency;1;Hz;1s;1s;mean;float;4;;;;55;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;3-phase average voltage L-N ;1;V;1s;1s;mean;float;4;;;;57;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;3-phase average voltage L-L ;1;V;1s;1s;mean;float;4;;;;59;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;3-phase average current L-L ;1;A;1s;1s;mean;float;4;;;;61;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;total apparent power;1;VA;1s;1s;mean;float;4;;;;63;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;total active power;1;W;1s;1s;mean;float;4;;;;65;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;total reactive power;1;var;1s;1s;mean;float;4;;;;67;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;total power factor;1;;1s;1s;mean;float;4;;;;69;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;amplitude unbalance of voltage;1;%;1s;1s;mean;float;4;;;;71;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;amplitude unbalance of current;1;%;1s;1s;mean;float;4;;;;73;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum voltage L1-N;1;V;1s;1s;mean;float;4;;;;75;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum voltage L2-N;1;V;1s;1s;mean;float;4;;;;77;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum voltage L3-N;1;V;1s;1s;mean;float;4;;;;79;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum voltage L1-L2;1;V;1s;1s;mean;float;4;;;;81;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum voltage L2-L3;1;V;1s;1s;mean;float;4;;;;83;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum voltage L3-L1;1;V;1s;1s;mean;float;4;;;;85;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum current L1;1;A;1s;1s;mean;float;4;;;;87;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum current L2;1;A;1s;1s;mean;float;4;;;;89;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum current L3;1;A;1s;1s;mean;float;4;;;;91;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum apparent power L1;1;VA;1s;1s;mean;float;4;;;;93;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum apparent power L2;1;VA;1s;1s;mean;float;4;;;;95;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum apparent power L3;1;VA;1s;1s;mean;float;4;;;;97;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum active power L1;1;W;1s;1s;mean;float;4;;;;99;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum active power L2;1;W;1s;1s;mean;float;4;;;;101;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum active power L3;1;W;1s;1s;mean;float;4;;;;103;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum reactive power L1 (Qn);1;var;1s;1s;mean;float;4;;;;105;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum reactive power L2 (Qn);1;var;1s;1s;mean;float;4;;;;107;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum reactive power L3 (Qn);1;var;1s;1s;mean;float;4;;;;109;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum power factor L1;1;;1s;1s;mean;float;4;;;;111;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum power factor L2;1;;1s;1s;mean;float;4;;;;113;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum power factor L3;1;;1s;1s;mean;float;4;;;;115;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum THD voltage L1-L2;1;%;1s;1s;mean;float;4;;;;117;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum THD voltage L2-L3;1;%;1s;1s;mean;float;4;;;;119;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum THD voltage L3-L1;1;%;1s;1s;mean;float;4;;;;121;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;reserved;;;;;;;;;;;123;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;reserved;;;;;;;;;;;125;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;reserved;;;;;;;;;;;127;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum line frequency;1;Hz;1s;1s;mean;float;4;;;;129;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 3-phase average voltage L-N ;1;V;1s;1s;mean;float;4;;;;131;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 3-phase average voltage L-L ;1;V;1s;1s;mean;float;4;;;;133;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 3-phase average current L-L ;1;A;1s;1s;mean;float;4;;;;135;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum total apparent power;1;VA;1s;1s;mean;float;4;;;;137;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum total active power;1;W;1s;1s;mean;float;4;;;;139;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum total reactive power (Qn);1;var;1s;1s;mean;float;4;;;;141;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum total power factor;1;;1s;1s;mean;float;4;;;;143;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal voltage L1-N;1;V;1s;1s;mean;float;4;;;;145;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal voltage L2-N;1;V;1s;1s;mean;float;4;;;;147;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal voltage L3-N;1;V;1s;1s;mean;float;4;;;;149;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal voltage L1-L2;1;V;1s;1s;mean;float;4;;;;151;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal voltage L2-L3;1;V;1s;1s;mean;float;4;;;;153;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal voltage L3-L1;1;V;1s;1s;mean;float;4;;;;155;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal current L1;1;A;1s;1s;mean;float;4;;;;157;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal current L2;1;A;1s;1s;mean;float;4;;;;159;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal current L3;1;A;1s;1s;mean;float;4;;;;161;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal apparent power L1;1;VA;1s;1s;mean;float;4;;;;163;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal apparent power L2;1;VA;1s;1s;mean;float;4;;;;165;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal apparent power L3;1;VA;1s;1s;mean;float;4;;;;167;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal active power L1;1;W;1s;1s;mean;float;4;;;;169;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal active power L2;1;W;1s;1s;mean;float;4;;;;171;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal active power L3;1;W;1s;1s;mean;float;4;;;;173;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal reactive power L1 (Qn);1;var;1s;1s;mean;float;4;;;;175;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal reactive power L2 (Qn);1;var;1s;1s;mean;float;4;;;;177;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal reactive power L3 (Qn);1;var;1s;1s;mean;float;4;;;;179;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal power factor L1;1;;1s;1s;mean;float;4;;;;181;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal power factor L2;1;;1s;1s;mean;float;4;;;;183;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal power factor L3;1;;1s;1s;mean;float;4;;;;185;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal line frequency;1;Hz;1s;1s;mean;float;4;;;;187;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal 3-phase average voltage L-N ;1;V;1s;1s;mean;float;4;;;;189;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal 3-phase average voltage L-L ;1;V;1s;1s;mean;float;4;;;;191;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal 3-phase average current L-L ;1;A;1s;1s;mean;float;4;;;;193;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal total apparent power;1;VA;1s;1s;mean;float;4;;;;195;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal total active power;1;W;1s;1s;mean;float;4;;;;197;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal total reactive power;1;var;1s;1s;mean;float;4;;;;199;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimal total power factor;1;;1s;1s;mean;float;4;;;;201;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;limit value violations;1;;1s;1s;mean;Unsigned long;4;;;;203;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;PMD diagnostic and status;1;;1s;1s;mean;Unsigned long;4;;;;205;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;digital outputs status;1;;1s;1s;mean;Unsigned long;4;;;;207;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;digital input status;1;;1s;1s;mean;Unsigned long;4;;;;209;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;active rate;1;;1s;1s;mean;Unsigned long;4;;;;211;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;hourmeter;1;s;1s;1s;mean;Unsigned long;4;;;;213;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;universal counter;1;;1s;1s;mean;Unsigned long;4;;;;215;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;change counter of basic parameters;1;;1s;1s;mean;Unsigned long;4;;;;217;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;change counter of all parameters;1;;1s;1s;mean;Unsigned long;4;;;;219;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;change counter limits;1;;1s;1s;mean;Unsigned long;4;;;;221;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;counter all events;1;;1s;1s;mean;Unsigned long;4;;;;223;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;counter of all alarms;1;;1s;1s;mean;Unsigned long;4;;;;225;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;counter on all load output records;1;;1s;1s;mean;Unsigned long;4;;;;227;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;counter for other;1;;1s;1s;mean;Unsigned long;4;;;;229;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;status digital outputs module 1;1;;1s;1s;mean;Unsigned long;4;;;;231;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;status digital input module 1;1;;1s;1s;mean;Unsigned long;4;;;;233;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;status digital outputs module 2;1;;1s;1s;mean;Unsigned long;4;;;;235;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;status digital input module 2;1;;1s;1s;mean;Unsigned long;4;;;;237;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;cos ? L1;1;;1s;1s;mean;float;4;;;;243;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;cos ? L2;1;;1s;1s;mean;float;4;;;;245;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;cos ? L3;1;;1s;1s;mean;float;4;;;;247;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;phase shift angle L1;1;°;1s;1s;mean;float;4;;;;249;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;phase shift angle L2;1;°;1s;1s;mean;float;4;;;;251;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;phase shift angle L3;1;°;1s;1s;mean;float;4;;;;253;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;phase angle L1-L2;1;°;1s;1s;mean;float;4;;;;255;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;phase angle L2-L3;1;°;1s;1s;mean;float;4;;;;257;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;phase angle L1-L3;1;°;1s;1s;mean;float;4;;;;259;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;THD voltage L1;1;%;1s;1s;mean;float;4;;;;261;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;THD voltage L2;1;%;1s;1s;mean;float;4;;;;263;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;THD voltage L3;1;%;1s;1s;mean;float;4;;;;265;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;THD current L1;1;%;1s;1s;mean;float;4;;;;267;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;THD current L2;1;%;1s;1s;mean;float;4;;;;269;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;THD current L3;1;%;1s;1s;mean;float;4;;;;271;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;distortion power L1;1;A;1s;1s;mean;float;4;;;;273;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;distortion power L2;1;A;1s;1s;mean;float;4;;;;275;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;distortion power L3;1;A;1s;1s;mean;float;4;;;;277;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;total reactive power L1 (Qtot);1;var;1s;1s;mean;float;4;;;;279;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;total reactive power L2 (Qtot);1;var;1s;1s;mean;float;4;;;;281;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;total reactive power L3 (Qtot);1;var;1s;1s;mean;float;4;;;;283;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP; reactive power L1 (Q1);1;var;1s;1s;mean;float;4;;;;285;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP; reactive power L1 (Q1);1;var;1s;1s;mean;float;4;;;;287;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP; reactive power L1 (Q1);1;var;1s;1s;mean;float;4;;;;289;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;voltage unbalance;1;%;1s;1s;mean;float;4;;;;291;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;current unbalance;1;%;1s;1s;mean;float;4;;;;293;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;neutral conductor current;1;A;1s;1s;mean;float;4;;;;295;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;total reactive power (Qtot);1;var;1s;1s;mean;float;4;;;;297;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;total reactive power (Q1);1;var;1s;1s;mean;float;4;;;;299;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean voltage L1-N;1;V;1s;1s;mean;float;4;;;;301;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean voltage L2-N;1;V;1s;1s;mean;float;4;;;;303;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean voltage L3-N;1;V;1s;1s;mean;float;4;;;;305;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean voltage L1-L2;1;V;1s;1s;mean;float;4;;;;307;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean voltage L2-L3;1;V;1s;1s;mean;float;4;;;;309;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean voltage L3-L1;1;V;1s;1s;mean;float;4;;;;311;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean current L1;1;A;1s;1s;mean;float;4;;;;313;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean current L2;1;A;1s;1s;mean;float;4;;;;315;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean current L3;1;A;1s;1s;mean;float;4;;;;317;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean apparent power L1;1;VA;1s;1s;mean;float;4;;;;319;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean apparent power L2;1;VA;1s;1s;mean;float;4;;;;321;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean apparent power L3;1;VA;1s;1s;mean;float;4;;;;323;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean active power L1;1;W;1s;1s;mean;float;4;;;;325;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean active power L2;1;W;1s;1s;mean;float;4;;;;327;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean active power L3;1;W;1s;1s;mean;float;4;;;;329;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean reactive power L1 (Qn);1;var;1s;1s;mean;float;4;;;;331;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean reactive power L2 (Qn);1;var;1s;1s;mean;float;4;;;;333;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean reactive power L3 (Qn);1;var;1s;1s;mean;float;4;;;;335;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean total reactive power L1 (Qtot);1;var;1s;1s;mean;float;4;;;;337;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean total reactive power L2 (Qtot);1;var;1s;1s;mean;float;4;;;;339;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean total reactive power L3 (Qtot);1;var;1s;1s;mean;float;4;;;;341;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean reactive power L1 (Q1);1;var;1s;1s;mean;float;4;;;;343;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean reactive power L2 (Q1);1;var;1s;1s;mean;float;4;;;;345;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean reactive power L3 (Q1);1;var;1s;1s;mean;float;4;;;;347;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean power factor L1;1;;1s;1s;mean;float;4;;;;349;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean power factor L2;1;;1s;1s;mean;float;4;;;;351;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean power factor L3;1;;1s;1s;mean;float;4;;;;353;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean total apparent power;1;VA;1s;1s;mean;float;4;;;;355;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean total active power;1;W;1s;1s;mean;float;4;;;;357;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean total reactive power (Qn);1;var;1s;1s;mean;float;4;;;;359;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean total reactive power (Qtot);1;var;1s;1s;mean;float;4;;;;361;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean total reactive power (Q1);1;var;1s;1s;mean;float;4;;;;363;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean total power factor;1;;1s;1s;mean;float;4;;;;365;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;shared on mean neutral conductor current;1;A;1s;1s;mean;float;4;;;;367;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;process hourmeter;1;s;1s;1s;mean;Unsigned long;4;;;;369;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;universal counter 2;1;;1s;1s;mean;Unsigned long;4;;;;371;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;pulse counter 0;1;;1s;1s;mean;Unsigned long;4;;;;373;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;pulse counter 02;1;;1s;1s;mean;Unsigned long;4;;;;375;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;pulse counter 03;1;;1s;1s;mean;Unsigned long;4;;;;377;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;pulse counter 04;1;;1s;1s;mean;Unsigned long;4;;;;379;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;pulse counter 05;1;;1s;1s;mean;Unsigned long;4;;;;381;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;pulse counter 06;1;;1s;1s;mean;Unsigned long;4;;;;383;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;pulse counter 07;1;;1s;1s;mean;Unsigned long;4;;;;385;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;pulse counter 08;1;;1s;1s;mean;Unsigned long;4;;;;387;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;pulse counter 09;1;;1s;1s;mean;Unsigned long;4;;;;389;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;pulse counter 10;1;;1s;1s;mean;Unsigned long;4;;;;391;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;total power factor reference in the current period;1;;1s;1s;mean;float;4;;;;479;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;total power factor output in the current period;1;;1s;1s;mean;float;4;;;;481;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;timestamp of the current period;1;;1s;1s;mean;timestamp;8;;;;483;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;average apparent power in the current period;1;VA;1s;1s;mean;float;4;;;;489;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;average active power reference in the current period;1;W;1s;1s;mean;float;4;;;;491;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;average reactive power reference in the current period;1;var;1s;1s;mean;float;4;;;;493;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;average active power output in the current period;1;W;1s;1s;mean;float;4;;;;495;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;average reactive power output in the current period;1;var;1s;1s;mean;float;4;;;;497;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;cumulated apparent power in the current period;1;VA;1s;1s;mean;float;4;;;;499;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;cumulated active power reference in the current period;1;W;1s;1s;mean;float;4;;;;501;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;cumulated reactive power reference in the current period;1;var;1s;1s;mean;float;4;;;;503;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;cumulated active power output in the current period;1;W;1s;1s;mean;float;4;;;;505;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;cumulated reactive power output in the current period;1;var;1s;1s;mean;float;4;;;;507;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maxumum active power of the current peroid;1;W;1s;1s;mean;float;4;;;;509;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum active power of the current peroid;1;W;1s;1s;mean;float;4;;;;511;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maxumum reactive power of the current peroid;1;var;1s;1s;mean;float;4;;;;513;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum reactive power of the current peroid;1;var;1s;1s;mean;float;4;;;;515;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;length of the current peroid;1;s;1s;1s;mean;Unsigned long;4;;;;517;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;time since the beginning of the current period;1;s;1s;1s;mean;Unsigned long;4;;;;519;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;actual subinterval duration;1;s;1s;1s;mean;Unsigned long;4;;;;521;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;imformation of the last period;1;;1s;1s;mean;Unsigned long;4;;;;523;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maxumum apparent power of the current peroid;1;VA;1s;1s;mean;float;4;;;;525;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum apparent power of the current peroid;1;VA;1s;1s;mean;float;4;;;;527;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;cumulated active power in respect of the current period;1;W;1s;1s;mean;float;4;;;;529;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;cumulated reactive power in respect of the current period;1;var;1s;1s;mean;float;4;;;;531;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;cumulated active power output in the current period;1;W;1s;1s;mean;float;4;;;;533;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;cumulated reactive power output in the current period;1;var;1s;1s;mean;float;4;;;;535;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum active power of the current period;1;W;1s;1s;mean;float;4;;;;537;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum active power of the current period;1;W;1s;1s;mean;float;4;;;;539;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum reactive power of the current period;1;var;1s;1s;mean;float;4;;;;541;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum reactive power of the current period;1;var;1s;1s;mean;float;4;;;;543;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;date / time;1;;1s;1s;mean;timestamp;8;;;;797;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;related active energy tariff 1;1;Wh;1s;1s;mean;double;8;;;;801;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;related active energy tariff 2;1;Wh;1s;1s;mean;double;8;;;;805;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;delivered active energy tariff 1;1;Wh;1s;1s;mean;double;8;;;;809;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;delivered active energy tariff 2;1;Wh;1s;1s;mean;double;8;;;;813;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;related reactive energy tariff 1;1;varh;1s;1s;mean;double;8;;;;817;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;related reactive energy tariff 2;1;varh;1s;1s;mean;double;8;;;;821;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;delivered reactive energy tariff 1;1;varh;1s;1s;mean;double;8;;;;825;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;delivered reactive energy tariff 2;1;varh;1s;1s;mean;double;8;;;;829;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;translucent energy tariff 1;1;VAh;1s;1s;mean;double;8;;;;833;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;translucent energy tariff 2;1;VAh;1s;1s;mean;double;8;;;;837;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;process active energy;1;Wh;1s;1s;mean;double;8;;;;841;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;process reactive energy;1;varh;1s;1s;mean;double;8;;;;845;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;process translucent energy;1;VAh;1s;1s;mean;double;8;;;;849;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;process active energy - prior measurement;1;Wh;1s;1s;mean;double;8;;;;853;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;process reactive energy - prior measurement;1;varh;1s;1s;mean;double;8;;;;857;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;process translucent energy - prior measurement;1;VAh;1s;1s;mean;double;8;;;;861;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;date / time;1;;1s;1s;mean;Unsigned long;4;;;;2799;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;related active energy tariff 1;1;Wh;1s;1s;mean;float;4;;;;2801;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;related active energy tariff 2;1;Wh;1s;1s;mean;float;4;;;;2803;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;delivered active energy tariff 1;1;Wh;1s;1s;mean;float;4;;;;2805;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;delivered active energy tariff 2;1;Wh;1s;1s;mean;float;4;;;;2807;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;related reactive energy tariff 1;1;varh;1s;1s;mean;float;4;;;;2809;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;related reactive energy tariff 2;1;varh;1s;1s;mean;float;4;;;;2811;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;delivered reactive energy tariff 1;1;varh;1s;1s;mean;float;4;;;;2813;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;delivered reactive energy tariff 2;1;varh;1s;1s;mean;float;4;;;;2815;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;translucent energy tariff 1;1;VAh;1s;1s;mean;float;4;;;;2817;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;translucent energy tariff 2;1;VAh;1s;1s;mean;float;4;;;;2819;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;process active energy;1;Wh;1s;1s;mean;float;4;;;;2821;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;process reactive energy;1;varh;1s;1s;mean;float;4;;;;2823;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;process translucent energy;1;VAh;1s;1s;mean;float;4;;;;2825;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;process active energy - prior measurement;1;Wh;1s;1s;mean;float;4;;;;2827;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;process reactive energy - prior measurement;1;varh;1s;1s;mean;float;4;;;;2829;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;process translucent energy - prior measurement;1;VAh;1s;1s;mean;float;4;;;;2831;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum voltage L1-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;3001;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum voltage L2-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;3007;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum voltage L3-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;3013;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum voltage L1-L2 with time;1;V;1s;1s;mean;float + timestamp;12;;;;3019;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum voltage L2-L3 with time;1;V;1s;1s;mean;float + timestamp;12;;;;3025;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum voltage L3-L1 with time;1;V;1s;1s;mean;float + timestamp;12;;;;3031;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum current L1 with time;1;A;1s;1s;mean;float + timestamp;12;;;;3037;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum current L2 with time;1;A;1s;1s;mean;float + timestamp;12;;;;3043;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum current L3 with time;1;A;1s;1s;mean;float + timestamp;12;;;;3049;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum apparent power L1 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;3055;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum apparent power L2 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;3061;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum apparent power L3 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;3067;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum active power L1 with time;1;W;1s;1s;mean;float + timestamp;12;;;;3073;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum active power L2 with time;1;W;1s;1s;mean;float + timestamp;12;;;;3079;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum active power L3 with time;1;W;1s;1s;mean;float + timestamp;12;;;;3085;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum reactive power L1 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3091;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum reactive power L2 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3097;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum reactive power L3 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3103;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum total reactive power L1 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3109;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum total reactive power L2 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3115;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum total reactive power L3 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3121;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum reactive power L1 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3127;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum reactive power L2 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3133;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum reactive power L3 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3139;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum power factor L1 with time;1;;1s;1s;mean;float + timestamp;12;;;;3145;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum power factor L2 with time;1;;1s;1s;mean;float + timestamp;12;;;;3151;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum power factor L3 with time;1;;1s;1s;mean;float + timestamp;12;;;;3157;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum THD voltage L1-L2 based on the fundamental frequency with time;1;%;1s;1s;mean;float + timestamp;12;;;;3163;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum THD voltage L2-L3 based on the fundamental frequency with time;1;%;1s;1s;mean;float + timestamp;12;;;;3169;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum THD voltage L3-L1 based on the fundamental frequency with time;1;%;1s;1s;mean;float + timestamp;12;;;;3175;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum cos ? L1 with time;1;cos ?_L1;1s;1s;mean;float + timestamp;12;;;;3199;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum cos ? L2 with time;1;cos ?_L2;1s;1s;mean;float + timestamp;12;;;;3205;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum cos ? L3 with time;1;cos ?_L3;1s;1s;mean;float + timestamp;12;;;;3211;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum phase shift angle L1 with time;1;°;1s;1s;mean;float + timestamp;12;;;;3217;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum phase shift angle L2 with time;1;°;1s;1s;mean;float + timestamp;12;;;;3223;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum phase shift angle L3 with time;1;°;1s;1s;mean;float + timestamp;12;;;;3229;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum phase angle L1-L2 with time;1;°;1s;1s;mean;float + timestamp;12;;;;3235;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum phase angle L2-L3 with time;1;°;1s;1s;mean;float + timestamp;12;;;;3241;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum phase angle L1-L3 with time;1;°;1s;1s;mean;float + timestamp;12;;;;3247;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum THD voltage L1 with time;1;%;1s;1s;mean;float + timestamp;12;;;;3253;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum THD voltage L2 with time;1;%;1s;1s;mean;float + timestamp;12;;;;3259;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum THD voltage L3 with time;1;%;1s;1s;mean;float + timestamp;12;;;;3265;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum THD current L1 with time;1;%;1s;1s;mean;float + timestamp;12;;;;3271;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum THD current L2 with time;1;%;1s;1s;mean;float + timestamp;12;;;;3277;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum THD current L3 with time;1;%;1s;1s;mean;float + timestamp;12;;;;3283;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum distortion power L1 with time;1;A;1s;1s;mean;float + timestamp;12;;;;3289;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum distortion power L2 with time;1;A;1s;1s;mean;float + timestamp;12;;;;3295;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum distortion power L3 with time;1;A;1s;1s;mean;float + timestamp;12;;;;3301;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum line frequency with time;1;;1s;1s;mean;float + timestamp;12;;;;3307;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 3-phase average voltage L-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;3313;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 3-phase average voltage L-L with time;1;V;1s;1s;mean;float + timestamp;12;;;;3319;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 3-phase average current with time;1;A;1s;1s;mean;float + timestamp;12;;;;3325;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum total apparent power with time;1;VA;1s;1s;mean;float + timestamp;12;;;;3331;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum total active power with time;1;W;1s;1s;mean;float + timestamp;12;;;;3337;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum total reactive power (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3343;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum total power factor with time;1;;1s;1s;mean;float + timestamp;12;;;;3349;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum neutral conductor current with time;1;A;1s;1s;mean;float + timestamp;12;;;;3355;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum total reactive power (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3361;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum total reactive power (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3367;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean voltage L1-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;3373;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean voltage L2-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;3379;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean voltage L3-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;3385;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean voltage L1-L2 with time;1;V;1s;1s;mean;float + timestamp;12;;;;3391;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean voltage L2-L3 with time;1;V;1s;1s;mean;float + timestamp;12;;;;3397;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean voltage L3-L1 with time;1;V;1s;1s;mean;float + timestamp;12;;;;3403;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean current L1 with time;1;A;1s;1s;mean;float + timestamp;12;;;;3409;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean current L2 with time;1;A;1s;1s;mean;float + timestamp;12;;;;3415;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean current L3 with time;1;A;1s;1s;mean;float + timestamp;12;;;;3421;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean apparent power L1 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;3427;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean apparent power L2 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;3433;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean apparent power L3 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;3439;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean active power L1 with time;1;W;1s;1s;mean;float + timestamp;12;;;;3445;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean active power L2 with time;1;W;1s;1s;mean;float + timestamp;12;;;;3451;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean active power L3 with time;1;W;1s;1s;mean;float + timestamp;12;;;;3457;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean reactive power L1 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3463;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean reactive power L2 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3469;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean reactive power L3 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3475;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean total reactive power L1 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3481;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean total reactive power L2 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3487;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean total reactive power L3 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3493;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean reactive power L1 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3499;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean reactive power L2 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3505;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean reactive power L3 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3511;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean power factor L1 with time;1;;1s;1s;mean;float + timestamp;12;;;;3517;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean power factor L2 with time;1;;1s;1s;mean;float + timestamp;12;;;;3523;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean power factor L3 with time;1;;1s;1s;mean;float + timestamp;12;;;;3529;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean total apparent power with time;1;VA;1s;1s;mean;float + timestamp;12;;;;3535;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean total active power with time;1;W;1s;1s;mean;float + timestamp;12;;;;3541;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean total reactive power (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3547;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean total reactive power (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3553;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean total reactive power (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;3559;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean total power factor with time;1;;1s;1s;mean;float + timestamp;12;;;;3565;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum shared on mean neutral conductor current with time;1;A;1s;1s;mean;float + timestamp;12;;;;3571;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum voltage L1-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;6001;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum voltage L2-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;6007;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum voltage L3-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;6013;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum voltage L1-L2 with time;1;V;1s;1s;mean;float + timestamp;12;;;;6019;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum voltage L2-L3 with time;1;V;1s;1s;mean;float + timestamp;12;;;;6025;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum voltage L3-L1 with time;1;V;1s;1s;mean;float + timestamp;12;;;;6031;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum current L1 with time;1;A;1s;1s;mean;float + timestamp;12;;;;6037;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum current L2 with time;1;A;1s;1s;mean;float + timestamp;12;;;;6043;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum current L3 with time;1;A;1s;1s;mean;float + timestamp;12;;;;6049;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum apparent power L1 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;6055;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum apparent power L2 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;6061;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum apparent power L3 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;6067;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum active power L1 with time;1;W;1s;1s;mean;float + timestamp;12;;;;6073;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum active power L2 with time;1;W;1s;1s;mean;float + timestamp;12;;;;6079;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum active power L3 with time;1;W;1s;1s;mean;float + timestamp;12;;;;6085;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum reactive power L1 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6091;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum reactive power L2 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6097;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum reactive power L3 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6103;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum total reactive power L1 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6109;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum total reactive power L2 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6115;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum total reactive power L3 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6121;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum reactive power L1 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6127;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum reactive power L2 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6133;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum reactive power L3 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6139;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum power factor L1 with time;1;;1s;1s;mean;float + timestamp;12;;;;6145;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum power factor L2 with time;1;;1s;1s;mean;float + timestamp;12;;;;6151;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum power factor L3 with time;1;;1s;1s;mean;float + timestamp;12;;;;6157;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum cos ? L1 with time;1;cos ?_L1;1s;1s;mean;float + timestamp;12;;;;6163;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum cos ? L2 with time;1;cos ?_L2;1s;1s;mean;float + timestamp;12;;;;6169;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum cos ? L3 with time;1;cos ?_L3;1s;1s;mean;float + timestamp;12;;;;6175;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum phase shift angle L1 with time;1;°;1s;1s;mean;float + timestamp;12;;;;6181;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum phase shift angle L2 with time;1;°;1s;1s;mean;float + timestamp;12;;;;6187;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum phase shift angle L3 with time;1;°;1s;1s;mean;float + timestamp;12;;;;6193;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum phase angle L1-L2 with time;1;°;1s;1s;mean;float + timestamp;12;;;;6199;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum phase angle L2-L3 with time;1;°;1s;1s;mean;float + timestamp;12;;;;6205;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum phase angle L1-L3 with time;1;°;1s;1s;mean;float + timestamp;12;;;;6211;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum line frequency with time;1;;1s;1s;mean;float + timestamp;12;;;;6217;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum 3-phase average voltage L-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;6223;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum 3-phase average voltage L-L with time;1;V;1s;1s;mean;float + timestamp;12;;;;6229;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum 3-phase average current with time;1;A;1s;1s;mean;float + timestamp;12;;;;6235;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum total apparent power with time;1;VA;1s;1s;mean;float + timestamp;12;;;;6241;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum total active power with time;1;W;1s;1s;mean;float + timestamp;12;;;;6247;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum total reactive power (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6253;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum total power factor (Qn) with time;1;;1s;1s;mean;float + timestamp;12;;;;6259;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum neutral conductor current with time;1;A;1s;1s;mean;float + timestamp;12;;;;6265;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum total reactive power (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6271;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum total reactive power (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6277;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean voltage L1-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;6283;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean voltage L2-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;6289;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean voltage L3-N with time;1;V;1s;1s;mean;float + timestamp;12;;;;6295;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean voltage L1-L2 with time;1;V;1s;1s;mean;float + timestamp;12;;;;6301;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean voltage L2-L3 with time;1;V;1s;1s;mean;float + timestamp;12;;;;6307;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean voltage L3-L1 with time;1;V;1s;1s;mean;float + timestamp;12;;;;6313;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean current L1 with time;1;A;1s;1s;mean;float + timestamp;12;;;;6319;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean current L2 with time;1;A;1s;1s;mean;float + timestamp;12;;;;6325;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean current L3 with time;1;A;1s;1s;mean;float + timestamp;12;;;;6331;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean apparent power L1 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;6337;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean apparent power L2 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;6343;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean apparent power L3 with time;1;VA;1s;1s;mean;float + timestamp;12;;;;6349;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean active power L1 with time;1;W;1s;1s;mean;float + timestamp;12;;;;6355;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean active power L2 with time;1;W;1s;1s;mean;float + timestamp;12;;;;6361;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean active power L3 with time;1;W;1s;1s;mean;float + timestamp;12;;;;6367;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean reactive power L1 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6373;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean reactive power L2 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6379;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean reactive power L3 (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6385;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean total reactive power L1 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6391;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean total reactive power L2 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6397;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean total reactive power L3 (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6403;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean reactive power L1 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6409;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean reactive power L2 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6415;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean reactive power L3 (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6421;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean power factor L1 with time;1;;1s;1s;mean;float + timestamp;12;;;;6427;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean power factor L2 with time;1;;1s;1s;mean;float + timestamp;12;;;;6433;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean power factor L3 with time;1;;1s;1s;mean;float + timestamp;12;;;;6439;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean total apparent power with time;1;VA;1s;1s;mean;float + timestamp;12;;;;6445;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean total active power with time;1;W;1s;1s;mean;float + timestamp;12;;;;6451;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean total reactive power (Qn) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6457;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean total reactive power (Qtot) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6463;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean total reactive power (Q1) with time;1;var;1s;1s;mean;float + timestamp;12;;;;6469;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean total power factor with time;1;;1s;1s;mean;float + timestamp;12;;;;6475;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;minimum shared on mean neutral conductor current with time;1;A;1s;1s;mean;float + timestamp;12;;;;6481;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;fundamental oscillation voltage L1-N;1;V;1s;1s;mean;float;4;;;;9001;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;fundamental oscillation voltage L2-N;1;V;1s;1s;mean;float;4;;;;9003;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;fundamental oscillation voltage L3-N;1;V;1s;1s;mean;float;4;;;;9005;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;3. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9007;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;3. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9009;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;3. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9011;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;5. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9013;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;5. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9015;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;5. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9017;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;7. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9019;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;7. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9021;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;7. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9023;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;9. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9025;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;9. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9027;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;9. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9029;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;11. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9031;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;11. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9033;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;11. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9035;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;13. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9037;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;13. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9039;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;13. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9041;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;15. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9043;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;15. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9045;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;15. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9047;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;17. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9049;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;17. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9051;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;17. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9053;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;19. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9055;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;19. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9057;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;19. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9059;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;21. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9061;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;21. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9063;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;21. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9065;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;23. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9067;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;23. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9069;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;23. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9071;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;25. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9073;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;25. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9075;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;25. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9077;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;27. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9079;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;27. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9081;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;27. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9083;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;29. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9085;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;29. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9087;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;29. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9089;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;31. harmonic voltage L1-N;1;%;1s;1s;mean;float;4;;;;9091;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;31. harmonic voltage L2-N;1;%;1s;1s;mean;float;4;;;;9093;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;31. harmonic voltage L3-N;1;%;1s;1s;mean;float;4;;;;9095;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;fundamental oscillation current L1;1;A;1s;1s;mean;float;4;;;;11001;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;fundamental oscillation current L2;1;A;1s;1s;mean;float;4;;;;11003;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;fundamental oscillation current L3;1;A;1s;1s;mean;float;4;;;;11005;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;3. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11007;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;3. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11009;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;3. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11011;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;5. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11013;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;5. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11015;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;5. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11017;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;7. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11019;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;7. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11021;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;7. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11023;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;9. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11025;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;9. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11027;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;9. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11029;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;11. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11031;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;11. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11033;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;11. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11035;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;13. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11037;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;13. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11039;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;13. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11041;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;15. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11043;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;15. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11045;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;15. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11047;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;17. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11049;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;17. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11051;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;17. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11053;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;19. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11055;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;19. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11057;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;19. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11059;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;21. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11061;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;21. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11063;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;21. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11065;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;23. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11067;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;23. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11069;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;23. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11071;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;25. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11073;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;25. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11075;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;25. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11077;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;27. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11079;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;27. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11081;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;27. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11083;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;29. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11085;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;29. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11087;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;29. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11089;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;31. harmonic current L1;1;A;1s;1s;mean;float;4;;;;11091;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;31. harmonic current L2;1;A;1s;1s;mean;float;4;;;;11093;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;31. harmonic current L3;1;A;1s;1s;mean;float;4;;;;11095;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;fundamental oscillation voltage L1-L2;1;V;1s;1s;mean;float;4;;;;22001;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;fundamental oscillation voltage L2-L3;1;V;1s;1s;mean;float;4;;;;22003;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;fundamental oscillation voltage L3-L1;1;V;1s;1s;mean;float;4;;;;22005;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;3. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22007;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;3. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22009;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;3. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22011;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;5. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22013;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;5. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22015;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;5. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22017;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;7. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22019;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;7. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22021;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;7. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22023;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;9. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22025;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;9. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22027;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;9. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22029;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;11. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22031;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;11. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22033;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;11. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22035;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;13. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22037;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;13. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22039;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;13. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22041;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;15. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22043;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;15. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22045;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;15. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22047;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;17. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22049;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;17. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22051;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;17. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22053;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;19. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22055;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;19. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22057;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;19. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22059;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;21. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22061;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;21. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22063;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;21. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22065;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;23. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22067;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;23. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22069;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;23. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22071;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;25. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22073;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;25. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22075;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;25. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22077;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;27. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22079;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;27. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22081;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;27. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22083;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;29. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22085;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;29. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22087;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;29. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22089;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;31. harmonic voltage L1-L2;1;%;1s;1s;mean;float;4;;;;22091;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;31. harmonic voltage L2-L3;1;%;1s;1s;mean;float;4;;;;22093;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;31. harmonic voltage L3-L1;1;%;1s;1s;mean;float;4;;;;22095;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 3. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;12999;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 3. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13005;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 3. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13011;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 5. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13017;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 5. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13023;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 5. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13029;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 7. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13035;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 7. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13041;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 7. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13047;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 9. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13053;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 9. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13059;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 9. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13065;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 11. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13071;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 11. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13077;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 11. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13083;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 13. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13089;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 13. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13095;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 13. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13101;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 15. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13107;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 15. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13113;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 15. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13119;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 17. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13125;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 17. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13131;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 17. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13137;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 19. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13143;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 19. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13149;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 19. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13155;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 21. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13161;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 21. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13167;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 21. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13173;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 23. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13179;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 23. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13185;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 23. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13191;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 25. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13197;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 25. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13203;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 25. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13209;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 27. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13215;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 27. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13221;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 27. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13227;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 29. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13233;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 29. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13239;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 29. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13245;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 31. harmonic voltage L1-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13251;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 31. harmonic voltage L2-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13257;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 31. harmonic voltage L3-N with time;1;%;1s;1s;mean;float + timestamp;6;;;;13263;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum fundamental oscillation current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19001;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum fundamental oscillation current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19007;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum fundamental oscillation current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19013;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 3. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19019;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 3. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19025;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 3. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19031;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 5. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19037;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 5. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19043;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 5. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19049;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 7. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19055;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 7. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19061;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 7. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19067;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 9. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19073;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 9. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19079;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 9. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19085;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 11. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19091;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 11. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19097;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 11. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19103;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 13. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19109;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 13. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19115;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 13. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19121;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 15. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19127;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 15. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19133;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 15. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19139;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 17. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19145;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 17. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19151;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 17. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19157;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 19. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19163;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 19. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19169;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 19. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19175;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 21. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19181;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 21. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19187;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 21. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19193;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 23. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19199;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 23. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19205;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 23. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19211;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 25. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19217;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 25. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19223;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 25. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19229;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 27. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19235;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 27. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19241;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 27. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19247;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 29. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19253;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 29. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19259;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 29. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19265;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 31. harmonic current L1 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19271;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 31. harmonic current L2 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19277;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;maximum 31. harmonic current L3 with time;1;A;1s;1s;mean;float + timestamp;6;;;;19283;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;connection type;1;;1s;1s;mean;Unsigned long;4;;;;50001;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;voltage transformer yes/no;1;;1s;1s;mean;Unsigned long;4;;;;50003;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;primary voltage;1;;1s;1s;mean;Unsigned long;4;;;;50005;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;secondary voltage;1;;1s;1s;mean;Unsigned long;4;;;;50007;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;current transformer yes/no;1;;1s;1s;mean;Unsigned long;4;;;;50009;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;primary current;1;;1s;1s;mean;Unsigned long;4;;;;50011;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;secondary current;1;;1s;1s;mean;Unsigned long;4;;;;50013;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;line frequency settings;1;;1s;1s;mean;Unsigned long;4;;;;50017;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;zero point suppression;1;%;1s;1s;mean;float;4;;;;50019;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;under an accrual duration;1;;1s;1s;mean;Unsigned long;4;;;;50021;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;synchronization;1;;1s;1s;mean;Unsigned long;4;;;;50023;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;DI 0.0 usage;1;;1s;1s;mean;Unsigned long;4;;;;50025;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;DI 0.0 pulse edge evaluation;1;;1s;1s;mean;Unsigned long;4;;;;50027;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;DI 0.0 usage of the count information;1;;1s;1s;mean;Unsigned long;4;;;;50029;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;DI 0.0 valency of the counter information;1;;1s;1s;mean;Unsigned long;4;;;;50031;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;DO 0.0 switching groups assignment;1;;1s;1s;mean;Unsigned long;4;;;;50033;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;DO 0.0 usage;1;;1s;1s;mean;Unsigned long;4;;;;50035;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;DO 0.0 limit allocation;1;;1s;1s;mean;Unsigned long;4;;;;50037;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;DO 0.0 pulse edge evaluation;1;;1s;1s;mean;Unsigned long;4;;;;50039;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;DO 0.0 source count signal;1;;1s;1s;mean;Unsigned long;4;;;;50041;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;DO 0.0 valency of the counter information;1;;1s;1s;mean;Unsigned long;4;;;;50043;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;DO 0.0 pulse length;1;;1s;1s;mean;Unsigned long;4;;;;50045;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;conversational language;1;;1s;1s;mean;Unsigned long;4;;;;50047;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;phase labels IEC/UL;1;;1s;1s;mean;Unsigned long;4;;;;50049;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;universal counter 1 source;1;;1s;1s;mean;Unsigned long;4;;;;50051;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;display update cycle;1;;1s;1s;mean;Unsigned long;4;;;;50053;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;display contrast;1;;1s;1s;mean;Unsigned long;4;;;;50055;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;display brightness;1;;1s;1s;mean;Unsigned long;4;;;;50057;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;display brightness is reduced;1;;1s;1s;mean;Unsigned long;4;;;;50059;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;brightness duration;1;;1s;1s;mean;Unsigned long;4;;;;50061;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 0 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50063;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 0 hysteresis;1;%;1s;1s;mean;float;4;;;;50065;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 0 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50067;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 0 source;1;;1s;1s;mean;Unsigned long;4;;;;50071;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 0 value;1;;1s;1s;mean;float;4;;;;50073;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 0 mode ?|< ;1;;1s;1s;mean;Unsigned long;4;;;;50075;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 1 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50077;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 1 hysteresis;1;%;1s;1s;mean;float;4;;;;50079;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 1 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50081;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 1 source;1;;1s;1s;mean;Unsigned long;4;;;;50085;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 1 value;1;;1s;1s;mean;float;4;;;;50087;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 1 mode ?|<;1;;1s;1s;mean;Unsigned long;4;;;;50089;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 2 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50091;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 2 hysteresis;1;%;1s;1s;mean;float;4;;;;50093;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 2 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50095;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 2 source;1;;1s;1s;mean;Unsigned long;4;;;;50099;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 2 value;1;;1s;1s;mean;float;4;;;;50101;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 2 mode ?|< ;1;;1s;1s;mean;Unsigned long;4;;;;50103;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 3 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50105;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 3 hysteresis;1;%;1s;1s;mean;float;4;;;;50107;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 3 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50109;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 3 source;1;;1s;1s;mean;Unsigned long;4;;;;50113;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 3 value;1;;1s;1s;mean;float;4;;;;50115;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 3 mode ?|<;1;;1s;1s;mean;Unsigned long;4;;;;50117;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 4 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50119;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 4 hysteresis;1;%;1s;1s;mean;float;4;;;;50121;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 4 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50123;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 4 source;1;;1s;1s;mean;Unsigned long;4;;;;50127;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 4 value;1;;1s;1s;mean;float;4;;;;50129;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 4 mode ?|< ;1;;1s;1s;mean;Unsigned long;4;;;;50131;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 5 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50133;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 5 hysteresis;1;%;1s;1s;mean;float;4;;;;50135;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 5 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50137;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 5 source;1;;1s;1s;mean;Unsigned long;4;;;;50141;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 5 value;1;;1s;1s;mean;float;4;;;;50143;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 5 mode ?|<;1;;1s;1s;mean;Unsigned long;4;;;;50145;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 6 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50147;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 6 hysteresis;1;%;1s;1s;mean;float;4;;;;50149;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 6 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50151;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 6 source;1;;1s;1s;mean;Unsigned long;4;;;;50155;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 6 value;1;;1s;1s;mean;float;4;;;;50157;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 6 mode ?|< ;1;;1s;1s;mean;Unsigned long;4;;;;50159;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 7 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50161;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 7 hysteresis;1;%;1s;1s;mean;float;4;;;;50163;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 7 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50165;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 7 source;1;;1s;1s;mean;Unsigned long;4;;;;50169;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 7 value;1;;1s;1s;mean;float;4;;;;50171;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 7 mode ?|<;1;;1s;1s;mean;Unsigned long;4;;;;50173;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 8 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50175;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 8 hysteresis;1;%;1s;1s;mean;float;4;;;;50177;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 8 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50179;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 8 source;1;;1s;1s;mean;Unsigned long;4;;;;50183;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 8 value;1;;1s;1s;mean;float;4;;;;50185;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 8 mode ?|< ;1;;1s;1s;mean;Unsigned long;4;;;;50187;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 9 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50189;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 9 hysteresis;1;%;1s;1s;mean;float;4;;;;50191;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 9 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50193;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 9 source;1;;1s;1s;mean;Unsigned long;4;;;;50197;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 9 value;1;;1s;1s;mean;float;4;;;;50199;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 9 mode ?|<;1;;1s;1s;mean;Unsigned long;4;;;;50201;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 10 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50203;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 10 hysteresis;1;%;1s;1s;mean;float;4;;;;50205;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 10 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50207;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 10 source;1;;1s;1s;mean;Unsigned long;4;;;;50211;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 10 value;1;;1s;1s;mean;float;4;;;;50213;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 10 mode ?|< ;1;;1s;1s;mean;Unsigned long;4;;;;50215;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 11 ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;50217;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 11 hysteresis;1;%;1s;1s;mean;float;4;;;;50219;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 11 delay;1;s;1s;1s;mean;Unsigned long;4;;;;50221;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 11 source;1;;1s;1s;mean;Unsigned long;4;;;;50225;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 11 value;1;;1s;1s;mean;float;4;;;;50227;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;limit 11 mode ?|<;1;;1s;1s;mean;Unsigned long;4;;;;50229;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;date format;1;;1s;1s;mean;Unsigned long;4;;;;50231;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;daylight saving time;1;;1s;1s;mean;Unsigned long;4;;;;50233;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;time zone;1;min;1s;1s;mean;long;4;;;;50235;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;mediation time moving averages;1;s;1s;1s;mean;Unsigned long;4;;;;50237;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;reactive power numbers used;1;;1s;1s;mean;Unsigned long;4;;;;50239;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;universal counter 1 DI-count signal;1;;1s;1s;mean;Unsigned long;4;;;;50241;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;invert current L1;1;;1s;1s;mean;Unsigned long;4;;;;50243;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;invert current L2;1;;1s;1s;mean;Unsigned long;4;;;;50245;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;invert current L3;1;;1s;1s;mean;Unsigned long;4;;;;50247;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;current lower limit for hourmeter;1;%;1s;1s;mean;Unsigned long;4;;;;50249;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;universal counter 1 source;1;;1s;1s;mean;Unsigned long;4;;;;50251;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;universal counter 2 DI-count signal;1;;1s;1s;mean;Unsigned long;4;;;;50253;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;digital input parameter;1;;1s;1s;mean;Unsigned long;14;;;;61167;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;digital output parameter;1;;1s;1s;mean;stOutputPara;14;;;;61175;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;event recording parameters;1;;1s;1s;mean;stEventPara;16;;;;62101;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;logically linked limit parameters;1;;1s;1s;mean;stCombLimitPara;54;;;;62301;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;IP-address;1;;1s;1s;mean;Unsigned long;4;;;;63001;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;subnet mask;1;;1s;1s;mean;Unsigned long;4;;;;63003;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;gateway;1;;1s;1s;mean;Unsigned long;4;;;;63005;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;bootloader version;1;;1s;1s;mean;Unsigned long;4;;;;63007;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;password protection ON/OFF;1;;1s;1s;mean;Unsigned long;4;;;;63009;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;date of manufacture;1;;1s;1s;mean;Unsigned long;4;;;;63011;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;ethernet protocol;1;;1s;1s;mean;Unsigned long;4;;;;63015;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;protocol module interface 1;1;;1s;1s;mean;Unsigned long;4;;;;63017;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;address module interface 1;1;;1s;1s;mean;Unsigned long;4;;;;63019;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;baudrate module interface 1;1;;1s;1s;mean;Unsigned long;4;;;;63021;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;format module interface 1;1;;1s;1s;mean;Unsigned long;4;;;;63023;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;response time module interface 1;1;ms;1s;1s;mean;Unsigned long;4;;;;63025;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;protocol module interface 2;1;;1s;1s;mean;Unsigned long;4;;;;63033;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;address module interface 2;1;;1s;1s;mean;Unsigned long;4;;;;63035;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;baudrate module interface 2;1;;1s;1s;mean;Unsigned long;4;;;;63037;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;format module interface 2;1;;1s;1s;mean;Unsigned long;4;;;;63039;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;response time module interface 2;1;ms;1s;1s;mean;Unsigned long;4;;;;63041;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;TCP/IP-Port gateway module interface 1;1;ms;1s;1s;mean;Unsigned long;4;;;;63043;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;TCP/IP-Port gateway module interface 2;1;ms;1s;1s;mean;Unsigned long;4;;;;63045;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;profibus ID PAC4200;1;;1s;1s;mean;Unsigned long;4;;;;63065;r;0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;I&M-data PAC4200;1;;1s;1s;mean;stIM0;54;;;;64001;r(w);0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;I&M 0 to I&M 4-data PAC4200;1;;1s;1s;mean;stIM14;178;;;;64028;rw;0x03 & 0x04 & 0x10;
Monitoring;Siemens;Modbus TCP;I&M-data module interface 1;1;;1s;1s;mean;stIM0-;54;;;;64117;r(w);0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;I&M-data module interface 2;1;;1s;1s;mean;stIM0;54;;;;64144;r(w);0x03 & 0x04;
Monitoring;Siemens;Modbus TCP;reset the maximum values;1;;1s;1s;mean;Unsigned short;2;;;;60002;w;0x06;
Monitoring;Siemens;Modbus TCP;reset the minimum values;1;;1s;1s;mean;Unsigned short;2;;;;60003;w;0x06;
Monitoring;Siemens;Modbus TCP;reset the energy meter;1;;1s;1s;mean;Unsigned short;2;;;;60004;w;0x06;
Monitoring;Siemens;Modbus TCP;synchronization of the measurement period;1;;1s;1s;mean;Unsigned short;2;;;;60005;w;0x06;
Monitoring;Siemens;Modbus TCP;tariff switch;1;;1s;1s;mean;Unsigned short;2;;;;60006;w;0x06;
Monitoring;Siemens;Modbus TCP;Acknowledge the diagnostic bit;1;;1s;1s;mean;Unsigned short;2;;;;60007;w;0x06;
Monitoring;Siemens;Modbus TCP;outputs switch (if configured);1;;1s;1s;mean;Unsigned short;2;;;;60008;w;0x06;
Monitoring;Siemens;Modbus TCP;power on command vector group;1;;1s;1s;mean;Unsigned short;2;;;;60009;w;0x06;
Monitoring;Siemens;Modbus TCP;reset the daily energy meters;1;;1s;1s;mean;Unsigned short;2;;;;60010;w;0x06;
Monitoring;Siemens;Modbus TCP;reset the load input record;1;;1s;1s;mean;Unsigned short;2;;;;60011;w;0x06;
Monitoring;Siemens;Modbus TCP;reset the energy record;1;;1s;1s;mean;Unsigned short;2;;;;60012;w;0x06;
Monitoring;Siemens;Modbus TCP;set the standard event-recording conditions;1;;1s;1s;mean;Unsigned short;2;;;;60013;w;0x06;
Monitoring;Siemens;Modbus TCP;set the standard I/O parameters;1;;1s;1s;mean;Unsigned short;2;;;;60014;w;0x06;
Monitoring;Siemens;Modbus TCP;increment date / time;1;;1s;1s;mean;Unsigned long;4;;;;65292;w;0x10;
1 Component Company Bus type Value name Value - factor Value - unit Logging rate sending rate Info value - type size (Byte) Endianness first Register BUS address offset read/write function range
2 Monitoring Siemens Modbus TCP voltage L1-N 1 V 1s 1s mean float 4 1 r 0x03 & 0x04
3 Monitoring Siemens Modbus TCP voltage L2-N 1 V 1s 1s mean float 4 3 r 0x03 & 0x04
4 Monitoring Siemens Modbus TCP voltage L3-N 1 V 1s 1s mean float 4 5 r 0x03 & 0x04
5 Monitoring Siemens Modbus TCP voltage L1-L2 1 V 1s 1s mean float 4 7 r 0x03 & 0x04
6 Monitoring Siemens Modbus TCP voltage L2-L3 1 V 1s 1s mean float 4 9 r 0x03 & 0x04
7 Monitoring Siemens Modbus TCP voltage L3-L1 1 V 1s 1s mean float 4 11 r 0x03 & 0x04
8 Monitoring Siemens Modbus TCP current L1 1 A 1s 1s mean float 4 13 r 0x03 & 0x04
9 Monitoring Siemens Modbus TCP current L2 1 A 1s 1s mean float 4 15 r 0x03 & 0x04
10 Monitoring Siemens Modbus TCP current L3 1 A 1s 1s mean float 4 17 r 0x03 & 0x04
11 Monitoring Siemens Modbus TCP apparent power L1 1 VA 1s 1s mean float 4 19 r 0x03 & 0x04
12 Monitoring Siemens Modbus TCP apparent power L2 1 VA 1s 1s mean float 4 21 r 0x03 & 0x04
13 Monitoring Siemens Modbus TCP apparent power L3 1 VA 1s 1s mean float 4 23 r 0x03 & 0x04
14 Monitoring Siemens Modbus TCP active power L1 1 W 1s 1s mean float 4 25 r 0x03 & 0x04
15 Monitoring Siemens Modbus TCP active power L2 1 W 1s 1s mean float 4 27 r 0x03 & 0x04
16 Monitoring Siemens Modbus TCP active power L3 1 W 1s 1s mean float 4 29 r 0x03 & 0x04
17 Monitoring Siemens Modbus TCP reactive power L1 (Qn) 1 var 1s 1s mean float 4 31 r 0x03 & 0x04
18 Monitoring Siemens Modbus TCP reactive power L2 (Qn) 1 var 1s 1s mean float 4 33 r 0x03 & 0x04
19 Monitoring Siemens Modbus TCP reactive power L3 (Qn) 1 var 1s 1s mean float 4 35 r 0x03 & 0x04
20 Monitoring Siemens Modbus TCP power factor L1 1 1s 1s mean float 4 37 r 0x03 & 0x04
21 Monitoring Siemens Modbus TCP power factor L2 1 1s 1s mean float 4 39 r 0x03 & 0x04
22 Monitoring Siemens Modbus TCP power factor L3 1 1s 1s mean float 4 41 r 0x03 & 0x04
23 Monitoring Siemens Modbus TCP THD voltage L1-L2 1 % 1s 1s mean float 4 43 r 0x03 & 0x04
24 Monitoring Siemens Modbus TCP THD voltage L2-L3 1 % 1s 1s mean float 4 45 r 0x03 & 0x04
25 Monitoring Siemens Modbus TCP THD voltage L3-L1 1 % 1s 1s mean float 4 47 r 0x03 & 0x04
26 Monitoring Siemens Modbus TCP reserved 49 r 0x03 & 0x04
27 Monitoring Siemens Modbus TCP reserved 51 r 0x03 & 0x04
28 Monitoring Siemens Modbus TCP reserved 53 r 0x03 & 0x04
29 Monitoring Siemens Modbus TCP line frequency 1 Hz 1s 1s mean float 4 55 r 0x03 & 0x04
30 Monitoring Siemens Modbus TCP 3-phase average voltage L-N 1 V 1s 1s mean float 4 57 r 0x03 & 0x04
31 Monitoring Siemens Modbus TCP 3-phase average voltage L-L 1 V 1s 1s mean float 4 59 r 0x03 & 0x04
32 Monitoring Siemens Modbus TCP 3-phase average current L-L 1 A 1s 1s mean float 4 61 r 0x03 & 0x04
33 Monitoring Siemens Modbus TCP total apparent power 1 VA 1s 1s mean float 4 63 r 0x03 & 0x04
34 Monitoring Siemens Modbus TCP total active power 1 W 1s 1s mean float 4 65 r 0x03 & 0x04
35 Monitoring Siemens Modbus TCP total reactive power 1 var 1s 1s mean float 4 67 r 0x03 & 0x04
36 Monitoring Siemens Modbus TCP total power factor 1 1s 1s mean float 4 69 r 0x03 & 0x04
37 Monitoring Siemens Modbus TCP amplitude unbalance of voltage 1 % 1s 1s mean float 4 71 r 0x03 & 0x04
38 Monitoring Siemens Modbus TCP amplitude unbalance of current 1 % 1s 1s mean float 4 73 r 0x03 & 0x04
39 Monitoring Siemens Modbus TCP maximum voltage L1-N 1 V 1s 1s mean float 4 75 r 0x03 & 0x04
40 Monitoring Siemens Modbus TCP maximum voltage L2-N 1 V 1s 1s mean float 4 77 r 0x03 & 0x04
41 Monitoring Siemens Modbus TCP maximum voltage L3-N 1 V 1s 1s mean float 4 79 r 0x03 & 0x04
42 Monitoring Siemens Modbus TCP maximum voltage L1-L2 1 V 1s 1s mean float 4 81 r 0x03 & 0x04
43 Monitoring Siemens Modbus TCP maximum voltage L2-L3 1 V 1s 1s mean float 4 83 r 0x03 & 0x04
44 Monitoring Siemens Modbus TCP maximum voltage L3-L1 1 V 1s 1s mean float 4 85 r 0x03 & 0x04
45 Monitoring Siemens Modbus TCP maximum current L1 1 A 1s 1s mean float 4 87 r 0x03 & 0x04
46 Monitoring Siemens Modbus TCP maximum current L2 1 A 1s 1s mean float 4 89 r 0x03 & 0x04
47 Monitoring Siemens Modbus TCP maximum current L3 1 A 1s 1s mean float 4 91 r 0x03 & 0x04
48 Monitoring Siemens Modbus TCP maximum apparent power L1 1 VA 1s 1s mean float 4 93 r 0x03 & 0x04
49 Monitoring Siemens Modbus TCP maximum apparent power L2 1 VA 1s 1s mean float 4 95 r 0x03 & 0x04
50 Monitoring Siemens Modbus TCP maximum apparent power L3 1 VA 1s 1s mean float 4 97 r 0x03 & 0x04
51 Monitoring Siemens Modbus TCP maximum active power L1 1 W 1s 1s mean float 4 99 r 0x03 & 0x04
52 Monitoring Siemens Modbus TCP maximum active power L2 1 W 1s 1s mean float 4 101 r 0x03 & 0x04
53 Monitoring Siemens Modbus TCP maximum active power L3 1 W 1s 1s mean float 4 103 r 0x03 & 0x04
54 Monitoring Siemens Modbus TCP maximum reactive power L1 (Qn) 1 var 1s 1s mean float 4 105 r 0x03 & 0x04
55 Monitoring Siemens Modbus TCP maximum reactive power L2 (Qn) 1 var 1s 1s mean float 4 107 r 0x03 & 0x04
56 Monitoring Siemens Modbus TCP maximum reactive power L3 (Qn) 1 var 1s 1s mean float 4 109 r 0x03 & 0x04
57 Monitoring Siemens Modbus TCP maximum power factor L1 1 1s 1s mean float 4 111 r 0x03 & 0x04
58 Monitoring Siemens Modbus TCP maximum power factor L2 1 1s 1s mean float 4 113 r 0x03 & 0x04
59 Monitoring Siemens Modbus TCP maximum power factor L3 1 1s 1s mean float 4 115 r 0x03 & 0x04
60 Monitoring Siemens Modbus TCP maximum THD voltage L1-L2 1 % 1s 1s mean float 4 117 r 0x03 & 0x04
61 Monitoring Siemens Modbus TCP maximum THD voltage L2-L3 1 % 1s 1s mean float 4 119 r 0x03 & 0x04
62 Monitoring Siemens Modbus TCP maximum THD voltage L3-L1 1 % 1s 1s mean float 4 121 r 0x03 & 0x04
63 Monitoring Siemens Modbus TCP reserved 123 r 0x03 & 0x04
64 Monitoring Siemens Modbus TCP reserved 125 r 0x03 & 0x04
65 Monitoring Siemens Modbus TCP reserved 127 r 0x03 & 0x04
66 Monitoring Siemens Modbus TCP maximum line frequency 1 Hz 1s 1s mean float 4 129 r 0x03 & 0x04
67 Monitoring Siemens Modbus TCP maximum 3-phase average voltage L-N 1 V 1s 1s mean float 4 131 r 0x03 & 0x04
68 Monitoring Siemens Modbus TCP maximum 3-phase average voltage L-L 1 V 1s 1s mean float 4 133 r 0x03 & 0x04
69 Monitoring Siemens Modbus TCP maximum 3-phase average current L-L 1 A 1s 1s mean float 4 135 r 0x03 & 0x04
70 Monitoring Siemens Modbus TCP maximum total apparent power 1 VA 1s 1s mean float 4 137 r 0x03 & 0x04
71 Monitoring Siemens Modbus TCP maximum total active power 1 W 1s 1s mean float 4 139 r 0x03 & 0x04
72 Monitoring Siemens Modbus TCP maximum total reactive power (Qn) 1 var 1s 1s mean float 4 141 r 0x03 & 0x04
73 Monitoring Siemens Modbus TCP maximum total power factor 1 1s 1s mean float 4 143 r 0x03 & 0x04
74 Monitoring Siemens Modbus TCP minimal voltage L1-N 1 V 1s 1s mean float 4 145 r 0x03 & 0x04
75 Monitoring Siemens Modbus TCP minimal voltage L2-N 1 V 1s 1s mean float 4 147 r 0x03 & 0x04
76 Monitoring Siemens Modbus TCP minimal voltage L3-N 1 V 1s 1s mean float 4 149 r 0x03 & 0x04
77 Monitoring Siemens Modbus TCP minimal voltage L1-L2 1 V 1s 1s mean float 4 151 r 0x03 & 0x04
78 Monitoring Siemens Modbus TCP minimal voltage L2-L3 1 V 1s 1s mean float 4 153 r 0x03 & 0x04
79 Monitoring Siemens Modbus TCP minimal voltage L3-L1 1 V 1s 1s mean float 4 155 r 0x03 & 0x04
80 Monitoring Siemens Modbus TCP minimal current L1 1 A 1s 1s mean float 4 157 r 0x03 & 0x04
81 Monitoring Siemens Modbus TCP minimal current L2 1 A 1s 1s mean float 4 159 r 0x03 & 0x04
82 Monitoring Siemens Modbus TCP minimal current L3 1 A 1s 1s mean float 4 161 r 0x03 & 0x04
83 Monitoring Siemens Modbus TCP minimal apparent power L1 1 VA 1s 1s mean float 4 163 r 0x03 & 0x04
84 Monitoring Siemens Modbus TCP minimal apparent power L2 1 VA 1s 1s mean float 4 165 r 0x03 & 0x04
85 Monitoring Siemens Modbus TCP minimal apparent power L3 1 VA 1s 1s mean float 4 167 r 0x03 & 0x04
86 Monitoring Siemens Modbus TCP minimal active power L1 1 W 1s 1s mean float 4 169 r 0x03 & 0x04
87 Monitoring Siemens Modbus TCP minimal active power L2 1 W 1s 1s mean float 4 171 r 0x03 & 0x04
88 Monitoring Siemens Modbus TCP minimal active power L3 1 W 1s 1s mean float 4 173 r 0x03 & 0x04
89 Monitoring Siemens Modbus TCP minimal reactive power L1 (Qn) 1 var 1s 1s mean float 4 175 r 0x03 & 0x04
90 Monitoring Siemens Modbus TCP minimal reactive power L2 (Qn) 1 var 1s 1s mean float 4 177 r 0x03 & 0x04
91 Monitoring Siemens Modbus TCP minimal reactive power L3 (Qn) 1 var 1s 1s mean float 4 179 r 0x03 & 0x04
92 Monitoring Siemens Modbus TCP minimal power factor L1 1 1s 1s mean float 4 181 r 0x03 & 0x04
93 Monitoring Siemens Modbus TCP minimal power factor L2 1 1s 1s mean float 4 183 r 0x03 & 0x04
94 Monitoring Siemens Modbus TCP minimal power factor L3 1 1s 1s mean float 4 185 r 0x03 & 0x04
95 Monitoring Siemens Modbus TCP minimal line frequency 1 Hz 1s 1s mean float 4 187 r 0x03 & 0x04
96 Monitoring Siemens Modbus TCP minimal 3-phase average voltage L-N 1 V 1s 1s mean float 4 189 r 0x03 & 0x04
97 Monitoring Siemens Modbus TCP minimal 3-phase average voltage L-L 1 V 1s 1s mean float 4 191 r 0x03 & 0x04
98 Monitoring Siemens Modbus TCP minimal 3-phase average current L-L 1 A 1s 1s mean float 4 193 r 0x03 & 0x04
99 Monitoring Siemens Modbus TCP minimal total apparent power 1 VA 1s 1s mean float 4 195 r 0x03 & 0x04
100 Monitoring Siemens Modbus TCP minimal total active power 1 W 1s 1s mean float 4 197 r 0x03 & 0x04
101 Monitoring Siemens Modbus TCP minimal total reactive power 1 var 1s 1s mean float 4 199 r 0x03 & 0x04
102 Monitoring Siemens Modbus TCP minimal total power factor 1 1s 1s mean float 4 201 r 0x03 & 0x04
103 Monitoring Siemens Modbus TCP limit value violations 1 1s 1s mean Unsigned long 4 203 r 0x03 & 0x04
104 Monitoring Siemens Modbus TCP PMD diagnostic and status 1 1s 1s mean Unsigned long 4 205 r 0x03 & 0x04
105 Monitoring Siemens Modbus TCP digital outputs status 1 1s 1s mean Unsigned long 4 207 r 0x03 & 0x04
106 Monitoring Siemens Modbus TCP digital input status 1 1s 1s mean Unsigned long 4 209 r 0x03 & 0x04
107 Monitoring Siemens Modbus TCP active rate 1 1s 1s mean Unsigned long 4 211 r 0x03 & 0x04
108 Monitoring Siemens Modbus TCP hourmeter 1 s 1s 1s mean Unsigned long 4 213 rw 0x03 & 0x04 & 0x10
109 Monitoring Siemens Modbus TCP universal counter 1 1s 1s mean Unsigned long 4 215 rw 0x03 & 0x04 & 0x10
110 Monitoring Siemens Modbus TCP change counter of basic parameters 1 1s 1s mean Unsigned long 4 217 r 0x03 & 0x04
111 Monitoring Siemens Modbus TCP change counter of all parameters 1 1s 1s mean Unsigned long 4 219 r 0x03 & 0x04
112 Monitoring Siemens Modbus TCP change counter limits 1 1s 1s mean Unsigned long 4 221 r 0x03 & 0x04
113 Monitoring Siemens Modbus TCP counter all events 1 1s 1s mean Unsigned long 4 223 r 0x03 & 0x04
114 Monitoring Siemens Modbus TCP counter of all alarms 1 1s 1s mean Unsigned long 4 225 r 0x03 & 0x04
115 Monitoring Siemens Modbus TCP counter on all load output records 1 1s 1s mean Unsigned long 4 227 r 0x03 & 0x04
116 Monitoring Siemens Modbus TCP counter for other 1 1s 1s mean Unsigned long 4 229 r 0x03 & 0x04
117 Monitoring Siemens Modbus TCP status digital outputs module 1 1 1s 1s mean Unsigned long 4 231 r 0x03 & 0x04
118 Monitoring Siemens Modbus TCP status digital input module 1 1 1s 1s mean Unsigned long 4 233 r 0x03 & 0x04
119 Monitoring Siemens Modbus TCP status digital outputs module 2 1 1s 1s mean Unsigned long 4 235 r 0x03 & 0x04
120 Monitoring Siemens Modbus TCP status digital input module 2 1 1s 1s mean Unsigned long 4 237 r 0x03 & 0x04
121 Monitoring Siemens Modbus TCP cos ? L1 1 1s 1s mean float 4 243 r 0x03 & 0x04
122 Monitoring Siemens Modbus TCP cos ? L2 1 1s 1s mean float 4 245 r 0x03 & 0x04
123 Monitoring Siemens Modbus TCP cos ? L3 1 1s 1s mean float 4 247 r 0x03 & 0x04
124 Monitoring Siemens Modbus TCP phase shift angle L1 1 1s 1s mean float 4 249 r 0x03 & 0x04
125 Monitoring Siemens Modbus TCP phase shift angle L2 1 1s 1s mean float 4 251 r 0x03 & 0x04
126 Monitoring Siemens Modbus TCP phase shift angle L3 1 1s 1s mean float 4 253 r 0x03 & 0x04
127 Monitoring Siemens Modbus TCP phase angle L1-L2 1 1s 1s mean float 4 255 r 0x03 & 0x04
128 Monitoring Siemens Modbus TCP phase angle L2-L3 1 1s 1s mean float 4 257 r 0x03 & 0x04
129 Monitoring Siemens Modbus TCP phase angle L1-L3 1 1s 1s mean float 4 259 r 0x03 & 0x04
130 Monitoring Siemens Modbus TCP THD voltage L1 1 % 1s 1s mean float 4 261 r 0x03 & 0x04
131 Monitoring Siemens Modbus TCP THD voltage L2 1 % 1s 1s mean float 4 263 r 0x03 & 0x04
132 Monitoring Siemens Modbus TCP THD voltage L3 1 % 1s 1s mean float 4 265 r 0x03 & 0x04
133 Monitoring Siemens Modbus TCP THD current L1 1 % 1s 1s mean float 4 267 r 0x03 & 0x04
134 Monitoring Siemens Modbus TCP THD current L2 1 % 1s 1s mean float 4 269 r 0x03 & 0x04
135 Monitoring Siemens Modbus TCP THD current L3 1 % 1s 1s mean float 4 271 r 0x03 & 0x04
136 Monitoring Siemens Modbus TCP distortion power L1 1 A 1s 1s mean float 4 273 r 0x03 & 0x04
137 Monitoring Siemens Modbus TCP distortion power L2 1 A 1s 1s mean float 4 275 r 0x03 & 0x04
138 Monitoring Siemens Modbus TCP distortion power L3 1 A 1s 1s mean float 4 277 r 0x03 & 0x04
139 Monitoring Siemens Modbus TCP total reactive power L1 (Qtot) 1 var 1s 1s mean float 4 279 r 0x03 & 0x04
140 Monitoring Siemens Modbus TCP total reactive power L2 (Qtot) 1 var 1s 1s mean float 4 281 r 0x03 & 0x04
141 Monitoring Siemens Modbus TCP total reactive power L3 (Qtot) 1 var 1s 1s mean float 4 283 r 0x03 & 0x04
142 Monitoring Siemens Modbus TCP reactive power L1 (Q1) 1 var 1s 1s mean float 4 285 r 0x03 & 0x04
143 Monitoring Siemens Modbus TCP reactive power L1 (Q1) 1 var 1s 1s mean float 4 287 r 0x03 & 0x04
144 Monitoring Siemens Modbus TCP reactive power L1 (Q1) 1 var 1s 1s mean float 4 289 r 0x03 & 0x04
145 Monitoring Siemens Modbus TCP voltage unbalance 1 % 1s 1s mean float 4 291 r 0x03 & 0x04
146 Monitoring Siemens Modbus TCP current unbalance 1 % 1s 1s mean float 4 293 r 0x03 & 0x04
147 Monitoring Siemens Modbus TCP neutral conductor current 1 A 1s 1s mean float 4 295 r 0x03 & 0x04
148 Monitoring Siemens Modbus TCP total reactive power (Qtot) 1 var 1s 1s mean float 4 297 r 0x03 & 0x04
149 Monitoring Siemens Modbus TCP total reactive power (Q1) 1 var 1s 1s mean float 4 299 r 0x03 & 0x04
150 Monitoring Siemens Modbus TCP shared on mean voltage L1-N 1 V 1s 1s mean float 4 301 r 0x03 & 0x04
151 Monitoring Siemens Modbus TCP shared on mean voltage L2-N 1 V 1s 1s mean float 4 303 r 0x03 & 0x04
152 Monitoring Siemens Modbus TCP shared on mean voltage L3-N 1 V 1s 1s mean float 4 305 r 0x03 & 0x04
153 Monitoring Siemens Modbus TCP shared on mean voltage L1-L2 1 V 1s 1s mean float 4 307 r 0x03 & 0x04
154 Monitoring Siemens Modbus TCP shared on mean voltage L2-L3 1 V 1s 1s mean float 4 309 r 0x03 & 0x04
155 Monitoring Siemens Modbus TCP shared on mean voltage L3-L1 1 V 1s 1s mean float 4 311 r 0x03 & 0x04
156 Monitoring Siemens Modbus TCP shared on mean current L1 1 A 1s 1s mean float 4 313 r 0x03 & 0x04
157 Monitoring Siemens Modbus TCP shared on mean current L2 1 A 1s 1s mean float 4 315 r 0x03 & 0x04
158 Monitoring Siemens Modbus TCP shared on mean current L3 1 A 1s 1s mean float 4 317 r 0x03 & 0x04
159 Monitoring Siemens Modbus TCP shared on mean apparent power L1 1 VA 1s 1s mean float 4 319 r 0x03 & 0x04
160 Monitoring Siemens Modbus TCP shared on mean apparent power L2 1 VA 1s 1s mean float 4 321 r 0x03 & 0x04
161 Monitoring Siemens Modbus TCP shared on mean apparent power L3 1 VA 1s 1s mean float 4 323 r 0x03 & 0x04
162 Monitoring Siemens Modbus TCP shared on mean active power L1 1 W 1s 1s mean float 4 325 r 0x03 & 0x04
163 Monitoring Siemens Modbus TCP shared on mean active power L2 1 W 1s 1s mean float 4 327 r 0x03 & 0x04
164 Monitoring Siemens Modbus TCP shared on mean active power L3 1 W 1s 1s mean float 4 329 r 0x03 & 0x04
165 Monitoring Siemens Modbus TCP shared on mean reactive power L1 (Qn) 1 var 1s 1s mean float 4 331 r 0x03 & 0x04
166 Monitoring Siemens Modbus TCP shared on mean reactive power L2 (Qn) 1 var 1s 1s mean float 4 333 r 0x03 & 0x04
167 Monitoring Siemens Modbus TCP shared on mean reactive power L3 (Qn) 1 var 1s 1s mean float 4 335 r 0x03 & 0x04
168 Monitoring Siemens Modbus TCP shared on mean total reactive power L1 (Qtot) 1 var 1s 1s mean float 4 337 r 0x03 & 0x04
169 Monitoring Siemens Modbus TCP shared on mean total reactive power L2 (Qtot) 1 var 1s 1s mean float 4 339 r 0x03 & 0x04
170 Monitoring Siemens Modbus TCP shared on mean total reactive power L3 (Qtot) 1 var 1s 1s mean float 4 341 r 0x03 & 0x04
171 Monitoring Siemens Modbus TCP shared on mean reactive power L1 (Q1) 1 var 1s 1s mean float 4 343 r 0x03 & 0x04
172 Monitoring Siemens Modbus TCP shared on mean reactive power L2 (Q1) 1 var 1s 1s mean float 4 345 r 0x03 & 0x04
173 Monitoring Siemens Modbus TCP shared on mean reactive power L3 (Q1) 1 var 1s 1s mean float 4 347 r 0x03 & 0x04
174 Monitoring Siemens Modbus TCP shared on mean power factor L1 1 1s 1s mean float 4 349 r 0x03 & 0x04
175 Monitoring Siemens Modbus TCP shared on mean power factor L2 1 1s 1s mean float 4 351 r 0x03 & 0x04
176 Monitoring Siemens Modbus TCP shared on mean power factor L3 1 1s 1s mean float 4 353 r 0x03 & 0x04
177 Monitoring Siemens Modbus TCP shared on mean total apparent power 1 VA 1s 1s mean float 4 355 r 0x03 & 0x04
178 Monitoring Siemens Modbus TCP shared on mean total active power 1 W 1s 1s mean float 4 357 r 0x03 & 0x04
179 Monitoring Siemens Modbus TCP shared on mean total reactive power (Qn) 1 var 1s 1s mean float 4 359 r 0x03 & 0x04
180 Monitoring Siemens Modbus TCP shared on mean total reactive power (Qtot) 1 var 1s 1s mean float 4 361 r 0x03 & 0x04
181 Monitoring Siemens Modbus TCP shared on mean total reactive power (Q1) 1 var 1s 1s mean float 4 363 r 0x03 & 0x04
182 Monitoring Siemens Modbus TCP shared on mean total power factor 1 1s 1s mean float 4 365 r 0x03 & 0x04
183 Monitoring Siemens Modbus TCP shared on mean neutral conductor current 1 A 1s 1s mean float 4 367 r 0x03 & 0x04
184 Monitoring Siemens Modbus TCP process hourmeter 1 s 1s 1s mean Unsigned long 4 369 rw 0x03 & 0x04 & 0x10
185 Monitoring Siemens Modbus TCP universal counter 2 1 1s 1s mean Unsigned long 4 371 rw 0x03 & 0x04 & 0x10
186 Monitoring Siemens Modbus TCP pulse counter 0 1 1s 1s mean Unsigned long 4 373 rw 0x03 & 0x04 & 0x10
187 Monitoring Siemens Modbus TCP pulse counter 02 1 1s 1s mean Unsigned long 4 375 rw 0x03 & 0x04 & 0x10
188 Monitoring Siemens Modbus TCP pulse counter 03 1 1s 1s mean Unsigned long 4 377 rw 0x03 & 0x04 & 0x10
189 Monitoring Siemens Modbus TCP pulse counter 04 1 1s 1s mean Unsigned long 4 379 rw 0x03 & 0x04 & 0x10
190 Monitoring Siemens Modbus TCP pulse counter 05 1 1s 1s mean Unsigned long 4 381 rw 0x03 & 0x04 & 0x10
191 Monitoring Siemens Modbus TCP pulse counter 06 1 1s 1s mean Unsigned long 4 383 rw 0x03 & 0x04 & 0x10
192 Monitoring Siemens Modbus TCP pulse counter 07 1 1s 1s mean Unsigned long 4 385 rw 0x03 & 0x04 & 0x10
193 Monitoring Siemens Modbus TCP pulse counter 08 1 1s 1s mean Unsigned long 4 387 rw 0x03 & 0x04 & 0x10
194 Monitoring Siemens Modbus TCP pulse counter 09 1 1s 1s mean Unsigned long 4 389 rw 0x03 & 0x04 & 0x10
195 Monitoring Siemens Modbus TCP pulse counter 10 1 1s 1s mean Unsigned long 4 391 rw 0x03 & 0x04 & 0x10
196 Monitoring Siemens Modbus TCP total power factor reference in the current period 1 1s 1s mean float 4 479 r 0x03 & 0x04
197 Monitoring Siemens Modbus TCP total power factor output in the current period 1 1s 1s mean float 4 481 r 0x03 & 0x04
198 Monitoring Siemens Modbus TCP timestamp of the current period 1 1s 1s mean timestamp 8 483 r 0x03 & 0x04
199 Monitoring Siemens Modbus TCP average apparent power in the current period 1 VA 1s 1s mean float 4 489 r 0x03 & 0x04
200 Monitoring Siemens Modbus TCP average active power reference in the current period 1 W 1s 1s mean float 4 491 r 0x03 & 0x04
201 Monitoring Siemens Modbus TCP average reactive power reference in the current period 1 var 1s 1s mean float 4 493 r 0x03 & 0x04
202 Monitoring Siemens Modbus TCP average active power output in the current period 1 W 1s 1s mean float 4 495 r 0x03 & 0x04
203 Monitoring Siemens Modbus TCP average reactive power output in the current period 1 var 1s 1s mean float 4 497 r 0x03 & 0x04
204 Monitoring Siemens Modbus TCP cumulated apparent power in the current period 1 VA 1s 1s mean float 4 499 r 0x03 & 0x04
205 Monitoring Siemens Modbus TCP cumulated active power reference in the current period 1 W 1s 1s mean float 4 501 r 0x03 & 0x04
206 Monitoring Siemens Modbus TCP cumulated reactive power reference in the current period 1 var 1s 1s mean float 4 503 r 0x03 & 0x04
207 Monitoring Siemens Modbus TCP cumulated active power output in the current period 1 W 1s 1s mean float 4 505 r 0x03 & 0x04
208 Monitoring Siemens Modbus TCP cumulated reactive power output in the current period 1 var 1s 1s mean float 4 507 r 0x03 & 0x04
209 Monitoring Siemens Modbus TCP maxumum active power of the current peroid 1 W 1s 1s mean float 4 509 r 0x03 & 0x04
210 Monitoring Siemens Modbus TCP minimum active power of the current peroid 1 W 1s 1s mean float 4 511 r 0x03 & 0x04
211 Monitoring Siemens Modbus TCP maxumum reactive power of the current peroid 1 var 1s 1s mean float 4 513 r 0x03 & 0x04
212 Monitoring Siemens Modbus TCP minimum reactive power of the current peroid 1 var 1s 1s mean float 4 515 r 0x03 & 0x04
213 Monitoring Siemens Modbus TCP length of the current peroid 1 s 1s 1s mean Unsigned long 4 517 r 0x03 & 0x04
214 Monitoring Siemens Modbus TCP time since the beginning of the current period 1 s 1s 1s mean Unsigned long 4 519 r 0x03 & 0x04
215 Monitoring Siemens Modbus TCP actual subinterval duration 1 s 1s 1s mean Unsigned long 4 521 r 0x03 & 0x04
216 Monitoring Siemens Modbus TCP imformation of the last period 1 1s 1s mean Unsigned long 4 523 r 0x03 & 0x04
217 Monitoring Siemens Modbus TCP maxumum apparent power of the current peroid 1 VA 1s 1s mean float 4 525 r 0x03 & 0x04
218 Monitoring Siemens Modbus TCP minimum apparent power of the current peroid 1 VA 1s 1s mean float 4 527 r 0x03 & 0x04
219 Monitoring Siemens Modbus TCP cumulated active power in respect of the current period 1 W 1s 1s mean float 4 529 r 0x03 & 0x04
220 Monitoring Siemens Modbus TCP cumulated reactive power in respect of the current period 1 var 1s 1s mean float 4 531 r 0x03 & 0x04
221 Monitoring Siemens Modbus TCP cumulated active power output in the current period 1 W 1s 1s mean float 4 533 r 0x03 & 0x04
222 Monitoring Siemens Modbus TCP cumulated reactive power output in the current period 1 var 1s 1s mean float 4 535 r 0x03 & 0x04
223 Monitoring Siemens Modbus TCP maximum active power of the current period 1 W 1s 1s mean float 4 537 r 0x03 & 0x04
224 Monitoring Siemens Modbus TCP minimum active power of the current period 1 W 1s 1s mean float 4 539 r 0x03 & 0x04
225 Monitoring Siemens Modbus TCP maximum reactive power of the current period 1 var 1s 1s mean float 4 541 r 0x03 & 0x04
226 Monitoring Siemens Modbus TCP minimum reactive power of the current period 1 var 1s 1s mean float 4 543 r 0x03 & 0x04
227 Monitoring Siemens Modbus TCP date / time 1 1s 1s mean timestamp 8 797 rw 0x03 & 0x04 & 0x10
228 Monitoring Siemens Modbus TCP related active energy tariff 1 1 Wh 1s 1s mean double 8 801 rw 0x03 & 0x04 & 0x10
229 Monitoring Siemens Modbus TCP related active energy tariff 2 1 Wh 1s 1s mean double 8 805 rw 0x03 & 0x04 & 0x10
230 Monitoring Siemens Modbus TCP delivered active energy tariff 1 1 Wh 1s 1s mean double 8 809 rw 0x03 & 0x04 & 0x10
231 Monitoring Siemens Modbus TCP delivered active energy tariff 2 1 Wh 1s 1s mean double 8 813 rw 0x03 & 0x04 & 0x10
232 Monitoring Siemens Modbus TCP related reactive energy tariff 1 1 varh 1s 1s mean double 8 817 rw 0x03 & 0x04 & 0x10
233 Monitoring Siemens Modbus TCP related reactive energy tariff 2 1 varh 1s 1s mean double 8 821 rw 0x03 & 0x04 & 0x10
234 Monitoring Siemens Modbus TCP delivered reactive energy tariff 1 1 varh 1s 1s mean double 8 825 rw 0x03 & 0x04 & 0x10
235 Monitoring Siemens Modbus TCP delivered reactive energy tariff 2 1 varh 1s 1s mean double 8 829 rw 0x03 & 0x04 & 0x10
236 Monitoring Siemens Modbus TCP translucent energy tariff 1 1 VAh 1s 1s mean double 8 833 rw 0x03 & 0x04 & 0x10
237 Monitoring Siemens Modbus TCP translucent energy tariff 2 1 VAh 1s 1s mean double 8 837 rw 0x03 & 0x04 & 0x10
238 Monitoring Siemens Modbus TCP process active energy 1 Wh 1s 1s mean double 8 841 rw 0x03 & 0x04 & 0x10
239 Monitoring Siemens Modbus TCP process reactive energy 1 varh 1s 1s mean double 8 845 rw 0x03 & 0x04 & 0x10
240 Monitoring Siemens Modbus TCP process translucent energy 1 VAh 1s 1s mean double 8 849 rw 0x03 & 0x04 & 0x10
241 Monitoring Siemens Modbus TCP process active energy - prior measurement 1 Wh 1s 1s mean double 8 853 rw 0x03 & 0x04 & 0x10
242 Monitoring Siemens Modbus TCP process reactive energy - prior measurement 1 varh 1s 1s mean double 8 857 rw 0x03 & 0x04 & 0x10
243 Monitoring Siemens Modbus TCP process translucent energy - prior measurement 1 VAh 1s 1s mean double 8 861 rw 0x03 & 0x04 & 0x10
244 Monitoring Siemens Modbus TCP date / time 1 1s 1s mean Unsigned long 4 2799 r 0x03 & 0x04
245 Monitoring Siemens Modbus TCP related active energy tariff 1 1 Wh 1s 1s mean float 4 2801 r 0x03 & 0x04
246 Monitoring Siemens Modbus TCP related active energy tariff 2 1 Wh 1s 1s mean float 4 2803 r 0x03 & 0x04
247 Monitoring Siemens Modbus TCP delivered active energy tariff 1 1 Wh 1s 1s mean float 4 2805 r 0x03 & 0x04
248 Monitoring Siemens Modbus TCP delivered active energy tariff 2 1 Wh 1s 1s mean float 4 2807 r 0x03 & 0x04
249 Monitoring Siemens Modbus TCP related reactive energy tariff 1 1 varh 1s 1s mean float 4 2809 r 0x03 & 0x04
250 Monitoring Siemens Modbus TCP related reactive energy tariff 2 1 varh 1s 1s mean float 4 2811 r 0x03 & 0x04
251 Monitoring Siemens Modbus TCP delivered reactive energy tariff 1 1 varh 1s 1s mean float 4 2813 r 0x03 & 0x04
252 Monitoring Siemens Modbus TCP delivered reactive energy tariff 2 1 varh 1s 1s mean float 4 2815 r 0x03 & 0x04
253 Monitoring Siemens Modbus TCP translucent energy tariff 1 1 VAh 1s 1s mean float 4 2817 r 0x03 & 0x04
254 Monitoring Siemens Modbus TCP translucent energy tariff 2 1 VAh 1s 1s mean float 4 2819 r 0x03 & 0x04
255 Monitoring Siemens Modbus TCP process active energy 1 Wh 1s 1s mean float 4 2821 r 0x03 & 0x04
256 Monitoring Siemens Modbus TCP process reactive energy 1 varh 1s 1s mean float 4 2823 r 0x03 & 0x04
257 Monitoring Siemens Modbus TCP process translucent energy 1 VAh 1s 1s mean float 4 2825 r 0x03 & 0x04
258 Monitoring Siemens Modbus TCP process active energy - prior measurement 1 Wh 1s 1s mean float 4 2827 r 0x03 & 0x04
259 Monitoring Siemens Modbus TCP process reactive energy - prior measurement 1 varh 1s 1s mean float 4 2829 r 0x03 & 0x04
260 Monitoring Siemens Modbus TCP process translucent energy - prior measurement 1 VAh 1s 1s mean float 4 2831 r 0x03 & 0x04
261 Monitoring Siemens Modbus TCP maximum voltage L1-N with time 1 V 1s 1s mean float + timestamp 12 3001 r 0x03 & 0x04
262 Monitoring Siemens Modbus TCP maximum voltage L2-N with time 1 V 1s 1s mean float + timestamp 12 3007 r 0x03 & 0x04
263 Monitoring Siemens Modbus TCP maximum voltage L3-N with time 1 V 1s 1s mean float + timestamp 12 3013 r 0x03 & 0x04
264 Monitoring Siemens Modbus TCP maximum voltage L1-L2 with time 1 V 1s 1s mean float + timestamp 12 3019 r 0x03 & 0x04
265 Monitoring Siemens Modbus TCP maximum voltage L2-L3 with time 1 V 1s 1s mean float + timestamp 12 3025 r 0x03 & 0x04
266 Monitoring Siemens Modbus TCP maximum voltage L3-L1 with time 1 V 1s 1s mean float + timestamp 12 3031 r 0x03 & 0x04
267 Monitoring Siemens Modbus TCP maximum current L1 with time 1 A 1s 1s mean float + timestamp 12 3037 r 0x03 & 0x04
268 Monitoring Siemens Modbus TCP maximum current L2 with time 1 A 1s 1s mean float + timestamp 12 3043 r 0x03 & 0x04
269 Monitoring Siemens Modbus TCP maximum current L3 with time 1 A 1s 1s mean float + timestamp 12 3049 r 0x03 & 0x04
270 Monitoring Siemens Modbus TCP maximum apparent power L1 with time 1 VA 1s 1s mean float + timestamp 12 3055 r 0x03 & 0x04
271 Monitoring Siemens Modbus TCP maximum apparent power L2 with time 1 VA 1s 1s mean float + timestamp 12 3061 r 0x03 & 0x04
272 Monitoring Siemens Modbus TCP maximum apparent power L3 with time 1 VA 1s 1s mean float + timestamp 12 3067 r 0x03 & 0x04
273 Monitoring Siemens Modbus TCP maximum active power L1 with time 1 W 1s 1s mean float + timestamp 12 3073 r 0x03 & 0x04
274 Monitoring Siemens Modbus TCP maximum active power L2 with time 1 W 1s 1s mean float + timestamp 12 3079 r 0x03 & 0x04
275 Monitoring Siemens Modbus TCP maximum active power L3 with time 1 W 1s 1s mean float + timestamp 12 3085 r 0x03 & 0x04
276 Monitoring Siemens Modbus TCP maximum reactive power L1 (Qn) with time 1 var 1s 1s mean float + timestamp 12 3091 r 0x03 & 0x04
277 Monitoring Siemens Modbus TCP maximum reactive power L2 (Qn) with time 1 var 1s 1s mean float + timestamp 12 3097 r 0x03 & 0x04
278 Monitoring Siemens Modbus TCP maximum reactive power L3 (Qn) with time 1 var 1s 1s mean float + timestamp 12 3103 r 0x03 & 0x04
279 Monitoring Siemens Modbus TCP maximum total reactive power L1 (Qtot) with time 1 var 1s 1s mean float + timestamp 12 3109 r 0x03 & 0x04
280 Monitoring Siemens Modbus TCP maximum total reactive power L2 (Qtot) with time 1 var 1s 1s mean float + timestamp 12 3115 r 0x03 & 0x04
281 Monitoring Siemens Modbus TCP maximum total reactive power L3 (Qtot) with time 1 var 1s 1s mean float + timestamp 12 3121 r 0x03 & 0x04
282 Monitoring Siemens Modbus TCP maximum reactive power L1 (Q1) with time 1 var 1s 1s mean float + timestamp 12 3127 r 0x03 & 0x04
283 Monitoring Siemens Modbus TCP maximum reactive power L2 (Q1) with time 1 var 1s 1s mean float + timestamp 12 3133 r 0x03 & 0x04
284 Monitoring Siemens Modbus TCP maximum reactive power L3 (Q1) with time 1 var 1s 1s mean float + timestamp 12 3139 r 0x03 & 0x04
285 Monitoring Siemens Modbus TCP maximum power factor L1 with time 1 1s 1s mean float + timestamp 12 3145 r 0x03 & 0x04
286 Monitoring Siemens Modbus TCP maximum power factor L2 with time 1 1s 1s mean float + timestamp 12 3151 r 0x03 & 0x04
287 Monitoring Siemens Modbus TCP maximum power factor L3 with time 1 1s 1s mean float + timestamp 12 3157 r 0x03 & 0x04
288 Monitoring Siemens Modbus TCP maximum THD voltage L1-L2 based on the fundamental frequency with time 1 % 1s 1s mean float + timestamp 12 3163 r 0x03 & 0x04
289 Monitoring Siemens Modbus TCP maximum THD voltage L2-L3 based on the fundamental frequency with time 1 % 1s 1s mean float + timestamp 12 3169 r 0x03 & 0x04
290 Monitoring Siemens Modbus TCP maximum THD voltage L3-L1 based on the fundamental frequency with time 1 % 1s 1s mean float + timestamp 12 3175 r 0x03 & 0x04
291 Monitoring Siemens Modbus TCP maximum cos ? L1 with time 1 cos ?_L1 1s 1s mean float + timestamp 12 3199 r 0x03 & 0x04
292 Monitoring Siemens Modbus TCP maximum cos ? L2 with time 1 cos ?_L2 1s 1s mean float + timestamp 12 3205 r 0x03 & 0x04
293 Monitoring Siemens Modbus TCP maximum cos ? L3 with time 1 cos ?_L3 1s 1s mean float + timestamp 12 3211 r 0x03 & 0x04
294 Monitoring Siemens Modbus TCP maximum phase shift angle L1 with time 1 1s 1s mean float + timestamp 12 3217 r 0x03 & 0x04
295 Monitoring Siemens Modbus TCP maximum phase shift angle L2 with time 1 1s 1s mean float + timestamp 12 3223 r 0x03 & 0x04
296 Monitoring Siemens Modbus TCP maximum phase shift angle L3 with time 1 1s 1s mean float + timestamp 12 3229 r 0x03 & 0x04
297 Monitoring Siemens Modbus TCP maximum phase angle L1-L2 with time 1 1s 1s mean float + timestamp 12 3235 r 0x03 & 0x04
298 Monitoring Siemens Modbus TCP maximum phase angle L2-L3 with time 1 1s 1s mean float + timestamp 12 3241 r 0x03 & 0x04
299 Monitoring Siemens Modbus TCP maximum phase angle L1-L3 with time 1 1s 1s mean float + timestamp 12 3247 r 0x03 & 0x04
300 Monitoring Siemens Modbus TCP maximum THD voltage L1 with time 1 % 1s 1s mean float + timestamp 12 3253 r 0x03 & 0x04
301 Monitoring Siemens Modbus TCP maximum THD voltage L2 with time 1 % 1s 1s mean float + timestamp 12 3259 r 0x03 & 0x04
302 Monitoring Siemens Modbus TCP maximum THD voltage L3 with time 1 % 1s 1s mean float + timestamp 12 3265 r 0x03 & 0x04
303 Monitoring Siemens Modbus TCP maximum THD current L1 with time 1 % 1s 1s mean float + timestamp 12 3271 r 0x03 & 0x04
304 Monitoring Siemens Modbus TCP maximum THD current L2 with time 1 % 1s 1s mean float + timestamp 12 3277 r 0x03 & 0x04
305 Monitoring Siemens Modbus TCP maximum THD current L3 with time 1 % 1s 1s mean float + timestamp 12 3283 r 0x03 & 0x04
306 Monitoring Siemens Modbus TCP maximum distortion power L1 with time 1 A 1s 1s mean float + timestamp 12 3289 r 0x03 & 0x04
307 Monitoring Siemens Modbus TCP maximum distortion power L2 with time 1 A 1s 1s mean float + timestamp 12 3295 r 0x03 & 0x04
308 Monitoring Siemens Modbus TCP maximum distortion power L3 with time 1 A 1s 1s mean float + timestamp 12 3301 r 0x03 & 0x04
309 Monitoring Siemens Modbus TCP maximum line frequency with time 1 1s 1s mean float + timestamp 12 3307 r 0x03 & 0x04
310 Monitoring Siemens Modbus TCP maximum 3-phase average voltage L-N with time 1 V 1s 1s mean float + timestamp 12 3313 r 0x03 & 0x04
311 Monitoring Siemens Modbus TCP maximum 3-phase average voltage L-L with time 1 V 1s 1s mean float + timestamp 12 3319 r 0x03 & 0x04
312 Monitoring Siemens Modbus TCP maximum 3-phase average current with time 1 A 1s 1s mean float + timestamp 12 3325 r 0x03 & 0x04
313 Monitoring Siemens Modbus TCP maximum total apparent power with time 1 VA 1s 1s mean float + timestamp 12 3331 r 0x03 & 0x04
314 Monitoring Siemens Modbus TCP maximum total active power with time 1 W 1s 1s mean float + timestamp 12 3337 r 0x03 & 0x04
315 Monitoring Siemens Modbus TCP maximum total reactive power (Qn) with time 1 var 1s 1s mean float + timestamp 12 3343 r 0x03 & 0x04
316 Monitoring Siemens Modbus TCP maximum total power factor with time 1 1s 1s mean float + timestamp 12 3349 r 0x03 & 0x04
317 Monitoring Siemens Modbus TCP maximum neutral conductor current with time 1 A 1s 1s mean float + timestamp 12 3355 r 0x03 & 0x04
318 Monitoring Siemens Modbus TCP maximum total reactive power (Qtot) with time 1 var 1s 1s mean float + timestamp 12 3361 r 0x03 & 0x04
319 Monitoring Siemens Modbus TCP maximum total reactive power (Q1) with time 1 var 1s 1s mean float + timestamp 12 3367 r 0x03 & 0x04
320 Monitoring Siemens Modbus TCP maximum shared on mean voltage L1-N with time 1 V 1s 1s mean float + timestamp 12 3373 r 0x03 & 0x04
321 Monitoring Siemens Modbus TCP maximum shared on mean voltage L2-N with time 1 V 1s 1s mean float + timestamp 12 3379 r 0x03 & 0x04
322 Monitoring Siemens Modbus TCP maximum shared on mean voltage L3-N with time 1 V 1s 1s mean float + timestamp 12 3385 r 0x03 & 0x04
323 Monitoring Siemens Modbus TCP maximum shared on mean voltage L1-L2 with time 1 V 1s 1s mean float + timestamp 12 3391 r 0x03 & 0x04
324 Monitoring Siemens Modbus TCP maximum shared on mean voltage L2-L3 with time 1 V 1s 1s mean float + timestamp 12 3397 r 0x03 & 0x04
325 Monitoring Siemens Modbus TCP maximum shared on mean voltage L3-L1 with time 1 V 1s 1s mean float + timestamp 12 3403 r 0x03 & 0x04
326 Monitoring Siemens Modbus TCP maximum shared on mean current L1 with time 1 A 1s 1s mean float + timestamp 12 3409 r 0x03 & 0x04
327 Monitoring Siemens Modbus TCP maximum shared on mean current L2 with time 1 A 1s 1s mean float + timestamp 12 3415 r 0x03 & 0x04
328 Monitoring Siemens Modbus TCP maximum shared on mean current L3 with time 1 A 1s 1s mean float + timestamp 12 3421 r 0x03 & 0x04
329 Monitoring Siemens Modbus TCP maximum shared on mean apparent power L1 with time 1 VA 1s 1s mean float + timestamp 12 3427 r 0x03 & 0x04
330 Monitoring Siemens Modbus TCP maximum shared on mean apparent power L2 with time 1 VA 1s 1s mean float + timestamp 12 3433 r 0x03 & 0x04
331 Monitoring Siemens Modbus TCP maximum shared on mean apparent power L3 with time 1 VA 1s 1s mean float + timestamp 12 3439 r 0x03 & 0x04
332 Monitoring Siemens Modbus TCP maximum shared on mean active power L1 with time 1 W 1s 1s mean float + timestamp 12 3445 r 0x03 & 0x04
333 Monitoring Siemens Modbus TCP maximum shared on mean active power L2 with time 1 W 1s 1s mean float + timestamp 12 3451 r 0x03 & 0x04
334 Monitoring Siemens Modbus TCP maximum shared on mean active power L3 with time 1 W 1s 1s mean float + timestamp 12 3457 r 0x03 & 0x04
335 Monitoring Siemens Modbus TCP maximum shared on mean reactive power L1 (Qn) with time 1 var 1s 1s mean float + timestamp 12 3463 r 0x03 & 0x04
336 Monitoring Siemens Modbus TCP maximum shared on mean reactive power L2 (Qn) with time 1 var 1s 1s mean float + timestamp 12 3469 r 0x03 & 0x04
337 Monitoring Siemens Modbus TCP maximum shared on mean reactive power L3 (Qn) with time 1 var 1s 1s mean float + timestamp 12 3475 r 0x03 & 0x04
338 Monitoring Siemens Modbus TCP maximum shared on mean total reactive power L1 (Qtot) with time 1 var 1s 1s mean float + timestamp 12 3481 r 0x03 & 0x04
339 Monitoring Siemens Modbus TCP maximum shared on mean total reactive power L2 (Qtot) with time 1 var 1s 1s mean float + timestamp 12 3487 r 0x03 & 0x04
340 Monitoring Siemens Modbus TCP maximum shared on mean total reactive power L3 (Qtot) with time 1 var 1s 1s mean float + timestamp 12 3493 r 0x03 & 0x04
341 Monitoring Siemens Modbus TCP maximum shared on mean reactive power L1 (Q1) with time 1 var 1s 1s mean float + timestamp 12 3499 r 0x03 & 0x04
342 Monitoring Siemens Modbus TCP maximum shared on mean reactive power L2 (Q1) with time 1 var 1s 1s mean float + timestamp 12 3505 r 0x03 & 0x04
343 Monitoring Siemens Modbus TCP maximum shared on mean reactive power L3 (Q1) with time 1 var 1s 1s mean float + timestamp 12 3511 r 0x03 & 0x04
344 Monitoring Siemens Modbus TCP maximum shared on mean power factor L1 with time 1 1s 1s mean float + timestamp 12 3517 r 0x03 & 0x04
345 Monitoring Siemens Modbus TCP maximum shared on mean power factor L2 with time 1 1s 1s mean float + timestamp 12 3523 r 0x03 & 0x04
346 Monitoring Siemens Modbus TCP maximum shared on mean power factor L3 with time 1 1s 1s mean float + timestamp 12 3529 r 0x03 & 0x04
347 Monitoring Siemens Modbus TCP maximum shared on mean total apparent power with time 1 VA 1s 1s mean float + timestamp 12 3535 r 0x03 & 0x04
348 Monitoring Siemens Modbus TCP maximum shared on mean total active power with time 1 W 1s 1s mean float + timestamp 12 3541 r 0x03 & 0x04
349 Monitoring Siemens Modbus TCP maximum shared on mean total reactive power (Qn) with time 1 var 1s 1s mean float + timestamp 12 3547 r 0x03 & 0x04
350 Monitoring Siemens Modbus TCP maximum shared on mean total reactive power (Qtot) with time 1 var 1s 1s mean float + timestamp 12 3553 r 0x03 & 0x04
351 Monitoring Siemens Modbus TCP maximum shared on mean total reactive power (Q1) with time 1 var 1s 1s mean float + timestamp 12 3559 r 0x03 & 0x04
352 Monitoring Siemens Modbus TCP maximum shared on mean total power factor with time 1 1s 1s mean float + timestamp 12 3565 r 0x03 & 0x04
353 Monitoring Siemens Modbus TCP maximum shared on mean neutral conductor current with time 1 A 1s 1s mean float + timestamp 12 3571 r 0x03 & 0x04
354 Monitoring Siemens Modbus TCP minimum voltage L1-N with time 1 V 1s 1s mean float + timestamp 12 6001 r 0x03 & 0x04
355 Monitoring Siemens Modbus TCP minimum voltage L2-N with time 1 V 1s 1s mean float + timestamp 12 6007 r 0x03 & 0x04
356 Monitoring Siemens Modbus TCP minimum voltage L3-N with time 1 V 1s 1s mean float + timestamp 12 6013 r 0x03 & 0x04
357 Monitoring Siemens Modbus TCP minimum voltage L1-L2 with time 1 V 1s 1s mean float + timestamp 12 6019 r 0x03 & 0x04
358 Monitoring Siemens Modbus TCP minimum voltage L2-L3 with time 1 V 1s 1s mean float + timestamp 12 6025 r 0x03 & 0x04
359 Monitoring Siemens Modbus TCP minimum voltage L3-L1 with time 1 V 1s 1s mean float + timestamp 12 6031 r 0x03 & 0x04
360 Monitoring Siemens Modbus TCP minimum current L1 with time 1 A 1s 1s mean float + timestamp 12 6037 r 0x03 & 0x04
361 Monitoring Siemens Modbus TCP minimum current L2 with time 1 A 1s 1s mean float + timestamp 12 6043 r 0x03 & 0x04
362 Monitoring Siemens Modbus TCP minimum current L3 with time 1 A 1s 1s mean float + timestamp 12 6049 r 0x03 & 0x04
363 Monitoring Siemens Modbus TCP minimum apparent power L1 with time 1 VA 1s 1s mean float + timestamp 12 6055 r 0x03 & 0x04
364 Monitoring Siemens Modbus TCP minimum apparent power L2 with time 1 VA 1s 1s mean float + timestamp 12 6061 r 0x03 & 0x04
365 Monitoring Siemens Modbus TCP minimum apparent power L3 with time 1 VA 1s 1s mean float + timestamp 12 6067 r 0x03 & 0x04
366 Monitoring Siemens Modbus TCP minimum active power L1 with time 1 W 1s 1s mean float + timestamp 12 6073 r 0x03 & 0x04
367 Monitoring Siemens Modbus TCP minimum active power L2 with time 1 W 1s 1s mean float + timestamp 12 6079 r 0x03 & 0x04
368 Monitoring Siemens Modbus TCP minimum active power L3 with time 1 W 1s 1s mean float + timestamp 12 6085 r 0x03 & 0x04
369 Monitoring Siemens Modbus TCP minimum reactive power L1 (Qn) with time 1 var 1s 1s mean float + timestamp 12 6091 r 0x03 & 0x04
370 Monitoring Siemens Modbus TCP minimum reactive power L2 (Qn) with time 1 var 1s 1s mean float + timestamp 12 6097 r 0x03 & 0x04
371 Monitoring Siemens Modbus TCP minimum reactive power L3 (Qn) with time 1 var 1s 1s mean float + timestamp 12 6103 r 0x03 & 0x04
372 Monitoring Siemens Modbus TCP minimum total reactive power L1 (Qtot) with time 1 var 1s 1s mean float + timestamp 12 6109 r 0x03 & 0x04
373 Monitoring Siemens Modbus TCP minimum total reactive power L2 (Qtot) with time 1 var 1s 1s mean float + timestamp 12 6115 r 0x03 & 0x04
374 Monitoring Siemens Modbus TCP minimum total reactive power L3 (Qtot) with time 1 var 1s 1s mean float + timestamp 12 6121 r 0x03 & 0x04
375 Monitoring Siemens Modbus TCP minimum reactive power L1 (Q1) with time 1 var 1s 1s mean float + timestamp 12 6127 r 0x03 & 0x04
376 Monitoring Siemens Modbus TCP minimum reactive power L2 (Q1) with time 1 var 1s 1s mean float + timestamp 12 6133 r 0x03 & 0x04
377 Monitoring Siemens Modbus TCP minimum reactive power L3 (Q1) with time 1 var 1s 1s mean float + timestamp 12 6139 r 0x03 & 0x04
378 Monitoring Siemens Modbus TCP minimum power factor L1 with time 1 1s 1s mean float + timestamp 12 6145 r 0x03 & 0x04
379 Monitoring Siemens Modbus TCP minimum power factor L2 with time 1 1s 1s mean float + timestamp 12 6151 r 0x03 & 0x04
380 Monitoring Siemens Modbus TCP minimum power factor L3 with time 1 1s 1s mean float + timestamp 12 6157 r 0x03 & 0x04
381 Monitoring Siemens Modbus TCP minimum cos ? L1 with time 1 cos ?_L1 1s 1s mean float + timestamp 12 6163 r 0x03 & 0x04
382 Monitoring Siemens Modbus TCP minimum cos ? L2 with time 1 cos ?_L2 1s 1s mean float + timestamp 12 6169 r 0x03 & 0x04
383 Monitoring Siemens Modbus TCP minimum cos ? L3 with time 1 cos ?_L3 1s 1s mean float + timestamp 12 6175 r 0x03 & 0x04
384 Monitoring Siemens Modbus TCP minimum phase shift angle L1 with time 1 1s 1s mean float + timestamp 12 6181 r 0x03 & 0x04
385 Monitoring Siemens Modbus TCP minimum phase shift angle L2 with time 1 1s 1s mean float + timestamp 12 6187 r 0x03 & 0x04
386 Monitoring Siemens Modbus TCP minimum phase shift angle L3 with time 1 1s 1s mean float + timestamp 12 6193 r 0x03 & 0x04
387 Monitoring Siemens Modbus TCP minimum phase angle L1-L2 with time 1 1s 1s mean float + timestamp 12 6199 r 0x03 & 0x04
388 Monitoring Siemens Modbus TCP minimum phase angle L2-L3 with time 1 1s 1s mean float + timestamp 12 6205 r 0x03 & 0x04
389 Monitoring Siemens Modbus TCP minimum phase angle L1-L3 with time 1 1s 1s mean float + timestamp 12 6211 r 0x03 & 0x04
390 Monitoring Siemens Modbus TCP minimum line frequency with time 1 1s 1s mean float + timestamp 12 6217 r 0x03 & 0x04
391 Monitoring Siemens Modbus TCP minimum 3-phase average voltage L-N with time 1 V 1s 1s mean float + timestamp 12 6223 r 0x03 & 0x04
392 Monitoring Siemens Modbus TCP minimum 3-phase average voltage L-L with time 1 V 1s 1s mean float + timestamp 12 6229 r 0x03 & 0x04
393 Monitoring Siemens Modbus TCP minimum 3-phase average current with time 1 A 1s 1s mean float + timestamp 12 6235 r 0x03 & 0x04
394 Monitoring Siemens Modbus TCP minimum total apparent power with time 1 VA 1s 1s mean float + timestamp 12 6241 r 0x03 & 0x04
395 Monitoring Siemens Modbus TCP minimum total active power with time 1 W 1s 1s mean float + timestamp 12 6247 r 0x03 & 0x04
396 Monitoring Siemens Modbus TCP minimum total reactive power (Qn) with time 1 var 1s 1s mean float + timestamp 12 6253 r 0x03 & 0x04
397 Monitoring Siemens Modbus TCP minimum total power factor (Qn) with time 1 1s 1s mean float + timestamp 12 6259 r 0x03 & 0x04
398 Monitoring Siemens Modbus TCP minimum neutral conductor current with time 1 A 1s 1s mean float + timestamp 12 6265 r 0x03 & 0x04
399 Monitoring Siemens Modbus TCP minimum total reactive power (Qtot) with time 1 var 1s 1s mean float + timestamp 12 6271 r 0x03 & 0x04
400 Monitoring Siemens Modbus TCP minimum total reactive power (Q1) with time 1 var 1s 1s mean float + timestamp 12 6277 r 0x03 & 0x04
401 Monitoring Siemens Modbus TCP minimum shared on mean voltage L1-N with time 1 V 1s 1s mean float + timestamp 12 6283 r 0x03 & 0x04
402 Monitoring Siemens Modbus TCP minimum shared on mean voltage L2-N with time 1 V 1s 1s mean float + timestamp 12 6289 r 0x03 & 0x04
403 Monitoring Siemens Modbus TCP minimum shared on mean voltage L3-N with time 1 V 1s 1s mean float + timestamp 12 6295 r 0x03 & 0x04
404 Monitoring Siemens Modbus TCP minimum shared on mean voltage L1-L2 with time 1 V 1s 1s mean float + timestamp 12 6301 r 0x03 & 0x04
405 Monitoring Siemens Modbus TCP minimum shared on mean voltage L2-L3 with time 1 V 1s 1s mean float + timestamp 12 6307 r 0x03 & 0x04
406 Monitoring Siemens Modbus TCP minimum shared on mean voltage L3-L1 with time 1 V 1s 1s mean float + timestamp 12 6313 r 0x03 & 0x04
407 Monitoring Siemens Modbus TCP minimum shared on mean current L1 with time 1 A 1s 1s mean float + timestamp 12 6319 r 0x03 & 0x04
408 Monitoring Siemens Modbus TCP minimum shared on mean current L2 with time 1 A 1s 1s mean float + timestamp 12 6325 r 0x03 & 0x04
409 Monitoring Siemens Modbus TCP minimum shared on mean current L3 with time 1 A 1s 1s mean float + timestamp 12 6331 r 0x03 & 0x04
410 Monitoring Siemens Modbus TCP minimum shared on mean apparent power L1 with time 1 VA 1s 1s mean float + timestamp 12 6337 r 0x03 & 0x04
411 Monitoring Siemens Modbus TCP minimum shared on mean apparent power L2 with time 1 VA 1s 1s mean float + timestamp 12 6343 r 0x03 & 0x04
412 Monitoring Siemens Modbus TCP minimum shared on mean apparent power L3 with time 1 VA 1s 1s mean float + timestamp 12 6349 r 0x03 & 0x04
413 Monitoring Siemens Modbus TCP minimum shared on mean active power L1 with time 1 W 1s 1s mean float + timestamp 12 6355 r 0x03 & 0x04
414 Monitoring Siemens Modbus TCP minimum shared on mean active power L2 with time 1 W 1s 1s mean float + timestamp 12 6361 r 0x03 & 0x04
415 Monitoring Siemens Modbus TCP minimum shared on mean active power L3 with time 1 W 1s 1s mean float + timestamp 12 6367 r 0x03 & 0x04
416 Monitoring Siemens Modbus TCP minimum shared on mean reactive power L1 (Qn) with time 1 var 1s 1s mean float + timestamp 12 6373 r 0x03 & 0x04
417 Monitoring Siemens Modbus TCP minimum shared on mean reactive power L2 (Qn) with time 1 var 1s 1s mean float + timestamp 12 6379 r 0x03 & 0x04
418 Monitoring Siemens Modbus TCP minimum shared on mean reactive power L3 (Qn) with time 1 var 1s 1s mean float + timestamp 12 6385 r 0x03 & 0x04
419 Monitoring Siemens Modbus TCP minimum shared on mean total reactive power L1 (Qtot) with time 1 var 1s 1s mean float + timestamp 12 6391 r 0x03 & 0x04
420 Monitoring Siemens Modbus TCP minimum shared on mean total reactive power L2 (Qtot) with time 1 var 1s 1s mean float + timestamp 12 6397 r 0x03 & 0x04
421 Monitoring Siemens Modbus TCP minimum shared on mean total reactive power L3 (Qtot) with time 1 var 1s 1s mean float + timestamp 12 6403 r 0x03 & 0x04
422 Monitoring Siemens Modbus TCP minimum shared on mean reactive power L1 (Q1) with time 1 var 1s 1s mean float + timestamp 12 6409 r 0x03 & 0x04
423 Monitoring Siemens Modbus TCP minimum shared on mean reactive power L2 (Q1) with time 1 var 1s 1s mean float + timestamp 12 6415 r 0x03 & 0x04
424 Monitoring Siemens Modbus TCP minimum shared on mean reactive power L3 (Q1) with time 1 var 1s 1s mean float + timestamp 12 6421 r 0x03 & 0x04
425 Monitoring Siemens Modbus TCP minimum shared on mean power factor L1 with time 1 1s 1s mean float + timestamp 12 6427 r 0x03 & 0x04
426 Monitoring Siemens Modbus TCP minimum shared on mean power factor L2 with time 1 1s 1s mean float + timestamp 12 6433 r 0x03 & 0x04
427 Monitoring Siemens Modbus TCP minimum shared on mean power factor L3 with time 1 1s 1s mean float + timestamp 12 6439 r 0x03 & 0x04
428 Monitoring Siemens Modbus TCP minimum shared on mean total apparent power with time 1 VA 1s 1s mean float + timestamp 12 6445 r 0x03 & 0x04
429 Monitoring Siemens Modbus TCP minimum shared on mean total active power with time 1 W 1s 1s mean float + timestamp 12 6451 r 0x03 & 0x04
430 Monitoring Siemens Modbus TCP minimum shared on mean total reactive power (Qn) with time 1 var 1s 1s mean float + timestamp 12 6457 r 0x03 & 0x04
431 Monitoring Siemens Modbus TCP minimum shared on mean total reactive power (Qtot) with time 1 var 1s 1s mean float + timestamp 12 6463 r 0x03 & 0x04
432 Monitoring Siemens Modbus TCP minimum shared on mean total reactive power (Q1) with time 1 var 1s 1s mean float + timestamp 12 6469 r 0x03 & 0x04
433 Monitoring Siemens Modbus TCP minimum shared on mean total power factor with time 1 1s 1s mean float + timestamp 12 6475 r 0x03 & 0x04
434 Monitoring Siemens Modbus TCP minimum shared on mean neutral conductor current with time 1 A 1s 1s mean float + timestamp 12 6481 r 0x03 & 0x04
435 Monitoring Siemens Modbus TCP fundamental oscillation voltage L1-N 1 V 1s 1s mean float 4 9001 r 0x03 & 0x04
436 Monitoring Siemens Modbus TCP fundamental oscillation voltage L2-N 1 V 1s 1s mean float 4 9003 r 0x03 & 0x04
437 Monitoring Siemens Modbus TCP fundamental oscillation voltage L3-N 1 V 1s 1s mean float 4 9005 r 0x03 & 0x04
438 Monitoring Siemens Modbus TCP 3. harmonic voltage L1-N 1 % 1s 1s mean float 4 9007 r 0x03 & 0x04
439 Monitoring Siemens Modbus TCP 3. harmonic voltage L2-N 1 % 1s 1s mean float 4 9009 r 0x03 & 0x04
440 Monitoring Siemens Modbus TCP 3. harmonic voltage L3-N 1 % 1s 1s mean float 4 9011 r 0x03 & 0x04
441 Monitoring Siemens Modbus TCP 5. harmonic voltage L1-N 1 % 1s 1s mean float 4 9013 r 0x03 & 0x04
442 Monitoring Siemens Modbus TCP 5. harmonic voltage L2-N 1 % 1s 1s mean float 4 9015 r 0x03 & 0x04
443 Monitoring Siemens Modbus TCP 5. harmonic voltage L3-N 1 % 1s 1s mean float 4 9017 r 0x03 & 0x04
444 Monitoring Siemens Modbus TCP 7. harmonic voltage L1-N 1 % 1s 1s mean float 4 9019 r 0x03 & 0x04
445 Monitoring Siemens Modbus TCP 7. harmonic voltage L2-N 1 % 1s 1s mean float 4 9021 r 0x03 & 0x04
446 Monitoring Siemens Modbus TCP 7. harmonic voltage L3-N 1 % 1s 1s mean float 4 9023 r 0x03 & 0x04
447 Monitoring Siemens Modbus TCP 9. harmonic voltage L1-N 1 % 1s 1s mean float 4 9025 r 0x03 & 0x04
448 Monitoring Siemens Modbus TCP 9. harmonic voltage L2-N 1 % 1s 1s mean float 4 9027 r 0x03 & 0x04
449 Monitoring Siemens Modbus TCP 9. harmonic voltage L3-N 1 % 1s 1s mean float 4 9029 r 0x03 & 0x04
450 Monitoring Siemens Modbus TCP 11. harmonic voltage L1-N 1 % 1s 1s mean float 4 9031 r 0x03 & 0x04
451 Monitoring Siemens Modbus TCP 11. harmonic voltage L2-N 1 % 1s 1s mean float 4 9033 r 0x03 & 0x04
452 Monitoring Siemens Modbus TCP 11. harmonic voltage L3-N 1 % 1s 1s mean float 4 9035 r 0x03 & 0x04
453 Monitoring Siemens Modbus TCP 13. harmonic voltage L1-N 1 % 1s 1s mean float 4 9037 r 0x03 & 0x04
454 Monitoring Siemens Modbus TCP 13. harmonic voltage L2-N 1 % 1s 1s mean float 4 9039 r 0x03 & 0x04
455 Monitoring Siemens Modbus TCP 13. harmonic voltage L3-N 1 % 1s 1s mean float 4 9041 r 0x03 & 0x04
456 Monitoring Siemens Modbus TCP 15. harmonic voltage L1-N 1 % 1s 1s mean float 4 9043 r 0x03 & 0x04
457 Monitoring Siemens Modbus TCP 15. harmonic voltage L2-N 1 % 1s 1s mean float 4 9045 r 0x03 & 0x04
458 Monitoring Siemens Modbus TCP 15. harmonic voltage L3-N 1 % 1s 1s mean float 4 9047 r 0x03 & 0x04
459 Monitoring Siemens Modbus TCP 17. harmonic voltage L1-N 1 % 1s 1s mean float 4 9049 r 0x03 & 0x04
460 Monitoring Siemens Modbus TCP 17. harmonic voltage L2-N 1 % 1s 1s mean float 4 9051 r 0x03 & 0x04
461 Monitoring Siemens Modbus TCP 17. harmonic voltage L3-N 1 % 1s 1s mean float 4 9053 r 0x03 & 0x04
462 Monitoring Siemens Modbus TCP 19. harmonic voltage L1-N 1 % 1s 1s mean float 4 9055 r 0x03 & 0x04
463 Monitoring Siemens Modbus TCP 19. harmonic voltage L2-N 1 % 1s 1s mean float 4 9057 r 0x03 & 0x04
464 Monitoring Siemens Modbus TCP 19. harmonic voltage L3-N 1 % 1s 1s mean float 4 9059 r 0x03 & 0x04
465 Monitoring Siemens Modbus TCP 21. harmonic voltage L1-N 1 % 1s 1s mean float 4 9061 r 0x03 & 0x04
466 Monitoring Siemens Modbus TCP 21. harmonic voltage L2-N 1 % 1s 1s mean float 4 9063 r 0x03 & 0x04
467 Monitoring Siemens Modbus TCP 21. harmonic voltage L3-N 1 % 1s 1s mean float 4 9065 r 0x03 & 0x04
468 Monitoring Siemens Modbus TCP 23. harmonic voltage L1-N 1 % 1s 1s mean float 4 9067 r 0x03 & 0x04
469 Monitoring Siemens Modbus TCP 23. harmonic voltage L2-N 1 % 1s 1s mean float 4 9069 r 0x03 & 0x04
470 Monitoring Siemens Modbus TCP 23. harmonic voltage L3-N 1 % 1s 1s mean float 4 9071 r 0x03 & 0x04
471 Monitoring Siemens Modbus TCP 25. harmonic voltage L1-N 1 % 1s 1s mean float 4 9073 r 0x03 & 0x04
472 Monitoring Siemens Modbus TCP 25. harmonic voltage L2-N 1 % 1s 1s mean float 4 9075 r 0x03 & 0x04
473 Monitoring Siemens Modbus TCP 25. harmonic voltage L3-N 1 % 1s 1s mean float 4 9077 r 0x03 & 0x04
474 Monitoring Siemens Modbus TCP 27. harmonic voltage L1-N 1 % 1s 1s mean float 4 9079 r 0x03 & 0x04
475 Monitoring Siemens Modbus TCP 27. harmonic voltage L2-N 1 % 1s 1s mean float 4 9081 r 0x03 & 0x04
476 Monitoring Siemens Modbus TCP 27. harmonic voltage L3-N 1 % 1s 1s mean float 4 9083 r 0x03 & 0x04
477 Monitoring Siemens Modbus TCP 29. harmonic voltage L1-N 1 % 1s 1s mean float 4 9085 r 0x03 & 0x04
478 Monitoring Siemens Modbus TCP 29. harmonic voltage L2-N 1 % 1s 1s mean float 4 9087 r 0x03 & 0x04
479 Monitoring Siemens Modbus TCP 29. harmonic voltage L3-N 1 % 1s 1s mean float 4 9089 r 0x03 & 0x04
480 Monitoring Siemens Modbus TCP 31. harmonic voltage L1-N 1 % 1s 1s mean float 4 9091 r 0x03 & 0x04
481 Monitoring Siemens Modbus TCP 31. harmonic voltage L2-N 1 % 1s 1s mean float 4 9093 r 0x03 & 0x04
482 Monitoring Siemens Modbus TCP 31. harmonic voltage L3-N 1 % 1s 1s mean float 4 9095 r 0x03 & 0x04
483 Monitoring Siemens Modbus TCP fundamental oscillation current L1 1 A 1s 1s mean float 4 11001 r 0x03 & 0x04
484 Monitoring Siemens Modbus TCP fundamental oscillation current L2 1 A 1s 1s mean float 4 11003 r 0x03 & 0x04
485 Monitoring Siemens Modbus TCP fundamental oscillation current L3 1 A 1s 1s mean float 4 11005 r 0x03 & 0x04
486 Monitoring Siemens Modbus TCP 3. harmonic current L1 1 A 1s 1s mean float 4 11007 r 0x03 & 0x04
487 Monitoring Siemens Modbus TCP 3. harmonic current L2 1 A 1s 1s mean float 4 11009 r 0x03 & 0x04
488 Monitoring Siemens Modbus TCP 3. harmonic current L3 1 A 1s 1s mean float 4 11011 r 0x03 & 0x04
489 Monitoring Siemens Modbus TCP 5. harmonic current L1 1 A 1s 1s mean float 4 11013 r 0x03 & 0x04
490 Monitoring Siemens Modbus TCP 5. harmonic current L2 1 A 1s 1s mean float 4 11015 r 0x03 & 0x04
491 Monitoring Siemens Modbus TCP 5. harmonic current L3 1 A 1s 1s mean float 4 11017 r 0x03 & 0x04
492 Monitoring Siemens Modbus TCP 7. harmonic current L1 1 A 1s 1s mean float 4 11019 r 0x03 & 0x04
493 Monitoring Siemens Modbus TCP 7. harmonic current L2 1 A 1s 1s mean float 4 11021 r 0x03 & 0x04
494 Monitoring Siemens Modbus TCP 7. harmonic current L3 1 A 1s 1s mean float 4 11023 r 0x03 & 0x04
495 Monitoring Siemens Modbus TCP 9. harmonic current L1 1 A 1s 1s mean float 4 11025 r 0x03 & 0x04
496 Monitoring Siemens Modbus TCP 9. harmonic current L2 1 A 1s 1s mean float 4 11027 r 0x03 & 0x04
497 Monitoring Siemens Modbus TCP 9. harmonic current L3 1 A 1s 1s mean float 4 11029 r 0x03 & 0x04
498 Monitoring Siemens Modbus TCP 11. harmonic current L1 1 A 1s 1s mean float 4 11031 r 0x03 & 0x04
499 Monitoring Siemens Modbus TCP 11. harmonic current L2 1 A 1s 1s mean float 4 11033 r 0x03 & 0x04
500 Monitoring Siemens Modbus TCP 11. harmonic current L3 1 A 1s 1s mean float 4 11035 r 0x03 & 0x04
501 Monitoring Siemens Modbus TCP 13. harmonic current L1 1 A 1s 1s mean float 4 11037 r 0x03 & 0x04
502 Monitoring Siemens Modbus TCP 13. harmonic current L2 1 A 1s 1s mean float 4 11039 r 0x03 & 0x04
503 Monitoring Siemens Modbus TCP 13. harmonic current L3 1 A 1s 1s mean float 4 11041 r 0x03 & 0x04
504 Monitoring Siemens Modbus TCP 15. harmonic current L1 1 A 1s 1s mean float 4 11043 r 0x03 & 0x04
505 Monitoring Siemens Modbus TCP 15. harmonic current L2 1 A 1s 1s mean float 4 11045 r 0x03 & 0x04
506 Monitoring Siemens Modbus TCP 15. harmonic current L3 1 A 1s 1s mean float 4 11047 r 0x03 & 0x04
507 Monitoring Siemens Modbus TCP 17. harmonic current L1 1 A 1s 1s mean float 4 11049 r 0x03 & 0x04
508 Monitoring Siemens Modbus TCP 17. harmonic current L2 1 A 1s 1s mean float 4 11051 r 0x03 & 0x04
509 Monitoring Siemens Modbus TCP 17. harmonic current L3 1 A 1s 1s mean float 4 11053 r 0x03 & 0x04
510 Monitoring Siemens Modbus TCP 19. harmonic current L1 1 A 1s 1s mean float 4 11055 r 0x03 & 0x04
511 Monitoring Siemens Modbus TCP 19. harmonic current L2 1 A 1s 1s mean float 4 11057 r 0x03 & 0x04
512 Monitoring Siemens Modbus TCP 19. harmonic current L3 1 A 1s 1s mean float 4 11059 r 0x03 & 0x04
513 Monitoring Siemens Modbus TCP 21. harmonic current L1 1 A 1s 1s mean float 4 11061 r 0x03 & 0x04
514 Monitoring Siemens Modbus TCP 21. harmonic current L2 1 A 1s 1s mean float 4 11063 r 0x03 & 0x04
515 Monitoring Siemens Modbus TCP 21. harmonic current L3 1 A 1s 1s mean float 4 11065 r 0x03 & 0x04
516 Monitoring Siemens Modbus TCP 23. harmonic current L1 1 A 1s 1s mean float 4 11067 r 0x03 & 0x04
517 Monitoring Siemens Modbus TCP 23. harmonic current L2 1 A 1s 1s mean float 4 11069 r 0x03 & 0x04
518 Monitoring Siemens Modbus TCP 23. harmonic current L3 1 A 1s 1s mean float 4 11071 r 0x03 & 0x04
519 Monitoring Siemens Modbus TCP 25. harmonic current L1 1 A 1s 1s mean float 4 11073 r 0x03 & 0x04
520 Monitoring Siemens Modbus TCP 25. harmonic current L2 1 A 1s 1s mean float 4 11075 r 0x03 & 0x04
521 Monitoring Siemens Modbus TCP 25. harmonic current L3 1 A 1s 1s mean float 4 11077 r 0x03 & 0x04
522 Monitoring Siemens Modbus TCP 27. harmonic current L1 1 A 1s 1s mean float 4 11079 r 0x03 & 0x04
523 Monitoring Siemens Modbus TCP 27. harmonic current L2 1 A 1s 1s mean float 4 11081 r 0x03 & 0x04
524 Monitoring Siemens Modbus TCP 27. harmonic current L3 1 A 1s 1s mean float 4 11083 r 0x03 & 0x04
525 Monitoring Siemens Modbus TCP 29. harmonic current L1 1 A 1s 1s mean float 4 11085 r 0x03 & 0x04
526 Monitoring Siemens Modbus TCP 29. harmonic current L2 1 A 1s 1s mean float 4 11087 r 0x03 & 0x04
527 Monitoring Siemens Modbus TCP 29. harmonic current L3 1 A 1s 1s mean float 4 11089 r 0x03 & 0x04
528 Monitoring Siemens Modbus TCP 31. harmonic current L1 1 A 1s 1s mean float 4 11091 r 0x03 & 0x04
529 Monitoring Siemens Modbus TCP 31. harmonic current L2 1 A 1s 1s mean float 4 11093 r 0x03 & 0x04
530 Monitoring Siemens Modbus TCP 31. harmonic current L3 1 A 1s 1s mean float 4 11095 r 0x03 & 0x04
531 Monitoring Siemens Modbus TCP fundamental oscillation voltage L1-L2 1 V 1s 1s mean float 4 22001 r 0x03 & 0x04
532 Monitoring Siemens Modbus TCP fundamental oscillation voltage L2-L3 1 V 1s 1s mean float 4 22003 r 0x03 & 0x04
533 Monitoring Siemens Modbus TCP fundamental oscillation voltage L3-L1 1 V 1s 1s mean float 4 22005 r 0x03 & 0x04
534 Monitoring Siemens Modbus TCP 3. harmonic voltage L1-L2 1 % 1s 1s mean float 4 22007 r 0x03 & 0x04
535 Monitoring Siemens Modbus TCP 3. harmonic voltage L2-L3 1 % 1s 1s mean float 4 22009 r 0x03 & 0x04
536 Monitoring Siemens Modbus TCP 3. harmonic voltage L3-L1 1 % 1s 1s mean float 4 22011 r 0x03 & 0x04
537 Monitoring Siemens Modbus TCP 5. harmonic voltage L1-L2 1 % 1s 1s mean float 4 22013 r 0x03 & 0x04
538 Monitoring Siemens Modbus TCP 5. harmonic voltage L2-L3 1 % 1s 1s mean float 4 22015 r 0x03 & 0x04
539 Monitoring Siemens Modbus TCP 5. harmonic voltage L3-L1 1 % 1s 1s mean float 4 22017 r 0x03 & 0x04
540 Monitoring Siemens Modbus TCP 7. harmonic voltage L1-L2 1 % 1s 1s mean float 4 22019 r 0x03 & 0x04
541 Monitoring Siemens Modbus TCP 7. harmonic voltage L2-L3 1 % 1s 1s mean float 4 22021 r 0x03 & 0x04
542 Monitoring Siemens Modbus TCP 7. harmonic voltage L3-L1 1 % 1s 1s mean float 4 22023 r 0x03 & 0x04
543 Monitoring Siemens Modbus TCP 9. harmonic voltage L1-L2 1 % 1s 1s mean float 4 22025 r 0x03 & 0x04
544 Monitoring Siemens Modbus TCP 9. harmonic voltage L2-L3 1 % 1s 1s mean float 4 22027 r 0x03 & 0x04
545 Monitoring Siemens Modbus TCP 9. harmonic voltage L3-L1 1 % 1s 1s mean float 4 22029 r 0x03 & 0x04
546 Monitoring Siemens Modbus TCP 11. harmonic voltage L1-L2 1 % 1s 1s mean float 4 22031 r 0x03 & 0x04
547 Monitoring Siemens Modbus TCP 11. harmonic voltage L2-L3 1 % 1s 1s mean float 4 22033 r 0x03 & 0x04
548 Monitoring Siemens Modbus TCP 11. harmonic voltage L3-L1 1 % 1s 1s mean float 4 22035 r 0x03 & 0x04
549 Monitoring Siemens Modbus TCP 13. harmonic voltage L1-L2 1 % 1s 1s mean float 4 22037 r 0x03 & 0x04
550 Monitoring Siemens Modbus TCP 13. harmonic voltage L2-L3 1 % 1s 1s mean float 4 22039 r 0x03 & 0x04
551 Monitoring Siemens Modbus TCP 13. harmonic voltage L3-L1 1 % 1s 1s mean float 4 22041 r 0x03 & 0x04
552 Monitoring Siemens Modbus TCP 15. harmonic voltage L1-L2 1 % 1s 1s mean float 4 22043 r 0x03 & 0x04
553 Monitoring Siemens Modbus TCP 15. harmonic voltage L2-L3 1 % 1s 1s mean float 4 22045 r 0x03 & 0x04
554 Monitoring Siemens Modbus TCP 15. harmonic voltage L3-L1 1 % 1s 1s mean float 4 22047 r 0x03 & 0x04
555 Monitoring Siemens Modbus TCP 17. harmonic voltage L1-L2 1 % 1s 1s mean float 4 22049 r 0x03 & 0x04
556 Monitoring Siemens Modbus TCP 17. harmonic voltage L2-L3 1 % 1s 1s mean float 4 22051 r 0x03 & 0x04
557 Monitoring Siemens Modbus TCP 17. harmonic voltage L3-L1 1 % 1s 1s mean float 4 22053 r 0x03 & 0x04
558 Monitoring Siemens Modbus TCP 19. harmonic voltage L1-L2 1 % 1s 1s mean float 4 22055 r 0x03 & 0x04
559 Monitoring Siemens Modbus TCP 19. harmonic voltage L2-L3 1 % 1s 1s mean float 4 22057 r 0x03 & 0x04
560 Monitoring Siemens Modbus TCP 19. harmonic voltage L3-L1 1 % 1s 1s mean float 4 22059 r 0x03 & 0x04
561 Monitoring Siemens Modbus TCP 21. harmonic voltage L1-L2 1 % 1s 1s mean float 4 22061 r 0x03 & 0x04
562 Monitoring Siemens Modbus TCP 21. harmonic voltage L2-L3 1 % 1s 1s mean float 4 22063 r 0x03 & 0x04
563 Monitoring Siemens Modbus TCP 21. harmonic voltage L3-L1 1 % 1s 1s mean float 4 22065 r 0x03 & 0x04
564 Monitoring Siemens Modbus TCP 23. harmonic voltage L1-L2 1 % 1s 1s mean float 4 22067 r 0x03 & 0x04
565 Monitoring Siemens Modbus TCP 23. harmonic voltage L2-L3 1 % 1s 1s mean float 4 22069 r 0x03 & 0x04
566 Monitoring Siemens Modbus TCP 23. harmonic voltage L3-L1 1 % 1s 1s mean float 4 22071 r 0x03 & 0x04
567 Monitoring Siemens Modbus TCP 25. harmonic voltage L1-L2 1 % 1s 1s mean float 4 22073 r 0x03 & 0x04
568 Monitoring Siemens Modbus TCP 25. harmonic voltage L2-L3 1 % 1s 1s mean float 4 22075 r 0x03 & 0x04
569 Monitoring Siemens Modbus TCP 25. harmonic voltage L3-L1 1 % 1s 1s mean float 4 22077 r 0x03 & 0x04
570 Monitoring Siemens Modbus TCP 27. harmonic voltage L1-L2 1 % 1s 1s mean float 4 22079 r 0x03 & 0x04
571 Monitoring Siemens Modbus TCP 27. harmonic voltage L2-L3 1 % 1s 1s mean float 4 22081 r 0x03 & 0x04
572 Monitoring Siemens Modbus TCP 27. harmonic voltage L3-L1 1 % 1s 1s mean float 4 22083 r 0x03 & 0x04
573 Monitoring Siemens Modbus TCP 29. harmonic voltage L1-L2 1 % 1s 1s mean float 4 22085 r 0x03 & 0x04
574 Monitoring Siemens Modbus TCP 29. harmonic voltage L2-L3 1 % 1s 1s mean float 4 22087 r 0x03 & 0x04
575 Monitoring Siemens Modbus TCP 29. harmonic voltage L3-L1 1 % 1s 1s mean float 4 22089 r 0x03 & 0x04
576 Monitoring Siemens Modbus TCP 31. harmonic voltage L1-L2 1 % 1s 1s mean float 4 22091 r 0x03 & 0x04
577 Monitoring Siemens Modbus TCP 31. harmonic voltage L2-L3 1 % 1s 1s mean float 4 22093 r 0x03 & 0x04
578 Monitoring Siemens Modbus TCP 31. harmonic voltage L3-L1 1 % 1s 1s mean float 4 22095 r 0x03 & 0x04
579 Monitoring Siemens Modbus TCP maximum 3. harmonic voltage L1-N with time 1 % 1s 1s mean float + timestamp 6 12999 r 0x03 & 0x04
580 Monitoring Siemens Modbus TCP maximum 3. harmonic voltage L2-N with time 1 % 1s 1s mean float + timestamp 6 13005 r 0x03 & 0x04
581 Monitoring Siemens Modbus TCP maximum 3. harmonic voltage L3-N with time 1 % 1s 1s mean float + timestamp 6 13011 r 0x03 & 0x04
582 Monitoring Siemens Modbus TCP maximum 5. harmonic voltage L1-N with time 1 % 1s 1s mean float + timestamp 6 13017 r 0x03 & 0x04
583 Monitoring Siemens Modbus TCP maximum 5. harmonic voltage L2-N with time 1 % 1s 1s mean float + timestamp 6 13023 r 0x03 & 0x04
584 Monitoring Siemens Modbus TCP maximum 5. harmonic voltage L3-N with time 1 % 1s 1s mean float + timestamp 6 13029 r 0x03 & 0x04
585 Monitoring Siemens Modbus TCP maximum 7. harmonic voltage L1-N with time 1 % 1s 1s mean float + timestamp 6 13035 r 0x03 & 0x04
586 Monitoring Siemens Modbus TCP maximum 7. harmonic voltage L2-N with time 1 % 1s 1s mean float + timestamp 6 13041 r 0x03 & 0x04
587 Monitoring Siemens Modbus TCP maximum 7. harmonic voltage L3-N with time 1 % 1s 1s mean float + timestamp 6 13047 r 0x03 & 0x04
588 Monitoring Siemens Modbus TCP maximum 9. harmonic voltage L1-N with time 1 % 1s 1s mean float + timestamp 6 13053 r 0x03 & 0x04
589 Monitoring Siemens Modbus TCP maximum 9. harmonic voltage L2-N with time 1 % 1s 1s mean float + timestamp 6 13059 r 0x03 & 0x04
590 Monitoring Siemens Modbus TCP maximum 9. harmonic voltage L3-N with time 1 % 1s 1s mean float + timestamp 6 13065 r 0x03 & 0x04
591 Monitoring Siemens Modbus TCP maximum 11. harmonic voltage L1-N with time 1 % 1s 1s mean float + timestamp 6 13071 r 0x03 & 0x04
592 Monitoring Siemens Modbus TCP maximum 11. harmonic voltage L2-N with time 1 % 1s 1s mean float + timestamp 6 13077 r 0x03 & 0x04
593 Monitoring Siemens Modbus TCP maximum 11. harmonic voltage L3-N with time 1 % 1s 1s mean float + timestamp 6 13083 r 0x03 & 0x04
594 Monitoring Siemens Modbus TCP maximum 13. harmonic voltage L1-N with time 1 % 1s 1s mean float + timestamp 6 13089 r 0x03 & 0x04
595 Monitoring Siemens Modbus TCP maximum 13. harmonic voltage L2-N with time 1 % 1s 1s mean float + timestamp 6 13095 r 0x03 & 0x04
596 Monitoring Siemens Modbus TCP maximum 13. harmonic voltage L3-N with time 1 % 1s 1s mean float + timestamp 6 13101 r 0x03 & 0x04
597 Monitoring Siemens Modbus TCP maximum 15. harmonic voltage L1-N with time 1 % 1s 1s mean float + timestamp 6 13107 r 0x03 & 0x04
598 Monitoring Siemens Modbus TCP maximum 15. harmonic voltage L2-N with time 1 % 1s 1s mean float + timestamp 6 13113 r 0x03 & 0x04
599 Monitoring Siemens Modbus TCP maximum 15. harmonic voltage L3-N with time 1 % 1s 1s mean float + timestamp 6 13119 r 0x03 & 0x04
600 Monitoring Siemens Modbus TCP maximum 17. harmonic voltage L1-N with time 1 % 1s 1s mean float + timestamp 6 13125 r 0x03 & 0x04
601 Monitoring Siemens Modbus TCP maximum 17. harmonic voltage L2-N with time 1 % 1s 1s mean float + timestamp 6 13131 r 0x03 & 0x04
602 Monitoring Siemens Modbus TCP maximum 17. harmonic voltage L3-N with time 1 % 1s 1s mean float + timestamp 6 13137 r 0x03 & 0x04
603 Monitoring Siemens Modbus TCP maximum 19. harmonic voltage L1-N with time 1 % 1s 1s mean float + timestamp 6 13143 r 0x03 & 0x04
604 Monitoring Siemens Modbus TCP maximum 19. harmonic voltage L2-N with time 1 % 1s 1s mean float + timestamp 6 13149 r 0x03 & 0x04
605 Monitoring Siemens Modbus TCP maximum 19. harmonic voltage L3-N with time 1 % 1s 1s mean float + timestamp 6 13155 r 0x03 & 0x04
606 Monitoring Siemens Modbus TCP maximum 21. harmonic voltage L1-N with time 1 % 1s 1s mean float + timestamp 6 13161 r 0x03 & 0x04
607 Monitoring Siemens Modbus TCP maximum 21. harmonic voltage L2-N with time 1 % 1s 1s mean float + timestamp 6 13167 r 0x03 & 0x04
608 Monitoring Siemens Modbus TCP maximum 21. harmonic voltage L3-N with time 1 % 1s 1s mean float + timestamp 6 13173 r 0x03 & 0x04
609 Monitoring Siemens Modbus TCP maximum 23. harmonic voltage L1-N with time 1 % 1s 1s mean float + timestamp 6 13179 r 0x03 & 0x04
610 Monitoring Siemens Modbus TCP maximum 23. harmonic voltage L2-N with time 1 % 1s 1s mean float + timestamp 6 13185 r 0x03 & 0x04
611 Monitoring Siemens Modbus TCP maximum 23. harmonic voltage L3-N with time 1 % 1s 1s mean float + timestamp 6 13191 r 0x03 & 0x04
612 Monitoring Siemens Modbus TCP maximum 25. harmonic voltage L1-N with time 1 % 1s 1s mean float + timestamp 6 13197 r 0x03 & 0x04
613 Monitoring Siemens Modbus TCP maximum 25. harmonic voltage L2-N with time 1 % 1s 1s mean float + timestamp 6 13203 r 0x03 & 0x04
614 Monitoring Siemens Modbus TCP maximum 25. harmonic voltage L3-N with time 1 % 1s 1s mean float + timestamp 6 13209 r 0x03 & 0x04
615 Monitoring Siemens Modbus TCP maximum 27. harmonic voltage L1-N with time 1 % 1s 1s mean float + timestamp 6 13215 r 0x03 & 0x04
616 Monitoring Siemens Modbus TCP maximum 27. harmonic voltage L2-N with time 1 % 1s 1s mean float + timestamp 6 13221 r 0x03 & 0x04
617 Monitoring Siemens Modbus TCP maximum 27. harmonic voltage L3-N with time 1 % 1s 1s mean float + timestamp 6 13227 r 0x03 & 0x04
618 Monitoring Siemens Modbus TCP maximum 29. harmonic voltage L1-N with time 1 % 1s 1s mean float + timestamp 6 13233 r 0x03 & 0x04
619 Monitoring Siemens Modbus TCP maximum 29. harmonic voltage L2-N with time 1 % 1s 1s mean float + timestamp 6 13239 r 0x03 & 0x04
620 Monitoring Siemens Modbus TCP maximum 29. harmonic voltage L3-N with time 1 % 1s 1s mean float + timestamp 6 13245 r 0x03 & 0x04
621 Monitoring Siemens Modbus TCP maximum 31. harmonic voltage L1-N with time 1 % 1s 1s mean float + timestamp 6 13251 r 0x03 & 0x04
622 Monitoring Siemens Modbus TCP maximum 31. harmonic voltage L2-N with time 1 % 1s 1s mean float + timestamp 6 13257 r 0x03 & 0x04
623 Monitoring Siemens Modbus TCP maximum 31. harmonic voltage L3-N with time 1 % 1s 1s mean float + timestamp 6 13263 r 0x03 & 0x04
624 Monitoring Siemens Modbus TCP maximum fundamental oscillation current L1 with time 1 A 1s 1s mean float + timestamp 6 19001 r 0x03 & 0x04
625 Monitoring Siemens Modbus TCP maximum fundamental oscillation current L2 with time 1 A 1s 1s mean float + timestamp 6 19007 r 0x03 & 0x04
626 Monitoring Siemens Modbus TCP maximum fundamental oscillation current L3 with time 1 A 1s 1s mean float + timestamp 6 19013 r 0x03 & 0x04
627 Monitoring Siemens Modbus TCP maximum 3. harmonic current L1 with time 1 A 1s 1s mean float + timestamp 6 19019 r 0x03 & 0x04
628 Monitoring Siemens Modbus TCP maximum 3. harmonic current L2 with time 1 A 1s 1s mean float + timestamp 6 19025 r 0x03 & 0x04
629 Monitoring Siemens Modbus TCP maximum 3. harmonic current L3 with time 1 A 1s 1s mean float + timestamp 6 19031 r 0x03 & 0x04
630 Monitoring Siemens Modbus TCP maximum 5. harmonic current L1 with time 1 A 1s 1s mean float + timestamp 6 19037 r 0x03 & 0x04
631 Monitoring Siemens Modbus TCP maximum 5. harmonic current L2 with time 1 A 1s 1s mean float + timestamp 6 19043 r 0x03 & 0x04
632 Monitoring Siemens Modbus TCP maximum 5. harmonic current L3 with time 1 A 1s 1s mean float + timestamp 6 19049 r 0x03 & 0x04
633 Monitoring Siemens Modbus TCP maximum 7. harmonic current L1 with time 1 A 1s 1s mean float + timestamp 6 19055 r 0x03 & 0x04
634 Monitoring Siemens Modbus TCP maximum 7. harmonic current L2 with time 1 A 1s 1s mean float + timestamp 6 19061 r 0x03 & 0x04
635 Monitoring Siemens Modbus TCP maximum 7. harmonic current L3 with time 1 A 1s 1s mean float + timestamp 6 19067 r 0x03 & 0x04
636 Monitoring Siemens Modbus TCP maximum 9. harmonic current L1 with time 1 A 1s 1s mean float + timestamp 6 19073 r 0x03 & 0x04
637 Monitoring Siemens Modbus TCP maximum 9. harmonic current L2 with time 1 A 1s 1s mean float + timestamp 6 19079 r 0x03 & 0x04
638 Monitoring Siemens Modbus TCP maximum 9. harmonic current L3 with time 1 A 1s 1s mean float + timestamp 6 19085 r 0x03 & 0x04
639 Monitoring Siemens Modbus TCP maximum 11. harmonic current L1 with time 1 A 1s 1s mean float + timestamp 6 19091 r 0x03 & 0x04
640 Monitoring Siemens Modbus TCP maximum 11. harmonic current L2 with time 1 A 1s 1s mean float + timestamp 6 19097 r 0x03 & 0x04
641 Monitoring Siemens Modbus TCP maximum 11. harmonic current L3 with time 1 A 1s 1s mean float + timestamp 6 19103 r 0x03 & 0x04
642 Monitoring Siemens Modbus TCP maximum 13. harmonic current L1 with time 1 A 1s 1s mean float + timestamp 6 19109 r 0x03 & 0x04
643 Monitoring Siemens Modbus TCP maximum 13. harmonic current L2 with time 1 A 1s 1s mean float + timestamp 6 19115 r 0x03 & 0x04
644 Monitoring Siemens Modbus TCP maximum 13. harmonic current L3 with time 1 A 1s 1s mean float + timestamp 6 19121 r 0x03 & 0x04
645 Monitoring Siemens Modbus TCP maximum 15. harmonic current L1 with time 1 A 1s 1s mean float + timestamp 6 19127 r 0x03 & 0x04
646 Monitoring Siemens Modbus TCP maximum 15. harmonic current L2 with time 1 A 1s 1s mean float + timestamp 6 19133 r 0x03 & 0x04
647 Monitoring Siemens Modbus TCP maximum 15. harmonic current L3 with time 1 A 1s 1s mean float + timestamp 6 19139 r 0x03 & 0x04
648 Monitoring Siemens Modbus TCP maximum 17. harmonic current L1 with time 1 A 1s 1s mean float + timestamp 6 19145 r 0x03 & 0x04
649 Monitoring Siemens Modbus TCP maximum 17. harmonic current L2 with time 1 A 1s 1s mean float + timestamp 6 19151 r 0x03 & 0x04
650 Monitoring Siemens Modbus TCP maximum 17. harmonic current L3 with time 1 A 1s 1s mean float + timestamp 6 19157 r 0x03 & 0x04
651 Monitoring Siemens Modbus TCP maximum 19. harmonic current L1 with time 1 A 1s 1s mean float + timestamp 6 19163 r 0x03 & 0x04
652 Monitoring Siemens Modbus TCP maximum 19. harmonic current L2 with time 1 A 1s 1s mean float + timestamp 6 19169 r 0x03 & 0x04
653 Monitoring Siemens Modbus TCP maximum 19. harmonic current L3 with time 1 A 1s 1s mean float + timestamp 6 19175 r 0x03 & 0x04
654 Monitoring Siemens Modbus TCP maximum 21. harmonic current L1 with time 1 A 1s 1s mean float + timestamp 6 19181 r 0x03 & 0x04
655 Monitoring Siemens Modbus TCP maximum 21. harmonic current L2 with time 1 A 1s 1s mean float + timestamp 6 19187 r 0x03 & 0x04
656 Monitoring Siemens Modbus TCP maximum 21. harmonic current L3 with time 1 A 1s 1s mean float + timestamp 6 19193 r 0x03 & 0x04
657 Monitoring Siemens Modbus TCP maximum 23. harmonic current L1 with time 1 A 1s 1s mean float + timestamp 6 19199 r 0x03 & 0x04
658 Monitoring Siemens Modbus TCP maximum 23. harmonic current L2 with time 1 A 1s 1s mean float + timestamp 6 19205 r 0x03 & 0x04
659 Monitoring Siemens Modbus TCP maximum 23. harmonic current L3 with time 1 A 1s 1s mean float + timestamp 6 19211 r 0x03 & 0x04
660 Monitoring Siemens Modbus TCP maximum 25. harmonic current L1 with time 1 A 1s 1s mean float + timestamp 6 19217 r 0x03 & 0x04
661 Monitoring Siemens Modbus TCP maximum 25. harmonic current L2 with time 1 A 1s 1s mean float + timestamp 6 19223 r 0x03 & 0x04
662 Monitoring Siemens Modbus TCP maximum 25. harmonic current L3 with time 1 A 1s 1s mean float + timestamp 6 19229 r 0x03 & 0x04
663 Monitoring Siemens Modbus TCP maximum 27. harmonic current L1 with time 1 A 1s 1s mean float + timestamp 6 19235 r 0x03 & 0x04
664 Monitoring Siemens Modbus TCP maximum 27. harmonic current L2 with time 1 A 1s 1s mean float + timestamp 6 19241 r 0x03 & 0x04
665 Monitoring Siemens Modbus TCP maximum 27. harmonic current L3 with time 1 A 1s 1s mean float + timestamp 6 19247 r 0x03 & 0x04
666 Monitoring Siemens Modbus TCP maximum 29. harmonic current L1 with time 1 A 1s 1s mean float + timestamp 6 19253 r 0x03 & 0x04
667 Monitoring Siemens Modbus TCP maximum 29. harmonic current L2 with time 1 A 1s 1s mean float + timestamp 6 19259 r 0x03 & 0x04
668 Monitoring Siemens Modbus TCP maximum 29. harmonic current L3 with time 1 A 1s 1s mean float + timestamp 6 19265 r 0x03 & 0x04
669 Monitoring Siemens Modbus TCP maximum 31. harmonic current L1 with time 1 A 1s 1s mean float + timestamp 6 19271 r 0x03 & 0x04
670 Monitoring Siemens Modbus TCP maximum 31. harmonic current L2 with time 1 A 1s 1s mean float + timestamp 6 19277 r 0x03 & 0x04
671 Monitoring Siemens Modbus TCP maximum 31. harmonic current L3 with time 1 A 1s 1s mean float + timestamp 6 19283 r 0x03 & 0x04
672 Monitoring Siemens Modbus TCP connection type 1 1s 1s mean Unsigned long 4 50001 rw 0x03 & 0x04 & 0x10
673 Monitoring Siemens Modbus TCP voltage transformer yes/no 1 1s 1s mean Unsigned long 4 50003 rw 0x03 & 0x04 & 0x10
674 Monitoring Siemens Modbus TCP primary voltage 1 1s 1s mean Unsigned long 4 50005 rw 0x03 & 0x04 & 0x10
675 Monitoring Siemens Modbus TCP secondary voltage 1 1s 1s mean Unsigned long 4 50007 rw 0x03 & 0x04 & 0x10
676 Monitoring Siemens Modbus TCP current transformer yes/no 1 1s 1s mean Unsigned long 4 50009 rw 0x03 & 0x04 & 0x10
677 Monitoring Siemens Modbus TCP primary current 1 1s 1s mean Unsigned long 4 50011 rw 0x03 & 0x04 & 0x10
678 Monitoring Siemens Modbus TCP secondary current 1 1s 1s mean Unsigned long 4 50013 rw 0x03 & 0x04 & 0x10
679 Monitoring Siemens Modbus TCP line frequency settings 1 1s 1s mean Unsigned long 4 50017 rw 0x03 & 0x04 & 0x10
680 Monitoring Siemens Modbus TCP zero point suppression 1 % 1s 1s mean float 4 50019 rw 0x03 & 0x04 & 0x10
681 Monitoring Siemens Modbus TCP under an accrual duration 1 1s 1s mean Unsigned long 4 50021 rw 0x03 & 0x04 & 0x10
682 Monitoring Siemens Modbus TCP synchronization 1 1s 1s mean Unsigned long 4 50023 rw 0x03 & 0x04 & 0x10
683 Monitoring Siemens Modbus TCP DI 0.0 usage 1 1s 1s mean Unsigned long 4 50025 rw 0x03 & 0x04 & 0x10
684 Monitoring Siemens Modbus TCP DI 0.0 pulse edge evaluation 1 1s 1s mean Unsigned long 4 50027 rw 0x03 & 0x04 & 0x10
685 Monitoring Siemens Modbus TCP DI 0.0 usage of the count information 1 1s 1s mean Unsigned long 4 50029 rw 0x03 & 0x04 & 0x10
686 Monitoring Siemens Modbus TCP DI 0.0 valency of the counter information 1 1s 1s mean Unsigned long 4 50031 rw 0x03 & 0x04 & 0x10
687 Monitoring Siemens Modbus TCP DO 0.0 switching groups assignment 1 1s 1s mean Unsigned long 4 50033 rw 0x03 & 0x04 & 0x10
688 Monitoring Siemens Modbus TCP DO 0.0 usage 1 1s 1s mean Unsigned long 4 50035 rw 0x03 & 0x04 & 0x10
689 Monitoring Siemens Modbus TCP DO 0.0 limit allocation 1 1s 1s mean Unsigned long 4 50037 rw 0x03 & 0x04 & 0x10
690 Monitoring Siemens Modbus TCP DO 0.0 pulse edge evaluation 1 1s 1s mean Unsigned long 4 50039 rw 0x03 & 0x04 & 0x10
691 Monitoring Siemens Modbus TCP DO 0.0 source count signal 1 1s 1s mean Unsigned long 4 50041 rw 0x03 & 0x04 & 0x10
692 Monitoring Siemens Modbus TCP DO 0.0 valency of the counter information 1 1s 1s mean Unsigned long 4 50043 rw 0x03 & 0x04 & 0x10
693 Monitoring Siemens Modbus TCP DO 0.0 pulse length 1 1s 1s mean Unsigned long 4 50045 rw 0x03 & 0x04 & 0x10
694 Monitoring Siemens Modbus TCP conversational language 1 1s 1s mean Unsigned long 4 50047 rw 0x03 & 0x04 & 0x10
695 Monitoring Siemens Modbus TCP phase labels IEC/UL 1 1s 1s mean Unsigned long 4 50049 rw 0x03 & 0x04 & 0x10
696 Monitoring Siemens Modbus TCP universal counter 1 source 1 1s 1s mean Unsigned long 4 50051 rw 0x03 & 0x04 & 0x10
697 Monitoring Siemens Modbus TCP display update cycle 1 1s 1s mean Unsigned long 4 50053 rw 0x03 & 0x04 & 0x10
698 Monitoring Siemens Modbus TCP display contrast 1 1s 1s mean Unsigned long 4 50055 rw 0x03 & 0x04 & 0x10
699 Monitoring Siemens Modbus TCP display brightness 1 1s 1s mean Unsigned long 4 50057 rw 0x03 & 0x04 & 0x10
700 Monitoring Siemens Modbus TCP display brightness is reduced 1 1s 1s mean Unsigned long 4 50059 rw 0x03 & 0x04 & 0x10
701 Monitoring Siemens Modbus TCP brightness duration 1 1s 1s mean Unsigned long 4 50061 rw 0x03 & 0x04 & 0x10
702 Monitoring Siemens Modbus TCP limit 0 ON/OFF 1 1s 1s mean Unsigned long 4 50063 rw 0x03 & 0x04 & 0x10
703 Monitoring Siemens Modbus TCP limit 0 hysteresis 1 % 1s 1s mean float 4 50065 rw 0x03 & 0x04 & 0x10
704 Monitoring Siemens Modbus TCP limit 0 delay 1 s 1s 1s mean Unsigned long 4 50067 rw 0x03 & 0x04 & 0x10
705 Monitoring Siemens Modbus TCP limit 0 source 1 1s 1s mean Unsigned long 4 50071 rw 0x03 & 0x04 & 0x10
706 Monitoring Siemens Modbus TCP limit 0 value 1 1s 1s mean float 4 50073 rw 0x03 & 0x04 & 0x10
707 Monitoring Siemens Modbus TCP limit 0 mode ?|< 1 1s 1s mean Unsigned long 4 50075 rw 0x03 & 0x04 & 0x10
708 Monitoring Siemens Modbus TCP limit 1 ON/OFF 1 1s 1s mean Unsigned long 4 50077 rw 0x03 & 0x04 & 0x10
709 Monitoring Siemens Modbus TCP limit 1 hysteresis 1 % 1s 1s mean float 4 50079 rw 0x03 & 0x04 & 0x10
710 Monitoring Siemens Modbus TCP limit 1 delay 1 s 1s 1s mean Unsigned long 4 50081 rw 0x03 & 0x04 & 0x10
711 Monitoring Siemens Modbus TCP limit 1 source 1 1s 1s mean Unsigned long 4 50085 rw 0x03 & 0x04 & 0x10
712 Monitoring Siemens Modbus TCP limit 1 value 1 1s 1s mean float 4 50087 rw 0x03 & 0x04 & 0x10
713 Monitoring Siemens Modbus TCP limit 1 mode ?|< 1 1s 1s mean Unsigned long 4 50089 rw 0x03 & 0x04 & 0x10
714 Monitoring Siemens Modbus TCP limit 2 ON/OFF 1 1s 1s mean Unsigned long 4 50091 rw 0x03 & 0x04 & 0x10
715 Monitoring Siemens Modbus TCP limit 2 hysteresis 1 % 1s 1s mean float 4 50093 rw 0x03 & 0x04 & 0x10
716 Monitoring Siemens Modbus TCP limit 2 delay 1 s 1s 1s mean Unsigned long 4 50095 rw 0x03 & 0x04 & 0x10
717 Monitoring Siemens Modbus TCP limit 2 source 1 1s 1s mean Unsigned long 4 50099 rw 0x03 & 0x04 & 0x10
718 Monitoring Siemens Modbus TCP limit 2 value 1 1s 1s mean float 4 50101 rw 0x03 & 0x04 & 0x10
719 Monitoring Siemens Modbus TCP limit 2 mode ?|< 1 1s 1s mean Unsigned long 4 50103 rw 0x03 & 0x04 & 0x10
720 Monitoring Siemens Modbus TCP limit 3 ON/OFF 1 1s 1s mean Unsigned long 4 50105 rw 0x03 & 0x04 & 0x10
721 Monitoring Siemens Modbus TCP limit 3 hysteresis 1 % 1s 1s mean float 4 50107 rw 0x03 & 0x04 & 0x10
722 Monitoring Siemens Modbus TCP limit 3 delay 1 s 1s 1s mean Unsigned long 4 50109 rw 0x03 & 0x04 & 0x10
723 Monitoring Siemens Modbus TCP limit 3 source 1 1s 1s mean Unsigned long 4 50113 rw 0x03 & 0x04 & 0x10
724 Monitoring Siemens Modbus TCP limit 3 value 1 1s 1s mean float 4 50115 rw 0x03 & 0x04 & 0x10
725 Monitoring Siemens Modbus TCP limit 3 mode ?|< 1 1s 1s mean Unsigned long 4 50117 rw 0x03 & 0x04 & 0x10
726 Monitoring Siemens Modbus TCP limit 4 ON/OFF 1 1s 1s mean Unsigned long 4 50119 rw 0x03 & 0x04 & 0x10
727 Monitoring Siemens Modbus TCP limit 4 hysteresis 1 % 1s 1s mean float 4 50121 rw 0x03 & 0x04 & 0x10
728 Monitoring Siemens Modbus TCP limit 4 delay 1 s 1s 1s mean Unsigned long 4 50123 rw 0x03 & 0x04 & 0x10
729 Monitoring Siemens Modbus TCP limit 4 source 1 1s 1s mean Unsigned long 4 50127 rw 0x03 & 0x04 & 0x10
730 Monitoring Siemens Modbus TCP limit 4 value 1 1s 1s mean float 4 50129 rw 0x03 & 0x04 & 0x10
731 Monitoring Siemens Modbus TCP limit 4 mode ?|< 1 1s 1s mean Unsigned long 4 50131 rw 0x03 & 0x04 & 0x10
732 Monitoring Siemens Modbus TCP limit 5 ON/OFF 1 1s 1s mean Unsigned long 4 50133 rw 0x03 & 0x04 & 0x10
733 Monitoring Siemens Modbus TCP limit 5 hysteresis 1 % 1s 1s mean float 4 50135 rw 0x03 & 0x04 & 0x10
734 Monitoring Siemens Modbus TCP limit 5 delay 1 s 1s 1s mean Unsigned long 4 50137 rw 0x03 & 0x04 & 0x10
735 Monitoring Siemens Modbus TCP limit 5 source 1 1s 1s mean Unsigned long 4 50141 rw 0x03 & 0x04 & 0x10
736 Monitoring Siemens Modbus TCP limit 5 value 1 1s 1s mean float 4 50143 rw 0x03 & 0x04 & 0x10
737 Monitoring Siemens Modbus TCP limit 5 mode ?|< 1 1s 1s mean Unsigned long 4 50145 rw 0x03 & 0x04 & 0x10
738 Monitoring Siemens Modbus TCP limit 6 ON/OFF 1 1s 1s mean Unsigned long 4 50147 rw 0x03 & 0x04 & 0x10
739 Monitoring Siemens Modbus TCP limit 6 hysteresis 1 % 1s 1s mean float 4 50149 rw 0x03 & 0x04 & 0x10
740 Monitoring Siemens Modbus TCP limit 6 delay 1 s 1s 1s mean Unsigned long 4 50151 rw 0x03 & 0x04 & 0x10
741 Monitoring Siemens Modbus TCP limit 6 source 1 1s 1s mean Unsigned long 4 50155 rw 0x03 & 0x04 & 0x10
742 Monitoring Siemens Modbus TCP limit 6 value 1 1s 1s mean float 4 50157 rw 0x03 & 0x04 & 0x10
743 Monitoring Siemens Modbus TCP limit 6 mode ?|< 1 1s 1s mean Unsigned long 4 50159 rw 0x03 & 0x04 & 0x10
744 Monitoring Siemens Modbus TCP limit 7 ON/OFF 1 1s 1s mean Unsigned long 4 50161 rw 0x03 & 0x04 & 0x10
745 Monitoring Siemens Modbus TCP limit 7 hysteresis 1 % 1s 1s mean float 4 50163 rw 0x03 & 0x04 & 0x10
746 Monitoring Siemens Modbus TCP limit 7 delay 1 s 1s 1s mean Unsigned long 4 50165 rw 0x03 & 0x04 & 0x10
747 Monitoring Siemens Modbus TCP limit 7 source 1 1s 1s mean Unsigned long 4 50169 rw 0x03 & 0x04 & 0x10
748 Monitoring Siemens Modbus TCP limit 7 value 1 1s 1s mean float 4 50171 rw 0x03 & 0x04 & 0x10
749 Monitoring Siemens Modbus TCP limit 7 mode ?|< 1 1s 1s mean Unsigned long 4 50173 rw 0x03 & 0x04 & 0x10
750 Monitoring Siemens Modbus TCP limit 8 ON/OFF 1 1s 1s mean Unsigned long 4 50175 rw 0x03 & 0x04 & 0x10
751 Monitoring Siemens Modbus TCP limit 8 hysteresis 1 % 1s 1s mean float 4 50177 rw 0x03 & 0x04 & 0x10
752 Monitoring Siemens Modbus TCP limit 8 delay 1 s 1s 1s mean Unsigned long 4 50179 rw 0x03 & 0x04 & 0x10
753 Monitoring Siemens Modbus TCP limit 8 source 1 1s 1s mean Unsigned long 4 50183 rw 0x03 & 0x04 & 0x10
754 Monitoring Siemens Modbus TCP limit 8 value 1 1s 1s mean float 4 50185 rw 0x03 & 0x04 & 0x10
755 Monitoring Siemens Modbus TCP limit 8 mode ?|< 1 1s 1s mean Unsigned long 4 50187 rw 0x03 & 0x04 & 0x10
756 Monitoring Siemens Modbus TCP limit 9 ON/OFF 1 1s 1s mean Unsigned long 4 50189 rw 0x03 & 0x04 & 0x10
757 Monitoring Siemens Modbus TCP limit 9 hysteresis 1 % 1s 1s mean float 4 50191 rw 0x03 & 0x04 & 0x10
758 Monitoring Siemens Modbus TCP limit 9 delay 1 s 1s 1s mean Unsigned long 4 50193 rw 0x03 & 0x04 & 0x10
759 Monitoring Siemens Modbus TCP limit 9 source 1 1s 1s mean Unsigned long 4 50197 rw 0x03 & 0x04 & 0x10
760 Monitoring Siemens Modbus TCP limit 9 value 1 1s 1s mean float 4 50199 rw 0x03 & 0x04 & 0x10
761 Monitoring Siemens Modbus TCP limit 9 mode ?|< 1 1s 1s mean Unsigned long 4 50201 rw 0x03 & 0x04 & 0x10
762 Monitoring Siemens Modbus TCP limit 10 ON/OFF 1 1s 1s mean Unsigned long 4 50203 rw 0x03 & 0x04 & 0x10
763 Monitoring Siemens Modbus TCP limit 10 hysteresis 1 % 1s 1s mean float 4 50205 rw 0x03 & 0x04 & 0x10
764 Monitoring Siemens Modbus TCP limit 10 delay 1 s 1s 1s mean Unsigned long 4 50207 rw 0x03 & 0x04 & 0x10
765 Monitoring Siemens Modbus TCP limit 10 source 1 1s 1s mean Unsigned long 4 50211 rw 0x03 & 0x04 & 0x10
766 Monitoring Siemens Modbus TCP limit 10 value 1 1s 1s mean float 4 50213 rw 0x03 & 0x04 & 0x10
767 Monitoring Siemens Modbus TCP limit 10 mode ?|< 1 1s 1s mean Unsigned long 4 50215 rw 0x03 & 0x04 & 0x10
768 Monitoring Siemens Modbus TCP limit 11 ON/OFF 1 1s 1s mean Unsigned long 4 50217 rw 0x03 & 0x04 & 0x10
769 Monitoring Siemens Modbus TCP limit 11 hysteresis 1 % 1s 1s mean float 4 50219 rw 0x03 & 0x04 & 0x10
770 Monitoring Siemens Modbus TCP limit 11 delay 1 s 1s 1s mean Unsigned long 4 50221 rw 0x03 & 0x04 & 0x10
771 Monitoring Siemens Modbus TCP limit 11 source 1 1s 1s mean Unsigned long 4 50225 rw 0x03 & 0x04 & 0x10
772 Monitoring Siemens Modbus TCP limit 11 value 1 1s 1s mean float 4 50227 rw 0x03 & 0x04 & 0x10
773 Monitoring Siemens Modbus TCP limit 11 mode ?|< 1 1s 1s mean Unsigned long 4 50229 rw 0x03 & 0x04 & 0x10
774 Monitoring Siemens Modbus TCP date format 1 1s 1s mean Unsigned long 4 50231 rw 0x03 & 0x04 & 0x10
775 Monitoring Siemens Modbus TCP daylight saving time 1 1s 1s mean Unsigned long 4 50233 rw 0x03 & 0x04 & 0x10
776 Monitoring Siemens Modbus TCP time zone 1 min 1s 1s mean long 4 50235 rw 0x03 & 0x04 & 0x10
777 Monitoring Siemens Modbus TCP mediation time moving averages 1 s 1s 1s mean Unsigned long 4 50237 rw 0x03 & 0x04 & 0x10
778 Monitoring Siemens Modbus TCP reactive power numbers used 1 1s 1s mean Unsigned long 4 50239 rw 0x03 & 0x04 & 0x10
779 Monitoring Siemens Modbus TCP universal counter 1 DI-count signal 1 1s 1s mean Unsigned long 4 50241 rw 0x03 & 0x04 & 0x10
780 Monitoring Siemens Modbus TCP invert current L1 1 1s 1s mean Unsigned long 4 50243 rw 0x03 & 0x04 & 0x10
781 Monitoring Siemens Modbus TCP invert current L2 1 1s 1s mean Unsigned long 4 50245 rw 0x03 & 0x04 & 0x10
782 Monitoring Siemens Modbus TCP invert current L3 1 1s 1s mean Unsigned long 4 50247 rw 0x03 & 0x04 & 0x10
783 Monitoring Siemens Modbus TCP current lower limit for hourmeter 1 % 1s 1s mean Unsigned long 4 50249 rw 0x03 & 0x04 & 0x10
784 Monitoring Siemens Modbus TCP universal counter 1 source 1 1s 1s mean Unsigned long 4 50251 rw 0x03 & 0x04 & 0x10
785 Monitoring Siemens Modbus TCP universal counter 2 DI-count signal 1 1s 1s mean Unsigned long 4 50253 rw 0x03 & 0x04 & 0x10
786 Monitoring Siemens Modbus TCP digital input parameter 1 1s 1s mean Unsigned long 14 61167 rw 0x03 & 0x04 & 0x10
787 Monitoring Siemens Modbus TCP digital output parameter 1 1s 1s mean stOutputPara 14 61175 rw 0x03 & 0x04 & 0x10
788 Monitoring Siemens Modbus TCP event recording parameters 1 1s 1s mean stEventPara 16 62101 rw 0x03 & 0x04 & 0x10
789 Monitoring Siemens Modbus TCP logically linked limit parameters 1 1s 1s mean stCombLimitPara 54 62301 rw 0x03 & 0x04 & 0x10
790 Monitoring Siemens Modbus TCP IP-address 1 1s 1s mean Unsigned long 4 63001 rw 0x03 & 0x04 & 0x10
791 Monitoring Siemens Modbus TCP subnet mask 1 1s 1s mean Unsigned long 4 63003 rw 0x03 & 0x04 & 0x10
792 Monitoring Siemens Modbus TCP gateway 1 1s 1s mean Unsigned long 4 63005 rw 0x03 & 0x04 & 0x10
793 Monitoring Siemens Modbus TCP bootloader version 1 1s 1s mean Unsigned long 4 63007 r 0x03 & 0x04
794 Monitoring Siemens Modbus TCP password protection ON/OFF 1 1s 1s mean Unsigned long 4 63009 r 0x03 & 0x04
795 Monitoring Siemens Modbus TCP date of manufacture 1 1s 1s mean Unsigned long 4 63011 r 0x03 & 0x04
796 Monitoring Siemens Modbus TCP ethernet protocol 1 1s 1s mean Unsigned long 4 63015 rw 0x03 & 0x04 & 0x10
797 Monitoring Siemens Modbus TCP protocol module interface 1 1 1s 1s mean Unsigned long 4 63017 rw 0x03 & 0x04 & 0x10
798 Monitoring Siemens Modbus TCP address module interface 1 1 1s 1s mean Unsigned long 4 63019 rw 0x03 & 0x04 & 0x10
799 Monitoring Siemens Modbus TCP baudrate module interface 1 1 1s 1s mean Unsigned long 4 63021 rw 0x03 & 0x04 & 0x10
800 Monitoring Siemens Modbus TCP format module interface 1 1 1s 1s mean Unsigned long 4 63023 rw 0x03 & 0x04 & 0x10
801 Monitoring Siemens Modbus TCP response time module interface 1 1 ms 1s 1s mean Unsigned long 4 63025 rw 0x03 & 0x04 & 0x10
802 Monitoring Siemens Modbus TCP protocol module interface 2 1 1s 1s mean Unsigned long 4 63033 rw 0x03 & 0x04 & 0x10
803 Monitoring Siemens Modbus TCP address module interface 2 1 1s 1s mean Unsigned long 4 63035 rw 0x03 & 0x04 & 0x10
804 Monitoring Siemens Modbus TCP baudrate module interface 2 1 1s 1s mean Unsigned long 4 63037 rw 0x03 & 0x04 & 0x10
805 Monitoring Siemens Modbus TCP format module interface 2 1 1s 1s mean Unsigned long 4 63039 rw 0x03 & 0x04 & 0x10
806 Monitoring Siemens Modbus TCP response time module interface 2 1 ms 1s 1s mean Unsigned long 4 63041 rw 0x03 & 0x04 & 0x10
807 Monitoring Siemens Modbus TCP TCP/IP-Port gateway module interface 1 1 ms 1s 1s mean Unsigned long 4 63043 rw 0x03 & 0x04 & 0x10
808 Monitoring Siemens Modbus TCP TCP/IP-Port gateway module interface 2 1 ms 1s 1s mean Unsigned long 4 63045 rw 0x03 & 0x04 & 0x10
809 Monitoring Siemens Modbus TCP profibus ID PAC4200 1 1s 1s mean Unsigned long 4 63065 r 0x03 & 0x04
810 Monitoring Siemens Modbus TCP I&M-data PAC4200 1 1s 1s mean stIM0 54 64001 r(w) 0x03 & 0x04
811 Monitoring Siemens Modbus TCP I&M 0 to I&M 4-data PAC4200 1 1s 1s mean stIM14 178 64028 rw 0x03 & 0x04 & 0x10
812 Monitoring Siemens Modbus TCP I&M-data module interface 1 1 1s 1s mean stIM0- 54 64117 r(w) 0x03 & 0x04
813 Monitoring Siemens Modbus TCP I&M-data module interface 2 1 1s 1s mean stIM0 54 64144 r(w) 0x03 & 0x04
814 Monitoring Siemens Modbus TCP reset the maximum values 1 1s 1s mean Unsigned short 2 60002 w 0x06
815 Monitoring Siemens Modbus TCP reset the minimum values 1 1s 1s mean Unsigned short 2 60003 w 0x06
816 Monitoring Siemens Modbus TCP reset the energy meter 1 1s 1s mean Unsigned short 2 60004 w 0x06
817 Monitoring Siemens Modbus TCP synchronization of the measurement period 1 1s 1s mean Unsigned short 2 60005 w 0x06
818 Monitoring Siemens Modbus TCP tariff switch 1 1s 1s mean Unsigned short 2 60006 w 0x06
819 Monitoring Siemens Modbus TCP Acknowledge the diagnostic bit 1 1s 1s mean Unsigned short 2 60007 w 0x06
820 Monitoring Siemens Modbus TCP outputs switch (if configured) 1 1s 1s mean Unsigned short 2 60008 w 0x06
821 Monitoring Siemens Modbus TCP power on command vector group 1 1s 1s mean Unsigned short 2 60009 w 0x06
822 Monitoring Siemens Modbus TCP reset the daily energy meters 1 1s 1s mean Unsigned short 2 60010 w 0x06
823 Monitoring Siemens Modbus TCP reset the load input record 1 1s 1s mean Unsigned short 2 60011 w 0x06
824 Monitoring Siemens Modbus TCP reset the energy record 1 1s 1s mean Unsigned short 2 60012 w 0x06
825 Monitoring Siemens Modbus TCP set the standard event-recording conditions 1 1s 1s mean Unsigned short 2 60013 w 0x06
826 Monitoring Siemens Modbus TCP set the standard I/O parameters 1 1s 1s mean Unsigned short 2 60014 w 0x06
827 Monitoring Siemens Modbus TCP increment date / time 1 1s 1s mean Unsigned long 4 65292 w 0x10

View file

@ -7,9 +7,11 @@ import csv
from datetime import datetime
import os
sqlerr = "INSERT INTO %s (DateTime,Type,error) VALUES (\'%s\',%s,%s)"
sqlnor = "INSERT INTO %s (DateTime,Type,cardnumber,customernumber,plug,meterreading) VALUES (\'%s\',%s,%s,%s,%s,%s)"
folder = 'pCharger'
number = 1
sqlerr = "INSERT INTO %s (DateTime,Type,error) VALUES (\'%s\',%s,%s);"
sqlnor = "INSERT INTO %s (DateTime,Type,cardnumber,customernumber,plug,meterreading) VALUES (\'%s\',%s,%s,%s,%s,%s);"
folder = 'I:\Rauch\pCharger0%s'
def clean(list):
'''
@ -56,7 +58,7 @@ def generateSQL(folder):
try:
for row in csv_data:
row = clean(row)
row[0] = "P-Charger_%s" % row[0]
row[0] = "P-Charger_0%s" % number #row[0]
row[1] = makeDatetime(row[1])
row[3] = int(row[3], 16).__str__()
if row[2] not in 'SE':
@ -66,5 +68,6 @@ def generateSQL(folder):
print sqlerr % tuple(row)
except:
continue
generateSQL(folder)
for i in range(1,8):
number = i
generateSQL('I:\Rauch\pCharger%s' % '0{0}'.format(number))

View file

@ -16,10 +16,16 @@ conf = c.readConf()
### Modbus ###
sw = Switch(MODBUS)
queue, query = sw.initialisiere()
sw.run()
print 'run'
print '\tTEST-QUERY:\t', query
print '\tTEST-QUEUE:\t', queue
sw.start()
while True:
query.put(1)
query.put(801)
query.put(3001)
query.put(50235)
query.put(797)
query.put(203)
sleep(0.5)
### Sym2Lib test ###